Testing 

Turn  the  LUX  adjuster  fully  clockwise  (SUN);  turn  the  TIME  adjuster  fully  anti-clockwise  to  the 
minimum (10s). 

 

Switch on the AC supply and after a 30sec warm-up period 
the sensor will now be in test mode   

 

Walk  test  the  sensor,  when  the  sensor  receives  a  valid 
trigger  signal  within  its  detection  area  the  lamp  will  turn 
on.    If the sensor does not receive any other valid trigger 
signal then the light should switch off 10sec (±3sec). 

 

While the lamp is on and if the sensor receives additional 
valid trigger signal then the timer will re-start and the light will remain on. 

 

Adjusting SENS adjuster for desired the detection range.     

 

Walk  test  immediately  outside  the  area  to  ensure  no  detection  or  activation  through  walls  and 
floors to minimize unwanted activations. 

 

After  testing  the  sensor ensuring  the  required  area  can  be  detected, Turn  the  LUX  adjuster to the 
required light operational level, adjust the TIME adjuster clockwise to the required time for the light 
duration to be on. 

 
Troubleshooting 

 

The load does switch on: 

o

 

  Please check the connections, and the AC mains supply is on 

o

 

  Please check if the load is operational 

o

 

  Please check the adjustment settings and make the necessary adjustments if required 

 