E-Mon D-mon 4000 Installation Instructions Manual Download Page 6

                   Technical Specifications

Voltage input 

2-wire, 120-volt; 3-wire, 120/240 

configuration: 

volt; 3-wire, 120/208-240 volt

Current Input: 

Up to 200 amps rms AC

Power Factor: 

0.5 leading or lagging

Frequency:  

50 Hz to 400 Hz

Accuracy:   

Certified to ANSI C12.1 (+/-1% of 

 

 

reading from 1% to 100% of rated 

  load).

Voltage operating 
range:  

+

Temperature
range: 

-20 degrees C to +50 degrees C

V25% 

continuously; 

overload:  +100% for 20 cycles

Current 

Can be overloaded 100% 

overload:  without damaging meter.

Display: Electro-mechanical 

6-digit 

display

Standard   120 volt; 100 or 200 amps
ranges: 

120/240 volts; 100 or 200 amps

 

120/208 volts; 100 or 200 amps

                                              

Troubleshooting Guide 

The Class 4000 electronic kilowatt-hour meter is caibrated and tested at the factory be-
fore being packaged and shipped.  If installed properly and in accordance with the instal-
lation instructions, the Class 4000 meter will provide years of trouble-free service.  If the 
meter should not function, the following guide will assist in troubleshooting the instal-
lation.  If, after following the procedures below, the meter still does not function, please 
call E-Mon’s technical department at (800) 334-3666 BEFORE removing the meter. 

 

PROBLEM 

 

 

PROCEDURE TO FOLLOW

1.  Display reads all ZEROs, or

  is not incrementing. 

.  

A.  Determine if the load is sufficient to update the 

 

     display. (A load of less than 1% of the meter rating 

 

 

 

 

     may require more than 24 hours to change the 

 

 

 

 

     display reading.)

 

 

 

 

B.  Check the current sensors for installation. 

 

 

 

 

 

 

 

 

C.  Be sure that the current and voltage inputs have 

 

 

 

 

     proper phase relationship.

 

 

 

 

 

 

 

 

D.  Check wiring to voltage terminals.

 

 

 

 

E.  Check circuit breaker or fuses.

 

 

 

 

F.   Test source for correct voltage.

2.  Display reads only a fraction 

A.  Check the supply voltage to be sure that it is on

     of the power consumption.   

     continuously 24 hours a day.

 

 

 

 

B.  Check the current sensors for installation and

 

 

 

 

     polarity.

 

 

 

 

C.  Check the sensor wiring to the terminal block in

 

 

 

 

     the meter (color coding white to white and black to

 

 

 

 

     black).