European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-721-IS

 

Issue 5

 

12-09-2022

Sheet 3 of 6

 

5.  Special Conditions for Safe Use 

 

Repair of the flamepath / flameproof joints is not permitted. 

 

The  enclosure  is  non-conducting  and  may  generate  an 
ignition-capable  level  of  electrostatic  charges  under  certain 
extreme conditions (such as high-pressure steam). The user 
should ensure that the equipment is not installed in a location 
where  it  may  be  subjected  to  external  conditions  that  might 
cause  a  build-up  of  electrostatic  charges  on  non-conducting 
surfaces. 

 

Additionally,  cleaning  of  the  equipment  should  be  done  only 
with a damp cloth. 

 

6.  Product Mounting and Access 

 

The location of the unit should be made with due regard to the 
area  over  which  the  warning  signal  must  be  visible.  They 
should only be fixed to services that can carry the weight of the 
unit. 

 

The BEx combined sounder beacon should be secured to any 
flat surface using at least two of the three 7mm fixing holes on 
the stainless steel U shaped mounting bracket. See Figure 1. 
The required angle can be achieved by loosening the two large 
bracket screws in the side of the unit, which allow adjustment 
of the sounder in steps of 18°. On completion of the installation 
then two large bracket adjustment screws on the side of the 
unit must be fully tightened to ensure that the unit cannot move 
in service. 

 

 

Fig. 1 Fixing Location for Combined Beacon/Beacon 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

7.  Access to the Flameproof Enclosure 

 

 

 

To  access  the  Ex  d  chamber,  remove  the  four  M6  hexagon 
socket head screws and withdraw the flameproof cover taking 
extreme  care  not  to  damage  the  flameproof  joints  in  the 
process. M6 cover screws are Class A4-80 stainless steel and 
only screws of this category can be used for the enclosure. 

 

Fig. 2 Accessing the Explosion proof Enclosure. 

 

On completion of the installation, the flameproof joints should 
be inspected to ensure that they are clean and that they have 
not been damaged during installation. 

 

Check that the earth bonding wire between the two castings is 
secure  and  the  ‘O’  ring  seal  is  in  place.  When  replacing  the 
flameproof  cover  casting  ensure  that  it  is  square  with  the 
flameproof  chamber  casting  before  inserting.  Carefully  push 
the cover in place allowing time for the air to be expelled. Only 
after  the  cover  is  fully  in  place  should  the  four  M6  Stainless 
Steel  A4-80  cover  bolts  and  their  spring  washer  be  inserted 
and tightened down. If the cover jams while it is being inserted, 
carefully remove it and try again. Never use the cover bolts to 
force the cover into position. 

 
 

 

Warning – High voltage may be present, 
risk of electric shock. DO NOT open when 
energised, disconnect power before 
opening. 

Warning – Hot surfaces. External surfaces 
and internal components may be hot after 
operation, take care when handling the 
equipment. 

(Appropriate cable glands 
to be customer supplied) 

Flameproof cover  

M6 Cover 
Screws 

M6 Spring 
Washer 

Flameproof 
Chamber  

Summary of Contents for 1-21-142

Page 1: ...nt taken by the various units Nominal current at nominal voltage Table 1 Electrical Ratings It is important that a suitable power supply is used to run the equipment The power supply selected must hav...

Page 2: ...cur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen Acetylene Temperature Classification for Gas Applicatio...

Page 3: ...to ensure that the unit cannot move in service Fig 1 Fixing Location for Combined Beacon Beacon 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexagon socket head...

Page 4: ...using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing connections should be made to the Internal Eart...

Page 5: ...mum resistance value of 3k3 and a minimum power rating of 0 5 watts or a minimum resistance value of 500 and a minimum power rating of 2 watts The resistor must be connected directly across the ve and...

Page 6: ...Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive at...

Page 7: ...MIN MINIMUM VALUES R1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Fl...

Page 8: ...TS 1 1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Appl...

Page 9: ...ality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G Ex db IIB T6 to T4 Gb II 2D Ex tb IIIC T65 C to T130 CDb IP6X Dust Protectionto EN60079 0 EN60079 31 St...

Page 10: ...r Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthem...

Page 11: ...Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIB T6 T4 Gb II 2D Ex tb IIIC T65 C T130 Db IP6X Dust Protection to EN6007...

Page 12: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Reviews: