INSTRUCTION MANUAL 

D1xC1 & D1xC2 
Alarm Horn Sounder & Strobe

 

Class II & III, Zone 20, 21 & 22

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-351-IS

 

Issue 1

 

21-03-2022

 

Sheet 1 of 6

 

D1xC1-R & D1xC2-R

 

D1xC1-F

 

D1xC2-F 

1) Product Table

Unit Type Code 

Nominal 

Input Voltage 

Nominal 

Input Current 

Voltage Range 

Sound 

Pressure Level dB(A) 

Max* 

Nom

.†

 

D1xC1X05RDC024-D 

24Vdc 

508mA 

20-28Vdc 

94 

90 

D1xC1X05RAC115-D 

115Vac 

200mA 

110-120Vac 50/60Hz 

D1xC1X05RAC230-D 

230Vac 

127mA 

220-240Vac 50/60Hz 

D1xC1X05FDC024-D 

24Vdc 

508mA 

20-28Vdc 

98 

94 

D1xC1X05FAC115-D 

115Vac 

200mA 

110-120Vac 50/60Hz 

D1xC1X05FAC230-D 

230Vac 

127mA 

220-240Vac 50/60Hz 

D1XC2X05RDC024-D 

24Vdc 

P2/P3: 647/1063mA 

20-28Vdc 

P2/P3 

96/98 

P2/P3 

92/94 

D1xC2X05RAC115-D 

115Vac 

P2/P3: 255/415mA 

110-120Vac 50/60Hz 

D1xC2X05RAC230-D 

230Vac 

P2/P3: 157/246mA 

220-240Vac 50/60Hz 

D1XC2X05FDC024-D 

24Vdc 

P2/P3: 647/1063mA 

20-28Vdc 

P2/P3 

106/109 

P2/P3 

103/105 

D1xC2X05FAC115-D 

115Vac 

P2/P3: 255/415mA 

110-120Vac 50/60Hz 

D1xC2X05FAC230-D 

230Vac 

P2/P3: 157/246mA 

220-240Vac 50/60Hz 

*Max = Tone 4

Nom. = Tone 44

The table shows the input current taken by the various sounders. 
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage. 
Nominal current at nominal voltage. 

Table 1: Electrical Ratings. 

2) Warnings

CAUTION 
TO  REDUCE  THE  RISK  OF  IGNITION  OF  HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT  SEALING  FITTING  IN  CONDUIT  RUNS  WITHIN  18  INCHES 
FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING 
UPWARDS OF HORIZONTAL 
DO  NOT  OPEN  WHEN  AN  EXPLOSIVE  ATMOSPHERE  IS 
PRESENT  
DO NOT OPEN WHEN ENERGISED  
POTENTIAL  ELECTROSTATIC  CHARGING  HAZARD  -  CLEAN 
ONLY WITH A DAMP CLOTH  

ATTENTION 
POUR 

REDUIRE 

LE 

RISQUE 

D’INFLAMMATION 

DES 

ATMOSPHÈRES DANGEREUSES : 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES. 
ÉQUIPEMENT  NE  DOIT PAS  ETRE INSTALLE  AVEC  LE  KLAXON 
TOURNEE VERS LE HAUT DE HORIZONTAL. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE  

Summary of Contents for D1xC1X05FAC115-D

Page 1: ...0 60Hz D1xC2X05FAC230 D 230Vac P2 P3 157 246mA 220 240Vac 50 60Hz Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The current levels shown above are for the 440H...

Page 2: ...nstallation must be carried out in compliance with the National Electric Code D1xC units have been tested and found suitable for use in atmospheres containing the following chemicals in accordance wit...

Page 3: ...essing the enclosure To access the Ex d chamber loosen the M4 grub screw on the cover Open the enclosure by turning the cover counterclockwise and remove the cover On completion of the installation th...

Page 4: ...uired then a suitable sealing washer must be fitted under the cable glands or blanking plugs A minimum ingress protection rating of IP6X must be maintained for installations in explosive dust atmosphe...

Page 5: ...ferent tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP switch 2 see fig 10 on the PCB for stage...

Page 6: ...06 305 for AC Schematic Diagrams 9 End of Line Monitoring DC Units 9 1 Standard DC End Of Line Monitoring All DC units have a blocking diode fitted in their supply input lines An end of line monitorin...

Page 7: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 8: ...age 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve WIRING LINKING BEACON SOUNDER FACTORY FITTED 6 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX...

Page 9: ...ED D190 06 301 6 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINI...

Page 10: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF 3 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 WIRING LINKING BEACON...

Page 11: ...T Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve ve IN ve IN D190 06 301 6 4 R2 ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUP...

Page 12: ...R2 R1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four S...

Page 13: ...DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 301 6 6 OPTIONAL LINE MONITOR...

Page 14: ...SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STA...

Page 15: ...CALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 305 R S RAIT B ISARD R N POTTS OF NTS 2 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 2 Stage 1 Live...