Technical Specifications
Voltage input
2-wire, 120-volt; 3-wire, 120/240
configuration:
volt; 3-wire, 120/208-240 volt
Current Input:
Up to 200 amps rms AC
Power Factor:
0.5 leading or lagging
Frequency:
50 Hz to 400 Hz
Accuracy:
Certified to ANSI C12.1 (+/-1% of
reading from 1% to 100% of rated
load).
Voltage operating
range:
+
Temperature
range:
-20 degrees C to +50 degrees C
V25%
continuously;
overload: +100% for 20 cycles
Current
Can be overloaded 100%
overload: without damaging meter.
Display: Electro-mechanical
6-digit
display
Standard 120 volt; 100 or 200 amps
ranges:
120/240 volts; 100 or 200 amps
120/208 volts; 100 or 200 amps
Troubleshooting Guide
The Class 4000 electronic kilowatt-hour meter is caibrated and tested at the factory be-
fore being packaged and shipped. If installed properly and in accordance with the instal-
lation instructions, the Class 4000 meter will provide years of trouble-free service. If the
meter should not function, the following guide will assist in troubleshooting the instal-
lation. If, after following the procedures below, the meter still does not function, please
call E-Mon’s technical department at (800) 334-3666 BEFORE removing the meter.
PROBLEM
PROCEDURE TO FOLLOW
1. Display reads all ZEROs, or
is not incrementing.
.
A. Determine if the load is sufficient to update the
display. (A load of less than 1% of the meter rating
may require more than 24 hours to change the
display reading.)
B. Check the current sensors for installation.
C. Be sure that the current and voltage inputs have
proper phase relationship.
D. Check wiring to voltage terminals.
E. Check circuit breaker or fuses.
F. Test source for correct voltage.
2. Display reads only a fraction
A. Check the supply voltage to be sure that it is on
of the power consumption.
continuously 24 hours a day.
B. Check the current sensors for installation and
polarity.
C. Check the sensor wiring to the terminal block in
the meter (color coding white to white and black to
black).