DC SOUNDERS
Positive
+
Negative
-
Stage 2
S2
Stage 3
S3
Earth
E
POWER SUPPLY SELECTION
It is important that a suitable power supply is used to run the
sounders. The power supply selected must have the
necessary capacity to provide the input current to all of the
sounders connected to the system.
Unit Type
Input
Input @ 1kHz
Max.
Voltage
Current I/P Volts
E2xS121EG
24V DC
280mA
30V
E2xS121EG
48V DC
215mA
58V
E2xS121EG
230V AC
76mA
253V
E2xS121EG
120V AC
142mA
132V
TONE SELECTION
The E2xS121EG sounders have 45 different tones that can
be selected for the first stage alarm. The sounders can then
be switched to sound second and third stage alarm tones.
The tones are selected by operation of a DIP switch on the
pcb for both DC and AC units. The tone table opposite shows
the switch positions for the 45 tones and which tones are
available for the second and third stages. To operate the
sounder on stage one simply connect the supply voltage to
the + & – terminals for DC units and the L, N & E terminals
for AC units.
The operation of the second and third stages is different for
DC and AC units.
DC Units Second and Third Stage Tone Selection
To activate the second stage, remotely switch the negative
supply to the S2 terminal. To activate the third stage,
remotely switch the negative supply to the S3 terminal.
NOTE the DC power supply to the + & - terminals must be
maintained for 2
nd
and 3
rd
stages.
AC Units Second and Third Stage Tone Selection
To select the second and third stages on the E2xS121EG AC
sounders the Common (C) terminal must be remotely
connected to the S2 terminal for the second stage and to the
S3 terminal for third stage. NOTE the AC power supply to the
L, N & E terminals must be maintained for 2
nd
and 3
rd
stages.
VOLUME CONTROL
The volume on the E2xS121EG sounder can be set using the
volume control (see pcb layouts on page 1). For maximum
output level the potentiometer should be set to the fully
clockwise position.
WARNING – HIGH VOLUME MAY CAUSE HARM TO
PERSONNEL IN CLOSE PROXIMITY
TONE SELECTION TABLE
45
Tone 34
Tone 38
0 0 1 1 0 1
1KHz 1s on, 1s off Intermittent
-
PFEER Gen. Alarm
Tone 5
Tone 2
1 1 0 1 0 1
Motor Siren - slow rise to 2400Hz
44
Tone 5
Tone 2
0 1 0 1 0 1
1200Hz Continuous
43
Tone 5
Tone 2
1 0 0 1 0 1
Motor Siren - slow rise to 800Hz
42
Tone 5
Tone 2
0 0 0 1 0 1
Motor Siren - slow rise to 1200Hz
41
Tone 27
Tone 31
1 1 1 0 0 1
544Hz (100mS)/440Hz (400mS)
- NF S 32-001
40
Tone 17
Tone 23
0 1 1 0 0 1
800Hz 0.25 sec on, 1 sec off Intermittent
39
Tone 45
Tone 34
1 0 1 0 0 1
2000Hz Continuous
38
Tone 45
Tone 9
0 0 1 0 0 1
1000Hz Continuous -
PFEER Toxic Gas
37
Tone 5
Tone 35
1 1 0 0 0 1
500-1200Hz 3.75 sec /0.25 sec
Australian Evac.
36
Tone 5
Tone 36
0 1 0 0 0 1
420Hz @ 0.625 Sec Australian Alert
35
Tone 45
Tone 38
1 0 0 0 0 1
1000 & 2000Hz @ 0.5 sec
Aletrnating - Signapore
34
Tone 5
Tone 2
0 0 0 0 0 1
745Hz @ 1Hz Intermittent
33
Tone 15
Tone 26
1 1 1 1 1 0
Two tone chime
32
Tone 5
Tone 26
0 1 1 1 1 0
660/1200Hz @ 1Hz Sweeping
31
Tone 5
Tone 2
1 0 1 1 1 0
300Hz Continuous
30
Tone 5
Tone 7
0 0 1 1 1 0
800/1000Hz @ 7Hz Sweeping
29
Tone 5
Tone 2
1 1 0 1 1 0
440Hz Continuous
28
Tone 5
Tone 26
0 1 0 1 1 0
554Hz Continuous
27
Tone 15
Tone 2
1 0 0 1 1 0
Bell
26
Tone 5
Tone 29
0 0 0 1 1 0
2400/2900Hz @ 50Hz Sweeping
25
Tone 5
Tone 29
1 1 1 0 1 0
800/1000Hz @ 50Hz Sweeping
24
Tone 5
Tone 6
0 1 1 0 1 0
800Hz @ 2Hz Intermittent
23
Tone 5
Tone 2
1 0 1 0 1 0
544Hz @ 0.875 sec Intermittent
22
Tone 5
Tone 2
0 0 1 0 1 0
554Hz/440Hz @ 1Hz Alternating
21
Tone 5
Tone 2
1 1 0 0 1 0
660Hz Continuous
20
Tone 5
Tone 2
0 1 0 0 1 0
1.4KHz - 1.6KHz 1s, 1.6KHz - 1.4
KHz 0.5s - NFC48-265
19
Tone 5
Tone 2
1 0 0 0 1 0
660Hz 1.8 sec on, 1.8 sec off Intermittent
18
Tone 27
Tone 2
0 0 0 0 1 0
544Hz (100mS)/440 Hz (400m/S)
- NF S 32-001
17
Tone 5
Tone 18
1 1 1 1 0 0
660Hz 150mS on, 150mS off Intermittent
16
Tone 5
Tone 2
0 1 1 1 0 0
800Hz Continuous
15
Tone 5
Tone 4
1 0 1 1 0 0
800Hz 0.25 sec on, 1 sec off Intermittent
14
Tone 5
Tone 15
0 0 1 1 0 0
2400Hz @ 1Hz Intermittent
13
Tone 5
Tone 4
1 1 0 1 0 0
800/1000Hz @ 0.875Hz Alternating
12
Tone 5
Tone 2
0 1 0 1 0 0
1000Hz @ 1Hz Intermittent
11
Tone 5
Tone 7
1 0 0 1 0 0
2400/2900Hz @ 2Hz Alternating
10
Tone 2
Tone 15
0 0 0 1 0 0
1200/500Hz @ 1Hz - DIN
PFEER P.T.A.P.
9
Tone 5
Tone 2
1 1 1 0 0 0
500/1200/500Hz @ 0.3Hz Sweeping
8
Tone 5
Tone 10
0 1 1 0 0 0
2400/2900Hz @ 1Hz Sweeping
7
Tone 5
Tone 7
1 0 1 0 0 0
2400/2900Hz @ 7Hz Sweeping
6
Tone 20
Tone 3
0 0 1 0 0 0
2400Hz Continuous
5
Tone 5
Tone 6
1 1 0 0 0 0
800/1000Hz @ 1Hz Sweeping
4
Tone 5
Tone 2
0 1 0 0 0 0
500/1200Hz @ 0.3Hz sec
Slow Whoop
3
Tone 5
Tone 17
1 0 0 0 0 0
800/1000Hz @ 0.25 sec Alternating
2
1 2 3 4 5 6
Tone 5
Tone 2
0 0 0 0 0 0
340Hz Continuous
1
Stage 3
Stage 2
Switch
Frequency Description
Stage 1
SWITCH POSITION EXPLANATION
1 = Switch in the ON position.
0 = Switch in the OFF position..
-
+
S2
S3
-
+
S2
S3
S3
S2
+
Stage 3
Stage 2
+
-
-