  LED Flash Mode Settings (AC & DC)

 

The Flash Mode Dip Switch can be changed to set the desired 
flash pattern

 

 

 

 

Flash Mode DIP Switch –

 

Shown with 1

-

OFF, 2

-

ON, 3

-

OFF (0 1 0), 

This denotes Flash mode 1Hz. For further flash modes refer to 
table:

 

 

Switch 

Setting

 

Flash Mode

 

0 0 0

 

Steady on

 

1 0 0

 

Blinking

 

0 1 0

 

Flashing 1Hz

*

 

1 1 0

 

Flashing 1.5Hz

*

 

0 0 1

 

Flashing 

-

 Double Strike

 

1 0 1

 

Flashing 

-

 Triple Strike

 

0 1 1

 

Flashing 2Hz

*

 

1 1 1

 

Flashing 

-

 Temporal

 

1   2   3

ON

• 

All models are approved for use as Audible Signal and Visual Appliance

 

    for use as General Signaling: UL464A & CSA C22.2 No 205

-

17

 

• 

Type 4 / 4X / 3R / 13, IP66

 

• 

-

40°C to +66°C / 

-

40°C to +151°F

 

 

General Signaling Canada:

 

 

 

AL121NHDC: 

-

40°C to +55°C / 

-

40°F to +131°F 

 

 

 

AL121NHAC: 

-

40°C to +40°C / 

-

40°F to +104°F  

 

• 

To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs

 

• 

EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & 

-

ve terminals of the PCBA (See diagram below). Please 

ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. 
Refer to the compatible control panel specification for EOL device values and ratings

 

• 

All DC Units have a blocked diode fitted in their supply input lines which allows reverse polarity monitoring.

 

• 

Note that the maximum forward polarity monitoring voltage is 6V. A monitoring voltage greater than 6V may activate the alarm horn sounder 
and the 2nd, 3rd or 4th stages.

 

Model

 

Nominal 

Voltage

 

Voltage Range

 

Max Operating RMS

#

 

Nominal Operating Current*

 

Beacon

 

Sounder

 

P2 / P3

 

Beacon

 

Sounder

 

P2 / P3

 

AL121HDC024

 

12V dc

 

11.5

-

14Vdc 

 

79.5mA

 

376mA / 440mA

 

168mA

 

430mA / 930mA

 

24V dc

 

16

-

33 Vdc 

(Regulated) 

 

87mA

 

430mA / 930mA

 

183mA

 

AL121HDC048

 

48V dc

 

48

-

54 Vdc

 

60mA

 

223mA / 453mA

 

115mA

 

AL121HAC230

 

115 Vac

 

100

-

240 Vac 

50/60Hz  

 

34mA

 

173mA / 340mA

 

166mA  

 

181mA / 383mA

 

230 Vac

 

19mA

 

105mA / 212mA

 

*Nominal Voltage, 1Hz Flash Pattern / Tone 12; 

#

Worst

-

case input voltage and worst case flash pattern

 