E2S BExCBGL2-05D-P Instruction Manual Download Page 2

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-711-IS

 

Issue 6

 

12-09-2022

Sheet 2 of 6

 

3.  Marking & Rating Information 

The  BExCBGL2-05D-P  Alarm  Horns  comply  with  the  following 
standards for hazardous locations:  
  

3.1 ATEX / IECEx & UKEx Ratings

 

 

Standards

EN60079-0:2018/IEC60079-0:2017 

(ed.7): 

Explosive 

Atmospheres - Equipment General Requirements. 
EN60079-1:2014/IEC60079-1:2014 

(ed.7): 

Explosive 

Atmospheres - Equipment Protection by Flameproof Enclosures 
“d”. 
EN60079-31:2014/IEC60079-31:2013 

(ed.2): 

Explosive 

Atmospheres - Equipment Dust Ignition Protection by enclosure 
“t”. 

Model No: 

Rating 

BExCBGL2-05D-P   Ex db IIB T4 Gb Ta. -50°C to +70°C 

Ex db IIB T4 Gb Ta. -50°C to +40°C 
Ex tb IIIC T95°C Db Ta. -50°C to +40°C 
Ex tb IIIC T110°C Db Ta. -50°C to +55°C 
Ex tb IIIC T125°C Db Ta. -50°C to +70°C 

See Product table for electrical ratings of each unit model 

 

Certificate No.    

KEMA  01ATEX2222X 
IECEx KEM 10.0024 
UL22UKEX2637X 

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

2813 

UKCA Marking and 
Approval Body No. 
 

 

0518 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.  Zones, Gas Group, Category and 

Temperature Classification 

The units can be installed in locations with the following conditions: 
 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation.

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Gas Groupings 

Group IIA

Propane

Group IIB

Ethylene

Group IIC

Hydrogen & Acetylene 

Temperature Classification for Gas Applications

T1

450

o

T2

300

o

C

T3

200

o

C

T4

135

o

C

T5

100

o

C

Area Classification Dust 

Zone 21 

Explosive dust air mixture likely to occur in normal 
operation.

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Dust Groupings 

Group IIIA

Combustible Dusts 

Group IIIB

Non-Conductive Dusts 

Group IIIC

Conductive Dusts 

Equipment Category 

2G, 2D

Equipment Protection Level 

Gb, Db,

Maximum Surface Temperature for Dust Applications

125°C  

 

Ambient Temperature Range

-50°C to +70°C Gas Groups IIA and IIB 

-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

IP Rating 

IP66/67 to EN/IEC60529 and

IP6X to EN/IEC60079-0, EN/IEC60079-31 

The  unit  must  only  be  installed  by  suitably  qualified  personnel  in 
accordance with the latest issues of the relevant standards: 
  
EN60079-14  /  IEC60079-14:  Explosive  atmospheres  -  Electrical 
installations design, selection and erection 
EN60079-10-1  /  IEC60079-10-1:  Explosive  atmospheres  - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2  /  IEC60079-10-2:  Explosive  atmospheres  - 
Classification of areas. Explosive dust atmospheres 
 
The installation of the unit must also be in accordance with any local 
codes that may apply and should only be carried out by a competent 
electrical engineer who has the necessary training.

 

 

Summary of Contents for BExCBGL2-05D-P

Page 1: ...shows the input current taken by the various units Nominal current at nominal voltage Table 1 Electrical Ratings It is important that a suitable power supply is used to run the equipment The power su...

Page 2: ...ve gas air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen Acetylene Temperatur...

Page 3: ...to ensure that the unit cannot move in service Fig 1 Fixing Location for Combined Beacon Beacon 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexagon socket head...

Page 4: ...ls which are both located on the terminal chamber section of the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the...

Page 5: ...line resistor is used it must have a minimum resistance value of 3k3 and a minimum power rating of 0 5 watts or a minimum resistance value of 500 and a minimum power rating of 2 watts The resistor mus...

Page 6: ...epair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atm...

Page 7: ...2022 BExCBGL2 05D DC LED XENON BEACONS WIRING DIAGRAM INTRODUCTION INTRODUCTION 1 RSR 05 09 2022 ve in ve in ve out ve out Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring S...

Page 8: ...TE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F...

Page 9: ...ality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G Ex db IIB T6 to T4 Gb II 2D Ex tb IIIC T65 C to T130 CDb IP6X Dust Protectionto EN60079 0 EN60079 31 St...

Page 10: ...r Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthem...

Page 11: ...Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIB T6 T4 Gb II 2D Ex tb IIIC T65 C T130 Db IP6X Dust Protection to EN6007...

Page 12: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Reviews: