5)  Special Conditions of Use 

 

When  used  for  a  Group  III  application,  the  surface  of  the 
enclosure  may  store  electrostatic  charge  and  become  a 
source  of  ignition in applications with  a low relative  humidity 
<~30% relative humidity where the surface is relatively free of 
surface contamination such as dirt, dust, or oil. 
 
Guidance  on  protection  against  the  risk  of  ignition  due  to 
electrostatic discharge can be found in EN TR50404 and IEC 
TR60079-32. 

 

End  user shall  adhere  to  the  manufacturer’s  installation  and 
instruction  when  performing  housekeeping  to  avoid  the 
potential for hazardous electrostatic charges during cleaning, 
by using a damp cloth. 
 
To  maintain  the  ingress  protection  rating  and  mode  of 
protection, the cable entries must be fitted with suitably rated, 
certified  cable  entry  and/or  blanking  devices  during 
installation.  
 
Equipment  with  the  flare  horn  shall  not be  installed  with  the 
flare higher than horizontal (to avoid accumulation of dust). 

 

The equipment incorporates metal parts isolated from earth, 
having capacitance values exceeding the limits permitted in 
the standards of certification. Mounting bracket – 10.33pF; 
Lens guard – 12.33pF. 

 

6)  Product Location and Access 
 

6.1. 

Location and Mounting 

 

The  location  of  the  unit  should  be  made  with  due  regard  to 
the area over which the warning signal must be audible. They 
should  only  be  fixed  to services that  can carry the  weight of 
the unit. 

 

The E2x combined sounder beacon should be secured to any 
flat surface using the three 7mm fixing holes on the stainless 
steel U shaped mounting bracket. See Figure 1. The required 
angle  can  be  achieved  by  loosening  the  two  large  bracket 
screws in the side of the unit, which allow adjustment of the 
unit in steps of 18°. On completion of the installation the two 
large bracket adjustment screws on the side of the unit must 
be  fully  tightened  to  ensure  that  the  unit  cannot  move  in 
service. 

 

 

Fig. 1a Fixing Location for Combined Sounder Beacon Flare 

 

 

Fig. 1b Fixing Location for Combined Sounder Beacon Radial 

 
 

6.2. 

Access to the Enclosure 

 

 

Warning – High voltage may be 
present, risk of electric shock.  
DO NOT open when energised, 
disconnect power before opening. 

 

Warning – Hot surfaces. External 
surfaces and internal components 
may be hot after operation, take 
care when handling the equipment. 

 

To access the enclosure, remove the four M4 posi pan head 
screws, M4 spring and plain washers and withdraw the cover.  

 

 

Fig. 2 Accessing the Enclosure. 

 

To  replace  cover,  check  that  the  ‘O’  ring  seal  is  in  place. 
Carefully push the cover in place. Insert and tighten down M4 
screws,  spring  and plain  washers in  the order  shown  above 
and tighten down. 

 

7)  Selection of Cable, Cable Glands, Blanking 

Elements & Adapters 

 

When  selecting  the  cable  size,  consideration  must  be  given 
to  the  input  current  that  each  unit  draws  (see  Table  1),  the 
number  of  sounders  on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity  to  provide  the  input  current  to  all  of  the  sounders 
connected to the line.  

 

The  dual  entries  can  be  ordered  with  one  of  the  following 
options: 
 
2-off M20 x 1.5 thread 
2-off ½” NPT thread 
1-off M20 x 1.5 & 1-off ½” NPT thread 
 

(Appropriate cable entry devices 
to be customer supplied)  

Beacon 
Housing  

M4 Cover 
Screw 

M4 Spring 
Washer 

M4 Plain 
Washer 

Sounder 
Housing  

Summary of Contents for E2xC1X05R

Page 1: ... Information 3 1 ATEX IECEx UKEx certification The E2xC1X05 combined alarm horn and xenon beacon complies with the following standards Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Explosive Atmospheres Equipment General Requirements EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Ed 5 1 Explosive Atmospheres Equipment Protection by Increased Safety e EN 60079 31 2014 IEC 60079 31 2013 Ed 2 Expl...

Page 2: ... C to 55 C Ex tc IIIC 85 C Dc Ta 20 C to 40 C Ex tc IIIC 100 C Dc Ta 20 C to 55 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classification When connected to an approved system the E2xC1X05 combined alarm horn and xenon beacon may be installed in Area Classification Zone 2 Explosive gas air mixture not likely to occur ...

Page 3: ... any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by loosening the two large bracket screws in the side of the unit which allow adjustment of the unit in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit must be fully tightened to ensure that...

Page 4: ...es must be a maximum cross sectional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws on the sounder PCBA need to be tightened down with a tightening torque of 0 45 Nm 4 Lb in Terminal screws on the beacon PCBA need to be tightened down with a tightening torque of 0 56 Nm 5 Lb in When connecting wires to the terminals great care should be taken to dress the ...

Page 5: ...11 3 2 Beacon Line Monitoring Independent Beacon and Sounder Operation Only The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 9a remove the ve and ve terminal plugs and fit the resistor across the two terminal plugs before refitting them to the PCBA as shown in Fig 9b A spacing of at least 1 16 1 58mm mus...

Page 6: ...c Australian Evac 36 Tone 5 Tone 36 0 1 0 0 0 1 420Hz 0 625 Sec Australian Alert 35 Tone 45 Tone 38 1 0 0 0 0 1 1000 2000Hz 0 5 sec Aletrnating Signapore 34 Tone 5 Tone 2 0 0 0 0 0 1 745Hz 1Hz Intermittent 33 Tone 15 Tone 26 1 1 1 1 1 0 Two tone chime 32 Tone 5 Tone 26 0 1 1 1 1 0 660 1200Hz 1Hz Sweeping 31 Tone 5 Tone 2 1 0 1 1 1 0 300Hz Continuous 30 Tone 5 Tone 7 0 0 1 1 1 0 800 1000Hz 7Hz Swee...

Page 7: ... DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS 05 08 2020 05 08 2020 ve OUT ve OUT EARTH EARTH E E DC E2XC1X05 E2XC1X10 UNITS Line Monitoring Stage 1 Apply power to Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve AC E2XC1X05 E2XC1X10 UNITS Power Live Ne...

Page 8: ...y Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 6...

Page 9: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 10: ...ion Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 ...

Page 11: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...