E2S E2xS121EG Instruction And Service Manual Download Page 1

 

__________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             

www.e2s.com             Fax: +44 (0)20 8740 4200 

Document No. IS4204     Issue:  C                      12-04-06               Sheet 1 of 2 

INSTRUCTION & SERVICE MANUAL 

E2xS121EG SOUNDERS 

For Use In Hazardous Areas 

 
 

 

 

 

 

45 Tones 3 stage Sounder 

 

Automatic Synchronisation 

 

Volume control 

 

IP Rating 

 

Operating Temperature Range 
-20ºC to +55ºC 

 

Unit Type No.

 

    E2xS121EG 

 

Input Voltages:

      DC Units  

10-30V or 48V  

 

 

    AC Units 

120V or 230V  

       

II 3G   EEx nA nL IIC T4 (Tamb. -20ºC to +55°C)

 

Certificate No. 

    DEMKO 06 ATEX 0421554 

 

Group/Category:    

II

 

3G 

 

Zone:

   

   Zone 2 

 
INSTALLATION 

The E2xS121EG sounders must be installed in accordance 
with the relevant parts of the EN60079 standards or the 
equivalent IEC standards. 

Note the units are factory set to 

tone 2 (800/1000Hz alternating at 2Hz) and maximum output

If necessary the unit should be connected to a suitable power 
supply in a safe area to determine what tone pattern and 
output level is required.

 

Flat Washer

Spring Washer

M4 Hex
Socket Screw

 

 
WARNING – DO NOT OPEN WHEN ENERGISED 
 
WARNING – TO AVOID A POSSIBLE ELECTROSTATIC 
 

       CHARGE ONLY CLEAN THE UNIT WITH A 

 

       DAMP CLOTH 

 
E2xS121EG DC PCB Layout

 

 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 
 
E2xS121EG AC PCB Layout 

 
 
 
 
 
 
 
 
 
 

 
 
MOUNTING

 

The E2xS121EG sounder must be mounted using the rotating 
bracket as shown.  

Release screw to rotate 
bracket.

18° Increments

 

WIRING CONECTIONS 

The E2xS121EG sounder has two M20 cable entries one of 
which is fitted with an M20 blanking plug. This should be 
removed if two cable entries are required. Cable entry devices 
shall be used which ensure a minimum ingress protection of 
IP54. 
 
The cable connections are made to the terminal blocks on the 
pcb assembly in the enclosure. On AC units a six way terminal 
block is provided for the Mains Input Supply and a separate 
three way terminal block is provided for selecting the second 
and third stage outputs if required. On DC units a ten way 
terminal block is provided for both the DC supply and the 
second and third stages. 

 

WARNING - ALL ELECTRICAL WIRING MUST BE 

       INSTALLED IN ACCORDANCE WITH THE 
       RELEVANT STANDARDS AND ANY LOCAL 
       CODES THAT MAY APPLY 

 

AC SOUNDERS 

Live 

 

 

Common 

Neutral   

 

Stage 2   

S2 

Earth 

 

 

Stage 3   

S3 

 
 

 
 
 
 
 

S

 S

 S

2

  S

   

  -

   

  

 +

  

 

Tone Selection
DIP Switch

Volume Control
Potentiometer

E2xS121EG DC Sounder
Tone Switch and Volume 
Control Positions

E

   

 E

   

 

 

L

N

C S2 

 

S3

S3

S2 

 

C

N

L

L

N

C

C

N

L

Stage 2
Stage 3

S2 

 

S3

 

Tone Selection
DIP Switch

Volume Control
Potentiometer

S

3

 S

2

 C

N   N

L   L

E   E

E2xS121EG AC Sounder
Tone Switch and Volume 
Control Positions

 

 