European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D191-00-401-IS Issue 1 03-06-2019 Sheet 2 of 6
Flame Path internal thread on
base shown hatched
Cemented Joint
between glass
dome and metal
casting on lid
shown hatched
Flame Path external thread
on lid shown hatched
2.4 ATEX / IECEx certification
The D1xB2LD2 LED beacons comply with the following
standards:
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7)
EN60079-1:2010 / IEC60079-1: ed. 7.0 (2014-06)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
The D1xB2LD2 LED Beacon is rated as follows:
Ex db IIC T5 Gb Ta -55°C to +80°C
Ex db IIC T6 Gb Ta -55°C to +70°C
Ex tb IIIC T100°C Db Ta -55°C to +80°C
For D1xB2LD2AC230 units, the certification approval has
validated continuous use up to 38°C ambient and are for
transient use up to 80°C ambient
Certificate No.
DEMKO 19 ATEX 2009X
IECEx ULD 19.0006X
ATEX Mark, Equipment
Group and Category
:
CE Marking
Notified Body No.:
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur
in normal operation, and if it does, it will
only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification:
T1
450ºC
T2
300ºC
T3
200ºC
T4
135ºC
T5
100ºC
T6
85ºC (up to 70°C ambient)
Dust Groupings:
Group IIIA
Combustible Flyings
Group IIIB
Non-conductive Dust
Group IIIC
Conductive Dust
Maximum Surface Temperature for Dust Applications:
100ºC
Equipment Category:
2G / 2D
Equipment Protection Level:
Gb, Gc, Db, Dc
Ambient Temperature Range:
-55°C to +80°C
2.5 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating
per EN60529:
IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
Suitable for exposure to Acetone , Ammonium Hydroxide ,
Diethyl Ether , Ethyl Acetate , Ethylene Dichloride , Furfural,
n-hexane , Methyl Ethyl Ketone , Methanol , 2-NitroPropane
and Toluene.
To maintain the ingress protection rating, the cable entries
must be fitted with suitably rated, certified cable entry and/or
blanking devices during installation.
2.6 Electrical Ratings
#
Rated at 1Hz
Table 1: Electrical Ratings
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the
units.
The input current will vary according to the voltage input
level.
3) Special Conditions of Use
The enclosure coating is non-conductive and may generate
an ignition-capable level of electrostatic charges under
certain extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be
subjected to external conditions (such as high pressure
steam) which might cause a buildup of electrostatic charges
on non-conducting surfaces. Additionally, cleaning of the
equipment should be done only with a damp cloth.
Model
Nom.
Voltage
Voltage
Range
Nom.
operating
current
#
MaX.
Operating
Current
D1xB2LD2DC024
24Vdc
18-30Vdc
230mA
500mA
D1xB2LD2AC115
115Vac
110-120Vac
95mA
180mA
D1xB2LD2AC230
230Vac
220-240Vac
50mA
100mA
0518
II 2G
II 2D