18) SIL 2 Specific Unit Mounting Requirements 

 
The beacon should be mounted no closer that 2m from a beacon or light source of similar candela output. This is to ensure false 
light activation does not occur when the unit is monitoring the light pulse duration and flash failure. 
 
 

19) SIL 2 Reliability Data 

 
Reliability and Functional safety IEC/EN61508 which has been assessed and is considered suitable for use in low demand safety 
function: 
 
1.  Random Hardware Failures and Architectural constraints (route 1

H

). 

2.  As an unvoted item (i.e. hardware fault tolerance of 0) at SIL 2. 
The product was assessed against failure modes: 

 

Failure respond to an input by lighting a beacon. 

 

Spurious light output despite no input. 

 

Integrity in respect of failure to release 

SIL 2 

Total Failure rate 

0.35 pmh 

H

azardous” failure rate (revealed)

 

0.287 pmh 

H

azardous” failure rate (unrevealed)

 

0.003 pmh 

S

afe” failure rate (revealed)

 

0.006 pmh 

S

afe” failure rate (unrevealed)

 

Diagnostic Coverage 

99% 

System type 

Hardware Fault Tolerance 

Safe Failure Fraction 

>99% 

PFD (hazardous failure) 

3.7 x 10

-5

 

Proof Test Interval 

Up to 1 year 

 
 

20) Synchronised Operation 

 
All D1xB2 SIL2 beacons that are connected to the same supply line will have a synchronised flash rate at one flash every second. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for D1xB2X05-S

Page 1: ...IQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER NE PAS PEINTURER POUR R DUIRE LE RISQUE D IN...

Page 2: ...ss III Div 1 Ta 55 C to 80 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 2 4 NEC Class Zone ratings US The D1xB2X Xenon beacons comply with th...

Page 3: ...t for a short time Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist f...

Page 4: ...14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC6007...

Page 5: ...in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT plugs should be greased before insertion For high ambient temperatures the cable entry temperature or t...

Page 6: ...h conductor should be at least equal in size and rating to the incoming power conductors External earthing connections should be made to the M5 earth stud using a ring crimp terminal to secure the ear...

Page 7: ...s MUST be fitted in the order shown above 13 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with...

Page 8: ...and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system The beacon will after commissioning remain powered in Stan...

Page 9: ...equire further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must...

Page 10: ...h it is highly recommended that the unit is wired as stated in section 17 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 17 3 places TB1 Curr...

Page 11: ...he circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Cu...

Page 12: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 621 IS available from the E2S webs...

Page 13: ...tion B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 17 4 SIL 2 Hard Reset Function...

Page 14: ...ndom Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input...

Page 15: ...specified when ordering The values of resistors available are shown in table 5 below Code Resistor Value Default resistor coding is as follows D1xB2X05DC024AS1S1R A AFZ Example of a custom requirement...

Page 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Page 17: ...Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility...

Page 18: ...Ex d IIC T6 T3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic...

Reviews: