ALL DIMENSIONS IN MM

IF IN DOUBT, ASK - 
DO NOT SCALE

2S

warning signals

NTS

D2xC2X05 & D2xC2X10 

COMBINED BEACON & SOUNDER WIRING DIAGRAM

D211-06-601

1

1

OF

R.N.POTTS

R.S. RAIT

B. ISARD

27-06-2019

27-06-2019

27-06-2019

MOD No.

REASON - INITIAL - DATE

ISSUE

1

INTRODUCTION
RSR 02-01-2020

D2x

-

-

+ve OUT

-ve OUT

EARTH

EARTH

+

+

E

E

-
-

-

+

+

+

E
E

+ve IN

+ve OUT

-ve IN

-ve OUT

EARTH IN

EARTH OUT

DC D2XC2X05 / D2XC2X10 UNITS
Line Monitoring

Stage 1: Apply power to Sve & -ve
Stage 2: Apply power to Sve & -ve. Connect Stage 2 to -ve
Stage 3: Apply power to Sve & -ve. Connect Stage 3 to -ve
Stage 4: Apply power to Sve & -ve. Connect Stage 2 and Stage 3 to -ve

AC D2XC2X05 / D2XC2X10 UNITS

Power: Live & Neutral

Stage 1: Apply power to Sounder L & N
Stage 2: Apply power to Sounder L & N. Connect Stage 2 to Common
Stage 3: Apply power to Sounder L & N. Connect Stage 3 to Common
Stage 4: Apply power to Sounder L & N. Connect Stage 2 and Stage 3 to Common

OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,  
REQUIRED MINIMUM VALUES:

R

1

 24VDC : 1KΩ MIN, 2W MIN OR 3K9Ω MIN, 0.5W MIN
 48VDC : 3.9KΩ MIN, 2W MIN OR 15KΩ MIN, 0.5W MIN

L

L

NEUTRAL OUT

LIVE OUT

EARTH

EARTH

N

N

E

E

N
N

N

L

L

L

C
S2
S3
E
E

LIVE IN

LIVE OUT

NEUTRAL IN

NEUTRAL OUT

COMMON

STAGE 2
STAGE 3

EARTH IN

EARTH OUT

S3

S2

STAGE 3

STAGE 2

R

1

R

1

2

UPDATED FORMAT
DH 17-05-2022

WIRING LINKING BEACON & SOUNDER
FACTORY FITTED

TO OPERATE SOUNDER AND BEACON 

INDEPENDENTLY, REMOVE FACTORY 
FITTED WIRES LINKING THE UNITS

Summary of Contents for D2xC2 Series

Page 1: ...WER BEFORE OPENING THE ENCLOSURE Avertissement NE PAS OUVRIR UN PRESENCE D ATMOSPHERE EXPLOSIVE NE PAS OUVRIR ENERGIE DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER Model Nominal Voltage Beacon Current Sounder Current D2xC2X05DC024 20 28Vdc 296mA 313mA D2x...

Page 2: ...a 40 C to 50 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X05DC048 X05AC115 X05AC230 Class I Div 2 ABCD T3 Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C to 50 C D2xC2 X10DC048 X10AC115 X10AC230 Class I Div 2 ABCD T2B Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50 C Class II Div 2 FG T6 Ta 40 C to 40 C Class III Div 1 2 Ta 40 C ...

Page 3: ...test issue of the following standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres 5 Special Conditions for Safe Use Special Condition for safe Us...

Page 4: ...For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT stopping plugs should be greased before insertion 8 Cable Connections Electrical connections are to be made into the terminal blocks on the PCBA located in the enclosure See section 6 of this man...

Page 5: ...End Of Line Monitoring DC Units Only On D2xC2 DC units dc reverse line monitoring can be used if required All DC units have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have the following values Min Resistance Min Power 24V DC 3 9KΩ 0 5W 1KΩ 2W 48V DC 15KΩ 0 5W 3 9KΩ...

Page 6: ...fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixings MUST be fitted in the order shown above 15 DIP Switch Please note that the D2xC2X05DC024 D2xC2X10DC024 beacon PCBAs have a DIP Switch that is NOT customer configurable This should only ever be set to 00 Fig 12 DIP Switch setting 00 16 Maintenance Overhaul Repair Maintenance repair and overhaul of the ...

Page 7: ... 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 300Hz Continuous 0 1 1 1 0 0 44 24 35 16 440Hz Continuous 1 1 1 1 0 0 44 24 35 17 470Hz Continuous 0 0 0 0 1 0 44 24 35 18 ...

Page 8: ...3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz Sweeping 1 0 1 0 1 1 57 24 12 55 800 1000Hz 50Hz Sweeping 0 1 1 0 1 1 54 24 12 56 2400 2900Hz 7Hz Sweeping 1 1 1 0 1 1 57 24 12 57 2400 2900Hz 1Hz Sweeping 0 0 0 1 1 1 47 24 12 58 2400 2900Hz 50Hz Swe...

Page 9: ...st setting see volume control section The sounder section produces a sound pressure level above 75dB A at 10 feet For fire alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet anechoic room UL464 92 2dB A at 10 feet reverberation room 3 Surge Current Rat...

Page 10: ...2 and Stage 3 to ve AC D2XC2X05 D2XC2X10 UNITS Power Live Neutral Stage 1 Apply power to Sounder L N Stage 2 Apply power to Sounder L N Connect Stage 2 to Common Stage 3 Apply power to Sounder L N Connect Stage 3 to Common Stage 4 Apply power to Sounder L N Connect Stage 2 and Stage 3 to Common OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED REQUIRED MINIMUM VALUES R1 24VDC 1KΩ MIN 2W MIN OR 3...

Page 11: ...therlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 3...

Page 12: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 13: ... Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Com...

Page 14: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Reviews: