background image

Manual SCA-SS-30-06 

V 0.9 

09/02    page 7 

 

e-motion Gesellschaft für Antriebstechnik mbH, Zettachring 2, D-70567 Stuttgart, Germany 
Tel.: +49-(0)711-7221535, Fax.: +49-(0)711-7221548 E-mail: [email protected]

 

6.  Connection of inputs and outputs 
 

6.1.  Connection Enable-Input 

The enable input can be switched on by the means of an external ground based voltage (high active) 
 

V

14

13

12

Gnd Signal

Enable In

+8V...+30V

 

 
or by the means of the auxiliary voltage output V (13) and a potential free switch (no). 
 

V

14

13

Enable In

 

 
 

6.2.  Input for Set Value 

The set value for speed (Operating modes I x R, Voltage Control, Tacho) respectively motor current 
(Operating mode Control) can be set on three different ways. 
 
 

6.2.1.  Input for set value by the means of external potentiometer 

 

+Reference

10

9

8

7

+Set value

-Set value

-Reference

 

In this case the pin (8) must not be connected. 

 
 

6.2.2.  Input for set value by the means of an analog voltage reference 

 

8

7

+Set value

-Set value

-10V...+10V

 

 
 

6.2.3.  Input for set value by the means of the integrated potentiometer for offset adjustment 

 

In this case the pins (7) - (10) must not be connected. 

 
 

6.3.  Wiring output error out 

 

Error Out

11

Last

Load

max. 30V

 

 

Summary of Contents for SCA-SS-30-06

Page 1: ...g it therefore a fast and easy integration is provided Screw terminals and a durable controller design allow a fast and straightforward commissioning Contents 1 Safety notes 1 2 Specification 2 3 Desc...

Page 2: ...9 336 EWG article 10 and appendix 1 EMV amended by 92 31 EWG and 93 68 EWG and meet the requirements with standard EN 61800 3 1996 if the following directions are observed usage of a zinc plated mount...

Page 3: ...ected to an differential amplifier Input voltage range 10 V 10 V Input impedance 100 kOhm Definition of polarity positive set value Set value Set value negative set value Set value Set value Input con...

Page 4: ...o 1k 33k 100k 33k 50k 100k 4k7 GNDA 3 1 5 Vcc 3 3 1 6 Power GND 4 Power supply connector Caution DO NOT connect Vcc and Power GND to the outputs Motor or Motor 3 2 Outputs 3 2 1 Auxiliary voltage outp...

Page 5: ...is no direct connection to Power GND or GND Signal These auxiliary voltage outputs are for connection with an external potentiometer and must not be connected to any other pin or for any other purpos...

Page 6: ...D 70567 Stuttgart Germany Tel 49 0 711 7221535 Fax 49 0 711 7221548 E mail mgmt e motion controls com 4 2 Selection of Input for Set Value Jumper 5 6 Via Offset Pot J5 J6 Via Ext Pot J5 Via Set Value...

Page 7: ...l free switch no Enable V 14 13 Enable In 6 2 Input for Set Value The set value for speed Operating modes I x R Voltage Control Tacho respectively motor current Operating mode Control can be set on th...

Page 8: ...4 Adjustment 1 Adjust max set value e g 10 V and turn potentiometer n max cw til the required speed is reached 2 Adjust potentiometer Imax to required value of current limitation Important Refer to mo...

Page 9: ...justed too low Check potentiometer adjustment I max Speed range too low Check potentiometer adjustment n max Wrong operation mode Check jumper setting Bad connections Check connectors Motor does not t...

Reviews: