European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                              

www.e2s.com             Fax: +44 (0)20 8740 4200 

Document No. IS4204     Issue:  C                        12-03-06               Sheet 2 of 2 

DC SOUNDERS 

Positive   

 

 

 

Negative  

 

Stage 2   

 

S2 

Stage 3   

 

S3 

 

 

Earth   

 

 
 
 
 
 
 

  
 
 
 

 
POWER SUPPLY SELECTION 

It is important that a suitable power supply is used to run the 
sounders.  The  power  supply  selected  must  have  the 
necessary  capacity  to  provide  the  input  current  to  all  of  the 
sounders connected to the system. 
  

Unit Type 

Input  

 

Input  @ 1kHz 

Max. 

 

 

Voltage   

Current              I/P Volts

 

 
E2xS121EG 

24V DC   

280mA   

30V 

E2xS121EG 

48V DC   

215mA   

58V 

E2xS121EG 

230V AC   

76mA 

 

253V 

E2xS121EG 

120V AC   

142mA   

132V 

 

TONE SELECTION

 

The  E2xS121EG  sounders  have  45  different  tones  that  can 
be selected for the first stage alarm. The sounders can then 
be  switched  to  sound  second  and  third  stage  alarm  tones. 
The  tones  are  selected  by  operation  of  a  DIP  switch on  the 
pcb for both DC and AC units. The tone table opposite shows 
the  switch  positions  for  the  45  tones  and  which  tones  are 
available  for  the  second  and  third  stages.  To  operate  the 
sounder  on  stage  one  simply  connect  the  supply  voltage  to 
the + & – terminals for DC units and the L, N & E terminals 
for AC units.  
 
The  operation  of the  second  and  third  stages is different for 
DC and AC units. 
 
DC Units Second and Third Stage Tone Selection 
To activate the second stage, remotely switch the negative 
supply to the S2 terminal.  To activate the third stage, 
remotely switch the negative supply to the S3 terminal.  
NOTE the DC power supply to the + & - terminals must be 
maintained for 2

nd

 and 3

rd

 stages. 

 
AC Units Second and Third Stage Tone Selection 
To select the second and third stages on the E2xS121EG AC 
sounders the Common (C) terminal must be remotely 
connected to the S2 terminal for the second stage and to the 
S3 terminal for third stage. NOTE the AC power supply to the 
L, N & E terminals must be maintained for 2

nd

 and 3

rd

 stages. 

 

VOLUME CONTROL 

The volume on the E2xS121EG sounder can be set using the 
volume  control  (see  pcb  layouts  on  page  1).  For  maximum 
output  level  the  potentiometer  should  be  set  to  the  fully 
clockwise position. 

 
WARNING – HIGH VOLUME MAY CAUSE HARM TO 

        PERSONNEL IN CLOSE PROXIMITY 

 

TONE SELECTION TABLE 
 

45

Tone 34

Tone 38

0  0  1  1  0  1

1KHz 1s on, 1s off Intermittent

PFEER Gen. Alarm

Tone 5

Tone 2

1  1  0  1  0  1

Motor Siren - slow rise to 2400Hz

44

Tone 5

Tone 2

0  1  0  1  0  1

1200Hz Continuous

43

Tone 5

Tone 2

1  0  0  1  0  1

Motor Siren - slow rise to 800Hz

42

Tone 5

Tone 2

0  0  0  1  0  1

Motor Siren - slow rise to 1200Hz

41

Tone 27

Tone 31

1  1  1  0  0  1

544Hz (100mS)/440Hz (400mS)
- NF S 32-001

40

Tone 17

Tone 23

0  1  1  0  0  1

800Hz 0.25 sec on, 1 sec off Intermittent

39

Tone 45

Tone 34

1  0  1  0  0  1

2000Hz Continuous

38

Tone 45

Tone 9

0  0  1  0  0  1

1000Hz Continuous - 

PFEER Toxic Gas

37

Tone 5

Tone 35

1  1  0  0  0  1

500-1200Hz 3.75 sec /0.25 sec 
Australian Evac.

