INSTRUCTION MANUAL
BExBG05D-P
Xenon Beacon
ATEx/IECEx & UKEx Gas & Dust
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D210-00-201-IS
Issue 5
12-09-2022
Sheet 1 of 6
BExBG05D-P
1. Product Table
Unit Type Code
Nominal
Input Voltage
Nominal
Input Current
Max I/P Voltage
BExBG05DPDC012
12Vdc
750mA
14V
BExBG05DPDC024
24Vdc
300mA
28V
BExBG05DPDC048
48Vdc
180mA
54V
BExBG05DPAC115
115Vac
140mA
126V
BExBG05DPAC230
230Vac
55mA
253V
It is important that a suitable power supply is used to run the equipment. The power supply selected must have the necessary capacity
to provide the input current to all of the units.
The above table shows the input current taken by the various beacons and shows the maximum voltage at which the beacons can be
operated:
The input current will vary according to the voltage input level.
2. Warnings
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGIZED
POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A DAMP CLOTH
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS (RATED 110°C) AT AMB. TEMPERATURES OVER
40°C