E2S D2xC1 Instruction And Service Manual Download Page 2

__________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. D189-00-001-IS     Issue:  9                        01-06-16               Sheet 2 of 7 

 

Maximum Surface Temperature for Dust Applications: 

 

90ºC 

 

3.2 Class / Zone ratings US 

 

The D2xS1 alarm horn complies with the following standards: 

 

ANSI/UL 60079-0-2013 
ANSI/UL60079-15-2013 
ISA60079-31-2013 

 

The D2X Alarm horn is rated as follows: 

 

Class I, Zone 2   AEx nA IIC T4 Gc (Ta -40ºC to +50°C) 
Zone 22  

AEx tc IIIC T90°C Dc (Ta -40ºC to +50°C) 

 

Installation must be carried out in compliance with the National 
Electric Code. 
 

3.3 Class / Zone ratings Canada

 

 
The D2xS1 alarm horn complies with the following standards: 
 
CAN/CSA C22.2 No. 60079-0:11 
CAN/CSA C22.2 No. 60079-15:12 
CAN/CSA C22.2 No. 60079-31:12 
 
The D2XS1 Alarm horn is rated as follows: 
 
Ex nA IIC T4 Gc X (Ta -40ºC to +50°C) 
Ex tc IIIC T90°C Dc (Ta -40ºC to +50°C) 
Class II Div 2 EFG T5 (Ta -40ºC to +50°C) 
 
Installation must be carried out in compliance with the 
Canadian Electric Code 

 
3.4 Class / Division Ratings for US and Canada 

 
The D2xS1 alarm horn complies with the following standards:-  
 
ANSI/ISA 12.12.01-2013 
CSA C22.2 No. 213-M1987 
CSA C22.2 No. 157-92:2006 
 
The D2XS1 Alarm horn is rated as follows: 
 
Class I Div 2 

ABCD T3C  

Ta -40ºC to +70ºC 

Class I Div 2 

ABCD T4  

Ta -40ºC to +65ºC 

Class I Div 2 

ABCD T4A  

Ta -40ºC to +50ºC 

Class II Div 2 

FG T5  

Ta -40ºC to +50ºC 

Class II Div 2 

FG T6  

Ta -40ºC to +45ºC 

Class III Div 1 & 2  

Ta -40ºC to +50ºC 

 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 
 

3.5 Ambient Temperature Range: 

 
 

-40ºC to +70ºC (Class I Div 2 only) 

 

-40ºC to +50ºC 

 

3.6 Ingress Protection Ratings 

 
The product is rated for ingress Protection as follows: 
 

IP rating per EN60529: 

 

IP66 

 

Type rating per UL50E / NEMA250: 

4 / 4X / 3R / 13  

  

To maintain the ingress protection rating, the two off M20 cable 
entries must be fitted with suitably rated, certified  cable entry 
and/or blanking devices during installation. 

 

3.7 Electrical Ratings 

 

Part No. 

Nominal 
Voltage 

Nominal 
Current  

Voltage 
Range 

Max 
Current 

D2xS1DC024  24Vdc 

313mA 

10-30Vdc 

313mA 
@ 24Vdc 

D2xS1DC048

 

48Vdc 

181mA 

38-58Vdc 

218mA 
@ 48Vdc 

D2xS1AC115

 

115Vac 

89mA 

115Vac 
+/-10% 
60Hz 

91mA @ 
126.5Vac 

D2xS1AC230

 

230Vac 

52mA 

230Vac 
+/-10% 
50Hz 

72mA @ 
253Vac 

 

3.8 Fire Alarm Ratings 

 
The following models are approved for use as audible signal 
appliances for fire alarm use –  public mode and produce a 
sound pressure level above 75dB(A) at 10 feet: 
 
D2xS1DC024 
 
For public mode fire alarm use the temporal pattern tone No. 
12 as per the tone table provided in these instructions must be 
selected. This tone produces a sound pressure level of 103.6 
dB(A) at 10 feet. 
 

4)  Special Conditions for Safe Use 

 
Special Condition for safe Use as stated on the Type 
Examination Certificate DEMKO 14 ATEX 4786493904X / CoC 
IECEx ULD 14.0004X: 
 
End user shall adhere to the manufacturer’s installation and 
instruction when performing housekeeping to avoid the 
potential for hazardous electrostatic charger during cleaning, 
by using a damp cloth. 
 
The D2xC1 is not to be mounted with the horn facing upwards 
The equipment shall only be used in end use with appropriately 
certified cable entry devices and blanking plugs

 

 

4.1 Installation 
 

The product must only be installed by suitably qualified 
personnel in accordance with the latest issues of the relevant 
standards. 
 
The installation of the units must also be in accordance with 
any local codes that may apply and should only be carried out 
by a competent electrical engineer who has the necessary 
training. 
 
The alarm horn is not to be mounted with the horn facing 
upwards. 
 
The equipment has not been assessed as a safety-related 
device (as referred to by Directive 94/9/EC Annex II, clause 
1.5). 
 
The cable entry temperature  may 70ºC / the cable 
branching point may exceed 80ºC. Therefore  suitable heat 
resisting cables and cable glands must be used, with a rated 
service temperature of at least 90ºC. 

 

To maintain the ingress protection rating and mode of 
protection, the  M20  x 1.5  cable entries must be fitted with 
suitably rated, certified  cable  glands  and/or suitably rated, 
certified  blanking devices during installation. If a high IP 

Summary of Contents for D2xC1

Page 1: ...NOWN TO BE FREE OF IGNITIBLE CONCENTRATIONS 3 Ratings and Markings 3 1 ATEX IECEx certification The D2xS1 alarm horn complies with the following standards EN60079 0 2012 IEC60079 0 ed 6 0 2011 06 EN60...

Page 2: ...cable entry and or blanking devices during installation 3 7 Electrical Ratings Part No Nominal Voltage Nominal Current Voltage Range Max Current D2xS1DC024 24Vdc 313mA 10 30Vdc 313mA 24Vdc D2xS1DC048...

Page 3: ...ations inspection and maintenance Units must not be opened while an explosive atmosphere is present If opening the unit during maintenance operations a clean environment must be maintained and any dus...

Page 4: ...ply terminals see fig 5 8 3 AC Units Second Third and Fourth Stage Tone Selection To select the second third and fourth stage tones on the D2xS1 AC alarm horns Stage two S2 operation Power L and N lin...

Page 5: ...se see fig 8 for DC fig 5 for AC The earth conductor should be at least equal in size and rating to the incoming power conductors The internal earth bonding wire connects the PCBA earth terminal to th...

Page 6: ...f x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0...

Page 7: ...44 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 44 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1...