36

Tone 5

Tone 36

0  1  0  0  0  1

420Hz @ 0.625 Sec Australian Alert

35

Tone 45

Tone 38

1  0  0  0  0  1

1000 & 2000Hz @ 0.5 sec 

Aletrnating - Signapore

34

Tone 5

Tone 2

0  0  0  0  0  1

745Hz @ 1Hz Intermittent

33

Tone 15

Tone 26

1  1  1  1  1  0

Two tone chime

32

Tone 5

Tone 26

0  1  1  1  1  0

660/1200Hz @ 1Hz Sweeping

31

Tone 5

Tone 2

1  0  1  1  1  0

300Hz Continuous

30

Tone 5

Tone 7

0  0  1  1  1  0

800/1000Hz @ 7Hz Sweeping

29

Tone 5

Tone 2

1  1  0  1  1  0

440Hz Continuous

28

Tone 5

Tone 26

0  1  0  1  1  0

554Hz Continuous

27

Tone 15

Tone 2

1  0  0  1  1  0

Bell

26

Tone 5

Tone 29

0  0  0  1  1  0

2400/2900Hz @ 50Hz Sweeping

25

Tone 5

Tone 29

1  1  1  0  1  0

800/1000Hz @ 50Hz Sweeping

24

Tone 5

Tone 6

0  1  1  0  1  0

800Hz @ 2Hz Intermittent

23

Tone 5

Tone 2

1  0  1  0  1  0

544Hz @ 0.875 sec Intermittent

22

Tone 5

Tone 2

0  0  1  0  1  0

554Hz/440Hz @ 1Hz Alternating

21

Tone 5

Tone 2

1  1  0  0  1  0

660Hz Continuous

20

Tone 5

Tone 2

0  1  0  0  1  0

1.4KHz - 1.6KHz 1s, 1.6KHz - 1.4 
KHz 0.5s - NFC48-265

19

Tone 5

Tone 2

1  0  0  0  1  0

660Hz 1.8 sec on, 1.8 sec off Intermittent

18

Tone 27

Tone 2

0  0  0  0  1  0

544Hz (100mS)/440 Hz (400m/S)
- NF S 32-001

17

Tone 5

Tone 18

1  1  1  1  0  0

660Hz 150mS on, 150mS off Intermittent

16

Tone 5

Tone 2

0  1  1  1  0  0

800Hz Continuous

15

Tone 5

Tone 4

1  0  1  1  0  0

800Hz 0.25 sec on, 1 sec off Intermittent

14

Tone 5

Tone 15

0  0  1  1  0  0

2400Hz @ 1Hz Intermittent

13

Tone 5

Tone 4

1  1  0  1  0  0

800/1000Hz @ 0.875Hz Alternating

12

Tone 5

Tone 2

0  1  0  1  0  0

1000Hz @ 1Hz Intermittent

11

Tone 5

Tone 7

1  0  0  1  0  0

2400/2900Hz @ 2Hz Alternating

10

Tone 2

Tone 15

0  0  0  1  0  0

1200/500Hz @ 1Hz - DIN 

PFEER P.T.A.P.

9

Tone 5

Tone 2

1  1  1  0  0  0

500/1200/500Hz @ 0.3Hz Sweeping

8

Tone 5

Tone 10

0  1  1  0  0  0

2400/2900Hz @ 1Hz Sweeping

7

Tone 5

Tone 7

1  0  1  0  0  0

2400/2900Hz @ 7Hz Sweeping

6

Tone 20

Tone 3

0  0  1  0  0  0

2400Hz Continuous

5

Tone 5

Tone 6

1  1  0  0  0  0

800/1000Hz @ 1Hz Sweeping

4

Tone 5

Tone 2

0  1  0  0  0  0

500/1200Hz @ 0.3Hz sec
Slow Whoop

3

Tone 5

Tone 17

1  0  0  0  0  0

800/1000Hz @ 0.25 sec Alternating

2

1  2  3  4  5  6

Tone 5

Tone 2

0  0  0  0  0  0

340Hz Continuous

1

Stage 3

Stage 2

Switch

Frequency Description

Stage 1

 
SWITCH POSITION EXPLANATION  

1 = Switch in the ON position. 
0 = Switch in the OFF position.. 
 

-

+

S2 

 

S3

-

+

S2 

 

S3

S3

S2 

 

+

Stage 3

Stage 2

+

-

-

 