E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D173-00-201-IS Issue 4 19/11/2021
S1 - LED Flash Mode Settings (AC & DC)
The Flash Mode Dip Switch can be changed to set the desired
flash pattern
Flash Mode DIP Switch – Shown with 1-OFF, 2-ON, 3-OFF (0 1 0),
This denotes Flash mode 1Hz. For further flash modes refer to
table:
Switch
Setting
Flash Mode
0 0 0
Steady on
1 0 0
Blinking
0 1 0
Flashing 1Hz
*
1 1 0
Flashing 1. Hz
*
0 0 1
Flashing - Double Strike
1 0 1
Flashing - Triple Strike
0 1 1
Flashing 2Hz
*
1 1 1
Flashing - Temporal
1 2 3
ON
•
All models are approved for use as Audible Signal and Visual Appliance
for use as General Signaling: UL464A & CSA C22.2 No 20 -17, UL1638A
•
Type 4 / 4X / 3R / 13, IP66
•
-
2 °C to + °C / -13°F to +131°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
Units can be mounted using the 2-off 10 x 7mm obround holes in the mounting lugs.
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings
Model
Nominal* Voltage
Voltage Range
Nominal Operating Current
#
Beacon
Sounder
DL112HDC024
12V dc
10-14Vdc
79. mA
200mA
24V dc
16-30Vdc
86. mA
200mA
DL112HDC048
48V dc
48-60Vdc
60mA
120mA
DL112HAC11
11 V ac
11 V ac ± 10% 0/60Hz
34mA
100mA
DL112HAC230
230V ac
230V ac ± 10% 0/60Hz
19mA
60mA
*Nominal Voltage, 1Hz Flash Pattern & Tone 12;
#
Worst-case input voltage and worst case flash pattern
Warnings
Attention
: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1
Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit exclusivement être
réalisée par du personnel qualifié, conformément au code national d'électricité américain, NFPA 70 ou CSA 22.1 Code canadien de
l'électricité, première partie, norme de sécurité relative aux installations électriques, Section 32
Attention
: Disconnect from power source before installation or service to prevent electric shock / Débranchez-le de la source
d'alimentation avant l'installation ou l'entretien pour éviter tout choc électrique.
Attention
: Do not paint / Ne pas Peinturer
Summary of Contents for DL112H
Page 10: ...Page left Intentionally blank...
Page 11: ...Page left Intentionally blank...
Page 12: ...Page left Intentionally blank...