European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D190-00-101-IS

 

Issue 3

 

28-11-2022

Sheet 3 of 8

 

5)  Specific Conditions of Installation 

 

ATEx/IECEx & UKEx Installations: 
 

The cable entries have two M20 x 1.5 – 6H entry thread and a 
single ½” NPT thread. If the installation is made using cable 
glands, only suitably rated ATEx/IECEx or UKEx certified cable 
glands must be used. They must be suitable for the type of 
cable being used and also meet the requirements of the 
current installation standards EN 60079-14 / IEC60079-14. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 
Any unused cable entries must be closed with suitably rated 
and UKEx certified blanking plugs. 
 
For high ambient temperatures the cable entry temperature 
may exceed 70ºC or the cable branching point temperature 
may  exceed  80ºC  and  therefore  suitable  heat  resisting 
cables and cable glands must be used, with a rated service 
temperature at least as stated below: 

 

NEC / CEC Installations: 
 

The cable entries have two M20 x 1.5 – 6H entry thread and a 
single ½” NPT thread. If the installation is made using cable 
glands, only suitably rated and UKEx certified cable glands 
must be used. They must be suitable for the type of cable 
being used and also meet the requirements of the current 
installation standards for NEC & CEC. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected within 18” of enclosure. 
 
Any unused cable entries must be closed with suitably rated 
and certified blanking plugs. 
 

All Installations: 
 
The plastic horn is not anti-static and the metallic enclosure has a 
non-conductive coating. These may generate an ignition-capable 
level of electrostatic charges under certain extreme conditions. The 
user should ensure that the equipment is not installed in a location 
where it may be subjected to external conditions that might cause a 
build-up of electrostatic charges on non-conducting surfaces. 
 
Only  the  explosionproof  cover  is  to  be  used  for  access  to  the 
enclosure for installation, service and maintenance. 
 

6)  Specific Conditions for Safe Use 

 

Flameproof threaded joints and cemented joints are not permitted to 
be repaired. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

7)  Product Mounting and Access 

 

7.1 

Mounting 

 

The D1x Alarm Horn may be secured to any flat surface using at 

least two of the three or four 7mm fixing holes. The enclosure 

provides IP66 protection and is suitable for installation in 

exterior locations providing it is positioned so that water cannot 

collect in the horn, and the cable entry is sealed. 

 

14

[5

.71 

in

.]

30

 [

1.

18

 in

.]

30

 [

1.

18

 in

.]

236.9 [9.33 in.]

21

9.

[8

.6

in

.]

335.9 [13.23 in.]

314.5 [12.38 in.]

40

3.

[1

5.

87

 in.

]

465.9 [18.34 in.]

55 [2.17 in.]

59

 [2

.3

in

.]

59

 [

2.

32

 in

.]

21

[8

.46 

in

.]

 

 

 

Fig 1: Mounting Locations 

 

The Equipment must not be installed with the horn facing upwards 
of horizontal. 

 
 
 
 

 

  

7.2 

Installation procedure 

  

a. 

Secure  the  D1x  unit  to  a  flat  surface  via  the  three  7mm 

fixing holes in the mounting    bracket.  

b.

  

Remove  the  explosionproof  cover  of  the  alarm  horn  by 

unscrewing  it,  taking  care  not  to  damage  the 

explosionproof  threads  in  the  process  (Refer  to  section 

7.4).  

c.

  

Fit an M20/NPT suitably rated cable gland or conduit entry 

into the hole in the enclosure and connect the field wiring 

to the appropriate alarm horn terminals as shown in D190-

06-005  (AC)  or  D190-06-001.  (DC).  The  power  supply 

terminals are duplicated so that units may be connected 

in parallel. An end of line monitoring resistor may be fitted 

to DC units only (see section 10). If the second and third 

M20/NPT  entries  are  not  used,  suitably  rated  stopping 

plugs must always be fitted. 

d.

  

Replace  the  explosionproof  cover  of  the  loudspeaker, 

taking  care  not  to  damage  the  explosionproof  threads. 

Tighten fully. 

  

7.3 

Hornless Variants 

  

The D1x Sounder is also available as a variant with no horn fitted 
in  the  factory.  The  Horn  threaded  nose  portion  has  a  fitment 
thread  of  1-3/8”  –  18  UNF  (to  BS1580  or  ANSI  B1.1).  The 
customer is responsible for sourcing and correctly fitting a suitable 
horn that meets all of the relevant safety requirements. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  

Minimum Ratings of Cables & Cable Glands

 

Max Ambient Temp (°C) 

55 

60 

65 

70

75

D1xS2-DC024-A Min. Rating (°C) 

70 

75 

80 

85

90

D1xS2-AC230-A Min. Rating (°C) 

 

70 

75 

80

85

Table 2: Min. Ratings of Cables & Cable Glands. 

D1xS2F 

D1xS2H 

Summary of Contents for D1xS2 Series

Page 1: ...S ATMOSPHERES DISCONNECT FROM SUPPLY BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WI...

Page 2: ...C Ex tb IIIC T95 C Db Ta 55 C to 75 C D1xS2 AC230 A Ex db IIC T5 Gb Ta 55 C to 75 C Ex db IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T93 C Db Ta 55 C to 75 C See Product table for electrical ratings of eac...

Page 3: ...arges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded...

Page 4: ...connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2 AWG24 AWG12 Fig 3 Wire Preparation When connecting wires to the terminals great care should be taken to dress the wires so that when the c...

Page 5: ...ders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for AC Un...

Page 6: ...iring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Neg...

Page 7: ...Resistor placement Optional 12 Way Terminal Module 11 Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in acc...

Page 8: ...ces may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a s...

Page 9: ...0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1...

Page 10: ...US 100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Ton...

Page 11: ...al Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A...

Page 12: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 13: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Page 14: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Page 15: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Page 16: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Page 17: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 18: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Page 19: ...te and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on th...

Page 20: ...Page left Intentionally blank...

Reviews: