European Safety Systems Ltd.

Impress House, Mansell Road, Acton, London W3 7QH

[email protected]

Tel: +44 (0)20 8743 8880

www.e-2-s.com

Fax: +44 (0)20 8740 4200

Document No. BExBGL1D (Gas-Dust) English

Issue A (Four Sheets)

26-01-11

(

4

)

Drawing A

Tighten screw to secure.
Spænd skruen for at fastgøre.
Schroef aandraaien om vast te zetten.
Serrer la vis pour une fixation sûre.
Zum Sichern Schraube anziehen.
Stringere la vite per il fissaggio.
Stram skruen for å feste.
Aperte o parafuso para fixar.
Apriete el tornillo para asegurar.

Dra åt skruven för att fästa.

Loosen screw to adjust.
Løsn skruen for at tilpasse.
Schroef losdraaien om af te stellen.
Desserrer la vis pour régler.

Zum Regulieren Schraube lockern.
Allentare la vite per poter effettuare la
regolazione.

Løsne skruen for å justere.
Desaperte o parafuso para ajustar.

Afloje el tornillo para ajustar.

Lossa skruven för att justera.

Lossen screw

to adjust

Tighten screw
to secure

180º

Drawing B

Drawing C

Supply Terminals

Stage S2 & S3
Terminals

Flash Pattern
Pin Headers

Drawing D

Supply and
Stage S2 & S3
Terminals

Flash Pattern
Pin Headers

Wiring Diagram E

BExBGL1D DC LED Beacon Wiring

S3

S2

Stage 3

Stage 2

+
-

-

+

+

-

S2 S3

S3

S2

C

-

+

BExBGL1D AC LED Beacon Wiring

S3

S2

Stage 3

Stage 2

L
N

C

C

N

L

L

N

C S2 S3

S3

S2

C

N

L

BExBGL1D DC LED
Beacons

BExBGL1D AC LED
Beacons

Summary of Contents for BExBGL1D

Page 1: ...USE HEAT RESISTING CABLES AND CABLE GLANDS Rated 110ºC AT AMB TEMPERATURES OVER 40ºC Year of Construction Serial No i e 10 1DB73000001 3 Type Approval Standards The beacon has EC Type Examination and IECEx certificates issued by KEMA and have been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007 IEC60079 1 2007 Ed6 Flameproof Enclosure d EN...

Page 2: ...d only screws of this category can be used on the beacons It is therefore important that these screws and their spring washers are kept in a safe place during installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check that the earth bonding wire between the tw...

Page 3: ... and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements For combustible dust applications the cable entry device and blanking elements shall be in type of explosion protection inc...

Page 4: ...e third stage flash pattern connect a ve supply line to terminal S3 The supply line to the S3 terminal will automatically override a supply to the S2 terminal AC Units Second and Third Stage Selection To select the second and third stage flash patterns on the BExBGL1D AC beacons the Common C terminal on the three way terminal block on the pcb is connected to the S2 terminal for the second stage to...

Page 5: ...ctrical Installations in Hazardous IEC60079 14 2007 Ed4 Areas other than mines EN60079 10 2003 Classification of Hazardous Areas IEC60079 10 2008 Ed1 Installation should only be carried out by competent personnel and local codes of practice applied 5 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification Gas...

Page 6: ...2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements For combustible dust applications the cable entry device and blanking elements shall be in type of explosion protection increased safety e or flameproof enclosure d and shall have an IP 6X rating according to EN...

Page 7: ...ts 26 01 11 3 Flash Pattern Table Stage 1 LED Stage 2 Stage 3 Pattern Flash Pattern Pattern Pattern 1 ON 9 8 2 Rotating 3 LED on Fast 7 1 3 Rotating 6 LED on Fast 8 1 4 Rotating 3 LED on Slow 9 1 5 Rotating 6 LED on Slow 6 1 6 Double strike strobe 1 Hz 9 1 7 Single strike strobe 2 Hz 3 1 8 Double strike strobe 2 Hz 3 1 9 Alternate side flash 1 1 2 Hz 3 1 PIN HEADER POSITIONS Pattern No 1 Pattern N...

Page 8: ...ete el tornillo para asegurar Dra åt skruven för att fästa Loosen screw to adjust Løsn skruen for at tilpasse Schroef losdraaien om af te stellen Desserrer la vis pour régler Zum Regulieren Schraube lockern Allentare la vite per poter effettuare la regolazione Løsne skruen for å justere Desaperte o parafuso para ajustar Afloje el tornillo para ajustar Lossa skruven för att justera Lossen screw to ...

Page 9: ...llte nur von qualifiziertem Fachpersonal vorgenommen werden Örtliche anerkannte Verfahren sind zu beachten 5 Zonen Gasgruppe Kategorie und Temperaturklassifizierung Die Geräte können an Standorten aufgestellt werden an denen die folgenden Bedingungen vorliegen Bereichseinteilung Gas Zone 1 Bei normalem Betrieb kann mit hoher Wahrscheinlichkeit eine explosive Gas Luft Mischung vorliegen Zone 2 Expl...

Page 10: ... verwendet werden die für Ex d Anwendungen zugelassen sind Die Kabelverschraubungen müssen für den eingesetzten Kabeltyp geeignet sein und zudem den Anforderungen der Ex d Norm zur Installation drucksicherer Geräte EN60079 14 2008 IEC60079 14 2007 entsprechen Wenn nur ein Kabeleingang verwendet wird muss der andere mit einem druckfesten Ex d Stopfen der für die Installationsbedingungen zugelassen ...

Page 11: ...n Kontrollwiderstand für das Leitungsende können über die Klemmen und angeschlossen werden Wird ein Widerstand für das Leitungsende verwendet muss sein Widerstandswert mindestens 3k3 Ohm und die Mindestleistung 0 5 Watt betragen oder aber es muss ein Widerstandswert von mindestens 500 Ohm und eine Mindestleistung von 2 Watt vorliegen Blinkmuster Tabelle Stufe 1 LED Stufe 2 Stufe 3 Muster Blinkmust...

Page 12: ...ions fulfilled by the equipment ll2 G Ex d llC T3 to T6 or ll2 G Exde llC T4 to T6 ll2 D Ex tD A21 lP66 or lP67 T85 C to T200 C Standards applied EN 60079 0 2006 EN 60079 1 2007 EN 60079 7 2003 EN 61241 0 2006 EN61241 1 2004 Directive 2004 108 EC Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 The standards EN 60...