12) Tone Table 

45

Tone 34

Tone 38

0  0  1  1  0  1

1KHz 1s on, 1s off Intermittent

PFEER Gen. Alarm

Tone 5

Tone 2

1  1  0  1  0  1

Motor Siren - slow rise to 2400Hz

44

Tone 5

Tone 2

0  1  0  1  0  1

1200Hz Continuous

43

Tone 5

Tone 2

1  0  0  1  0  1

Motor Siren - slow rise to 800Hz

42

Tone 5

Tone 2

0  0  0  1  0  1

Motor Siren - slow rise to 1200Hz

41

Tone 27

Tone 31

1  1  1  0  0  1

544Hz (100mS)/440Hz (400mS)
- NF S 32-001

40

Tone 17

Tone 23

0  1  1  0  0  1

800Hz 0.25 sec on, 1 sec off Intermittent

39

Tone 45

Tone 34

1  0  1  0  0  1

2000Hz Continuous

38

Tone 45

Tone 9

0  0  1  0  0  1

1000Hz Continuous - 

PFEER Toxic Gas

37

Tone 5

Tone 35

1  1  0  0  0  1

500-1200Hz 3.75 sec /0.25 sec 
Australian Evac.

36

Tone 5

Tone 36

0  1  0  0  0  1

420Hz @ 0.625 Sec Australian Alert

35

Tone 45

Tone 38

1  0  0  0  0  1

1000 & 2000Hz @ 0.5 sec 

Aletrnating - Signapore

34

Tone 5

Tone 2

0  0  0  0  0  1

745Hz @ 1Hz Intermittent

33

Tone 15

Tone 26

1  1  1  1  1  0

Two tone chime

32

Tone 5

Tone 26

0  1  1  1  1  0

660/1200Hz @ 1Hz Sweeping

31

Tone 5

Tone 2

1  0  1  1  1  0

300Hz Continuous

30

Tone 5

Tone 7

0  0  1  1  1  0

800/1000Hz @ 7Hz Sweeping

29

Tone 5

Tone 2

1  1  0  1  1  0

440Hz Continuous

28

Tone 5

Tone 26

0  1  0  1  1  0

554Hz Continuous

27

Tone 15

Tone 2

1  0  0  1  1  0

Bell

26

Tone 5

Tone 29

0  0  0  1  1  0

2400/2900Hz @ 50Hz Sweeping

25

Tone 5

Tone 29

1  1  1  0  1  0

800/1000Hz @ 50Hz Sweeping

24

Tone 5

Tone 6

0  1  1  0  1  0

800Hz @ 2Hz Intermittent

23

Tone 5

Tone 2

1  0  1  0  1  0

544Hz @ 0.875 sec Intermittent

22

Tone 5

Tone 2

0  0  1  0  1  0

554Hz/440Hz @ 1Hz Alternating

21

Tone 5

Tone 2

1  1  0  0  1  0

660Hz Continuous

20

Tone 5

Tone 2

0  1  0  0  1  0

1.4KHz - 1.6KHz 1s, 1.6KHz - 1.4 
KHz 0.5s - NFC48-265

19

Tone 5

Tone 2

1  0  0  0  1  0

660Hz 1.8 sec on, 1.8 sec off Intermittent

18

Tone 27

Tone 2

0  0  0  0  1  0

544Hz (100mS)/440 Hz (400m/S)
- NF S 32-001

17

Tone 5

Tone 18

1  1  1  1  0  0

660Hz 150mS on, 150mS off Intermittent

16

Tone 5

Tone 2

0  1  1  1  0  0

800Hz Continuous

15

Tone 5

Tone 4

1  0  1  1  0  0

800Hz 0.25 sec on, 1 sec off Intermittent

14

Tone 5

Tone 15

0  0  1  1  0  0

2400Hz @ 1Hz Intermittent

13

Tone 5

Tone 4

1  1  0  1  0  0

800/1000Hz @ 0.875Hz Alternating

12

Tone 5

Tone 2

0  1  0  1  0  0

1000Hz @ 1Hz Intermittent

11

Tone 5

Tone 7

1  0  0  1  0  0

2400/2900Hz @ 2Hz Alternating

10

Tone 2

Tone 15

0  0  0  1  0  0

1200/500Hz @ 1Hz - DIN 

PFEER P.T.A.P.

9

Tone 5

Tone 2

1  1  1  0  0  0

500/1200/500Hz @ 0.3Hz Sweeping

8

Tone 5

Tone 10

0  1  1  0  0  0

2400/2900Hz @ 1Hz Sweeping

7

Tone 5

Tone 7

1  0  1  0  0  0

2400/2900Hz @ 7Hz Sweeping

6

Tone 20

Tone 3

0  0  1  0  0  0

2400Hz Continuous

5

Tone 5

Tone 6

1  1  0  0  0  0

800/1000Hz @ 1Hz Sweeping

4

Tone 5

Tone 2

0  1  0  0  0  0

500/1200Hz @ 0.3Hz sec
Slow Whoop

3

Tone 5

Tone 17

1  0  0  0  0  0

800/1000Hz @ 0.25 sec Alternating

2

1  2  3  4  5  6

Tone 5

Tone 2

0  0  0  0  0  0

340Hz Continuous

1

Stage 3

Stage 2

Switch

Frequency Description

Stage 1

 

Fig. 9 Dip Switch 

 

1=ON; 0=OFF 

Example shown: 100000 = Tone 2 (Default setting) 

 

Summary of Contents for E2xS1FDC024

Page 1: ...31 2013 ed 2 0 2013 11 Certificate No DEMKO 06ATEX 0421554X IECEx ULD 14 0012X The E2XS1 Alarm horn is rated as follows CE Marking Zones Gas Dust Groups and Temperature Classification When connected to an approved system the E2XS1 alarm horn may be installed in Zone 2 explosive gas air mixture not likely to occur in normal operation and if it does it will only exist for a short time Zone 22 explos...

Page 2: ...important that a suitable power supply is used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all the units The input current will vary according to the voltage input level and the frequency of the tone selected The current levels shown above are for the tone resulting in max current draw tone 1 340Hz Continuous 3 Special Conditions ...

Page 3: ...the cable branching temperature may exceed 80ºC Therefore suitable heat resisting cables and cable glands must be used as per table below Ambient Temp 40ºC 45ºC 50ºC 55ºC Min Rating of cables and cable glands 90ºC 95ºC 100ºC 105ºC If a high IP Ingress Protection rating is required then a suitable sealing washer must be fitted under the cable glands or blanking plugs For use in explosive dust atmos...

Page 4: ...ply connect the supply voltage to the L and N supply terminals see fig 4 8 2 2 AC Units Second Third Stage Tone Selection To select the second and third stage tones on the E2xS1 AC sounder Stage two S2 Operation Power L and N Link the Common C and S2 terminal Dip switch alters stage 2 tone Stage three S3 Operation Power L and N Link the Common C and S3 terminals Dip switch alters stage 3 tone Fig ...

Page 5: ...ected for the first stage alarm The sounders can then be switched to sound second and third stage alarm tones The tones are selected by operation of a DIP switch on the PCB for both DC and AC units The tone table on page six shows the switch positions for the 45 tones and which tones are available for the second and third stages To operate the sounder on stage 1 simply connect the supply voltage t...

Page 6: ...0 1 1 0 554Hz Continuous 27 Tone 15 Tone 2 1 0 0 1 1 0 Bell 26 Tone 5 Tone 29 0 0 0 1 1 0 2400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 800Hz 2Hz Intermittent 23 Tone 5 Tone 2 1 0 1 0 1 0 544Hz 0 875 sec Intermittent 22 Tone 5 Tone 2 0 0 1 0 1 0 554Hz 440Hz 1Hz Alternating 21 Tone 5 Tone 2 1 1 0 0 1 0 660Hz Continuous 20 Tone 5 Tone 2...

Page 7: ......