background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           www.e2s.com              Tel: +44 (0)208 743 8880 

Document No. D202-00-211-IS           Issue 5           16-12-2022                         Sheet 5 of 7                                                                                            

 

Wiring Diagram for 8-Way DIN Rail 
 

 

Fig. 4 DIN Rail in Base 

 

Wiring Diagram for 6-Way PCB Terminal Board 
 
 
 
 
 

 

 
 
 
 

Fig. 5 PCB Terminal Block in Base

 

 
See  section  13  and  page  9  for  details  of  adding  Series  and 
EOL  devices  on  the  PCB.  This  can  either  be  done  at  the 
order stage or added to the correct terminal blocks afterward 
(see example  on  sheet 7).  All  devices must comply  with  the 
requirements stipulated in section 13. 

 

12) Testing unit operation 

 

The push button types -PB -PT and -PM are all operated by 
pressing in the main plunger down activating the switch.  
 

PB – Dual Action Push Button 

 
The  -PB  plunger  needs  to  be  firstly  twisted  by  90  degrees 
clockwise  to  position  shown  and  then pressed in.  There  will 
be  a  click  sound  to  indicate  positive  engagement  and  the 
plunger will stay in place. 
 

 

 

 

Fig 6 -PB Version Twist and Push Action 

 
On -PB versions, the plunger will remain in position until the 
unit  is  reset.  This  is  done  by  pulling  the  plunger  back  up  to 
the start position shown in fig 6. Then the plunger is twisted 
back 90 degrees anti-clockwise to the stop. 
 

PM – Momentary Push Button 

 
The -PM needs to have the protective flip lid opened first and 
then the main plunger pressed in. There will be a click sound 
to indicate positive engagement, the plunger will spring back 
up if not held pressed. 
 

 

Fig 7 -PM Version Push Action 

 
On  –PM  versions  the  operation  is  momentary  and  as  such 
the plunger will reset automatically once the pressure on the 
plunger is released. 
 

PT – Tool Reset Push Button 

 
The -PT needs to have the protective flip lid opened first and 
then the main plunger pressed in. There will be a click sound 
to  indicate  positive  engagement  and  the  plunger  will  stay  in 
place. 
 

M/S 1        M/S 2 
+    -           +    - 
1   3           4    6 

SERIES 1     

 

SERIES 2 

          EOL 1    EOL 2

 

Summary of Contents for GNExCP7-PB-S

Page 1: ...rters Electromechanical contactors and motorstarters Ed 2 Issue Date 2014 01 04 The GNExCP7 callpoints are rated as follows Class I Div 2 Group ABCD T6 Ta 55 C to 60 C Class II Div 2 Group FG T4 Ta 55 C to 60 C Class III Div 1 2 Ta 55 C to 60 C 2 2 NEC Class Zone ratings US The GNExCP7 callpoints comply with the following standards UL 60079 0 2017 Ed 6 Explosive Atmospheres Part 0 Equipment Genera...

Page 2: ...s it will only exist for a short time Dust Groupings Group IIIA Combustible Flyings Group IIIB Non conductive Dust Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications ATEx IECEx UKEX 90ºC NEC CEC 125 C IP Rating IP66 67 to EN IEC60529 and IP6X to EN IEC60079 0 EN IEC60079 31 Equipment Category 2G 2D Equipment Protection Level Gb Gc Db Dc Ambient Temperature Range ATEX IECE...

Page 3: ...wire between the two castings is secure and the O ring seal is in place When fitting the flameproof cover ensure the cover is sitting flat and correctly positioned on the base Insert the M6 x 50 stainless steel A4 70 Cap Head cover bolts and fully tighten down tightening torque 3 5Nm ensuring no gap is visible between the cover and base of the enclosure The enclosure is non conductive and may gene...

Page 4: ...CEx UKEX certified adapters 10 Cable Connections Electrical Connections are to be made into the terminal blocks using solid or stranded wire See section 6 of this manual for access to the flameproof enclosure Wires having a cross sectional area between 0 5 mm to 2 5mm AWG 20 14 can be connected to each terminal way If an input and output wire is required the 2 off Live Neutral or terminals can be ...

Page 5: ...ly twisted by 90 degrees clockwise to position shown and then pressed in There will be a click sound to indicate positive engagement and the plunger will stay in place Fig 6 PB Version Twist and Push Action On PB versions the plunger will remain in position until the unit is reset This is done by pulling the plunger back up to the start position shown in fig 6 Then the plunger is twisted back 90 d...

Page 6: ...aximum voltage stated must not be exceeded as the internal resistor modules are rated as compliant with Ex d according to the unit voltage If lower value resistors than seen on table are required it may be possible to configure but seek advice from E2S to ensure compliance is still maintained EOL End of line device resistor ExxxR diode ED1 zener ExxxZ Microswitch 1 M S 1 Microswitch 2 M S 2 The un...

Page 7: ...sidered suitable for use in low demand safety function Random Hardware Failures and Systematic Failures route 2H As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure to close a contact when the call point is struck with specified force Failure to open a contact when the call point is struck with specified force Spurious output despite...

Page 8: ... as shown in Operated condition Terminals 4 5 7 8 closed Terminals 4 5 6 open COM N O N C EOL SER NOTE These can be fitted either by customer or pre installed by E2S at point of order When fitting diodes or zener diodes polarity across devices must be observed Resistor polarity is unimportant SERIES EOL Wiring option shown with EOL series devices acting in parallel 3A Circuit as shown in Unoperate...

Page 9: ...8 1 2 3 4 5 6 7 8 COM N O N C COM N O N C COM N O N C COM N O N C Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condition Terminals...

Page 10: ...n in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condition Terminals 1 4 M S 1 and 5 8 M S 2 closed Terminals 1 3 M S 1 and 5 7 M S 2 open N C N O COM N C SER EOL SER EOL 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and M S 2 open Termi...

Page 11: ... S 1 M S 2 R B Y R B Y R B Y R B Y 5B Circuit as shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed R N POTTS Optional Single or Double Microswitch Circuit shown with Double Microswitch Unit un operated GNExCP7 PCB Version Devices selected only as example On M S 1 Series resistor and EOL Zener diode On M S 2 EOL resistor with no series devic...

Page 12: ...quipment II 2G Ex d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use ...

Page 13: ... d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain hazard...

Reviews: