background image

 

 

 
 
 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D209-00-501-IS

 

Issue 1

 

20-08-22

 

 

Sheet 1 of 6

 

 

INSTRUCTION MANUAL 

E2xC1X05R & E2xC1X05F Combined Sounder & Beacon

 

For use in Hazardous Locations

 

 

 

E2XC1X05F 

E2XC1X05R 

1)  Product Table 

 

 
Ensure the system power supply is capable of providing the maximum current required for all units. Review associated cable 
size, length and quantity of units on each circuit.

 

 

2)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 
 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 HAUT TENSION, RISK DE CHOC. 

ATTENDEZ 5 MINUTES APRES AVOIR 
DEBRANCHE L’ALIMENTATION AVANT 
D’OUVRIR LA BOITIER 

 

3)  Rating & Marking Information 

 

3.1. ATEX / IECEx / UKEx certification 

 
The  E2xC1X05  combined  alarm  horn  and  xenon  beacon 
complies with the following standards: 

Standards 

EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): 

Explosive Atmospheres - Equipment. General Requirements 

EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment Dust Ignition Protection 
by Enclosure "t" 

Ratings 

E2XC1X05 : 
 

Ex ec IIC T3 Gc Ta -20°C to +40°C 
Ex ec IIC T2 Gc Ta -20°C to +55°C 
Ex tc IIIC 85°C Dc Ta -20°C to +40°C 
Ex tc IIIC 100°C Dc Ta -20°C to +55°C 

 
Certificate No. 

DEMKO 06ATEX 0421554X 
IECEx ULD 14.0012X 
UL21UKEX2135X

 

ATEX Mark, Equipment 
Group and Category: 

 

II 3G 
II 3D

 

CE Marking 
 

 

 

UKCA Marking 

 

 

Model 

Nom. 

Voltage 

Voltage Range 

Sounder 

Current 

Beacon 

 Current

 

E2xC1X05FDC024 

E2xC1X05RDC024 

24Vdc 

20-28Vdc 

284mA 

275mA 

E2xC1X05FDC048 

E2xC1X05RDC048 

48Vdc 

42-54Vdc 

146mA 

145mA 

E2xC1X05FAC115 

E2xC1X05RAC115 

115-120Vac 

50/60Hz 

N/- 10% 

104mA 

80mA 

E2xC1X05FAC230 

E2xC1X05RAC230 

220-230Vac 

50/60Hz 

N/- 10% 

54mA 

30mA 

The current levels shown above are for the tone resulting in max. current draw (tone 1 - 340Hz Continuous) 
Table 1: Electrical Ratings. 

Summary of Contents for E2xC1X05R

Page 1: ... Information 3 1 ATEX IECEx UKEx certification The E2xC1X05 combined alarm horn and xenon beacon complies with the following standards Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Explosive Atmospheres Equipment General Requirements EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Ed 5 1 Explosive Atmospheres Equipment Protection by Increased Safety e EN 60079 31 2014 IEC 60079 31 2013 Ed 2 Expl...

Page 2: ... C to 55 C Ex tc IIIC 85 C Dc Ta 20 C to 40 C Ex tc IIIC 100 C Dc Ta 20 C to 55 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classification When connected to an approved system the E2xC1X05 combined alarm horn and xenon beacon may be installed in Area Classification Zone 2 Explosive gas air mixture not likely to occur ...

Page 3: ... any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by loosening the two large bracket screws in the side of the unit which allow adjustment of the unit in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit must be fully tightened to ensure that...

Page 4: ...es must be a maximum cross sectional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws on the sounder PCBA need to be tightened down with a tightening torque of 0 45 Nm 4 Lb in Terminal screws on the beacon PCBA need to be tightened down with a tightening torque of 0 56 Nm 5 Lb in When connecting wires to the terminals great care should be taken to dress the ...

Page 5: ...11 3 2 Beacon Line Monitoring Independent Beacon and Sounder Operation Only The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 9a remove the ve and ve terminal plugs and fit the resistor across the two terminal plugs before refitting them to the PCBA as shown in Fig 9b A spacing of at least 1 16 1 58mm mus...

Page 6: ...c Australian Evac 36 Tone 5 Tone 36 0 1 0 0 0 1 420Hz 0 625 Sec Australian Alert 35 Tone 45 Tone 38 1 0 0 0 0 1 1000 2000Hz 0 5 sec Aletrnating Signapore 34 Tone 5 Tone 2 0 0 0 0 0 1 745Hz 1Hz Intermittent 33 Tone 15 Tone 26 1 1 1 1 1 0 Two tone chime 32 Tone 5 Tone 26 0 1 1 1 1 0 660 1200Hz 1Hz Sweeping 31 Tone 5 Tone 2 1 0 1 1 1 0 300Hz Continuous 30 Tone 5 Tone 7 0 0 1 1 1 0 800 1000Hz 7Hz Swee...

Page 7: ... DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS 05 08 2020 05 08 2020 ve OUT ve OUT EARTH EARTH E E DC E2XC1X05 E2XC1X10 UNITS Line Monitoring Stage 1 Apply power to Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve AC E2XC1X05 E2XC1X10 UNITS Power Live Ne...

Page 8: ...y Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 6...

Page 9: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 10: ...ion Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 ...

Page 11: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Reviews: