background image

__________________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 2425-P      Issue B     17-04-02                                 Sheet 2 of 4

 

 

The units should be securely bolted to a suitable surface using 
the  7mm  diameter  boltholes  in  the  stainless  steel  U  shaped 
mounting  bracket  (see  figure  1).  The  angle  can  then  be 
adjusted in the direction that the message is primarily required 
to  cover.  This  can  be  achieved  by  loosening  the  two  large 
bracket  screws in  the  side of  the unit,  which  allow  adjustment 
in steps of 18

°

. On completion of the installation the two large 

bracket adjustment screws on the side of the unit must be fully 
tightened to ensure that the unit cannot move in service. 

 

 

7) 

Safety Warning (Electrostatic Hazard)

 

 

The acoustic horn section is made of ABS Plastic, therefore to 
avoid  a  possible  ELECTROSTACTIC CHARGE  the  unit  must 
only be cleaned with a damp cloth. 

 

8) 

Access to the Flameproof Enclosure

 

 

In order to connect the electrical supply cables and to record a 
message  onto  the  units,  it  is  necessary  to  remove  the 
flameproof cover to gain access to the flameproof chamber. To 
achieve this remove the four M6 hexagon socket head screws 
(see  figure  2)  and  withdraw  the  flameproof  cover  taking  
extreme  care  not  to  damage  the  flameproof  joints  in  the  
process.  
 
Note  the  four 

M6  screws  are  Class  A4-80  stainless  steel 

and  only  screws  of  this  category  can  be  used  on  these 
units. 

It  is  therefore  important  that  these  screws  and  their 

spring washers are kept in a safe place during installation. 
 
On  completion  of  the  cable  wiring  installation  the  flameproof 
joints  should  be  inspected  to  ensure  that  they  are  clean  and  
that  they  have  not  been  damaged  during  installation.  Also 
check  that  the  earth  bonding  wire  between  the  two  casting 
sections  is  secure  and  the  ‘O’  ring  seal  is  in  place.  W hen 
replacing  the flameproof cover casting ensure  that  it  is  square 
with the flameproof chamber casting before inserting. Carefully 
push the cover in place allowing time for the air to be expelled. 
Only  after  the  cover  is  fully  in  place  should  the  four  M6 
Stainless Steel A4-80 cover  bolts and their spring  washers be 
inserted and tightened down. If the cover jams while it is being 
inserted, carefully remove it and try again. Never use the cover 
bolts to force the cover into position. 
 

 
 

9) 

Power Supply Selection 

 

It  is  important  that  a suitable power  supply  is  used to  run  the  
Appello’s  and  that  the  cables used  to connect  the  units to  the 
power  supply  are  selected  to  ensure  that  they  have  the  
necessary capacity.  
 
The  following  table  shows  the  input  current  taken  by  the  
various sounder units:- 

 

Unit Type 

Input  

 

Input 

 

Max. 

 

 

Voltage   

Current   

I/P Volts

 

 
BExA120D 

24V DC   

480mA 

 

30V 

BExA120D 

230V AC   

45mA 

 

253V 

BExA120D 

115V AC   

90mA 

 

126V 

 
BExA110D 

24V DC   

480mA 

 

30V 

BExA110D 

230V AC   

45mA 

 

253V 

BExA110D 

115V AC   

90mA 

 

126V 

 

The  input  current  will  vary  according  to  the  voltage input  level 
and  the  frequency  of  the  tone  selected.  The  current  values 
shown  above  are  for  the  554/440Hz  tone  @  nominal  input 
voltage. The above table also shows the maximum voltages at 
which the units can be operated. 
 

10) 

  Cable Selection 

 

W hen selecting the cable size  consideration  must  be  given  to 
the  input  current  that  each  unit  draws  (see  table  above),  the 
number  of  units  on  the  line  and  the  length  of  the  cable  runs. 
The  cable  size  selected must  have  the  necessary  capacity  to 
provide  the  input  current  to  all  of  the  Appello’s  connected  to 
the line.  
 
SAFETY W ARNING: If the Appello’s are used at high ambient 
temperatures,  i.e.  over  +40ºC,  then  the  cable  entry 
temperature  may  exceed  +70ºC  and  therefore  suitable  heat 
resisting  cables  must  be  used,  with  a  rated  service 
temperature of at least 95ºC. 
 

11) 

  Earthing 

 

Both  AC  and  DC  Appello  units  must  be  connected  to  a  good 
quality earth. The units are provided with  internal  and external 

Figure 1 

Flameproof  
Chamber

 

Flameproof  
Cover

 

S/S Mounting 
Bracket

 

Figure 2 

4 off M6 Cover Screws 

External Earth  
Terminal

 

Plastic Acoustic Horn 
 
Please see Safety Warning 
in Section 7 of this manual 

Reviews: