INSTRUCTIONS FOR SELF-DIAGNOSTIC TEST:

 

 

Once the unit is properly installed according to the installation instruction sheet and AC power supplied, 

the dual color LED indicator will come ON and the self-diagnostic test function will automatically initiate. 

The LED indicates the unit’s status. A STEADY GREEN LED indicates normal service; FLASHING 

GREEN indicates the unit is testing; GREEN/RED FLASHING indicates the battery is charging; RED (in

different combinations) would indicate a service alert. Refer to the SERVICE INDICATION chart below for

more details. The LED would be OFF when the unit is in emergency mode.      

  

 

 

 

 

 

 

SELF-DIAGNOSTIC SERVICE

 

 

The self-diagnostic function is factory preset and performs the following:

a.  Monitoring of battery, battery charger, and lamps.

b.  Self-testing and a 30-second or longer discharge once every 30 days, after AC power has been 

     supplied for a minimum of 24 hrs.

c.  Self-testing and a 30-minute  or longer discharge once every 180 days, after AC power has been 

     supplied for a minimum of 24 hrs.

d.  Self-testing and a 90-minute discharge once every 365 days, after AC power has been supplied for

     a minimum of 24 hrs.     

 

 

 

 

 

 

 

 

SERVICE INDICATION

 

MANUAL TESTING

 

 

WARNING:

The unit also provides for manual testing by pushing the test button in a specific pattern. 

 

 

n

o

it

a

c

i

d

n

D

E

L

 

&

 

n

o

it

c

a

e

R

 

n

o

it

c

A

Push test button Once (within 2 seconds) 

30-second test: FLASHING Green 

Push test button Twice (within 2 seconds) 

30-minute test: Green FLASHING twice 

Push test button Three times (within 2 

seconds) 

90-minute test: Green FLASHING three times 

Push test button and hold for 3 seconds (In 

test mode) 

Cancels test. If self-test is cancelled it is recommended that a 

manual test of the same duration be performed at a more 

convenient time to ensure compliance

Push test button and hold for 6 seconds (In 

test mode) 

System reset

 

 

 

 

a)  Make sure that power is OFF before making any electrical connections.

b)  Unused wires must be capped using enclosed wire nuts.  

 

 

 

 

 

s

u

t

a

t

S

 r

o

t

a

c

i

d

n

D

E

L

 

s

c

i

n

o

rt

c

e

l

e

 

e

c

a

l

p

e

R

 

d

e

h

s

a

lf

 

e

n

O

 

y

r

e

tt

a

b

 

e

c

a

l

p

e

R

 

d

e

h

s

a

lf

 

o

w

T

 

 

 

Four flash red

 

Replace lamp head board

 

 

 

 

 

  

 

Steady red

 

Battery disconnected

 

Solid green

 

Trickle charge

 

Flashing green

 

In test

 

Red/Green flashing

 

Hi charge

 

 

 

 

Summary of Contents for E-XML4 Series

Page 1: ...wire nut 1 Separate front cover from back plate with a flat blade screwdriver Open from top slot first and then from side slots gently See Figure1 2 Remove knock out hole in the center of the back plate Remove knock out slots on the back plate that correspond to the size of the junction Box 3 Feed AC supply leads through the center hole in the back plate Then make the proper electrical connections...

Page 2: ... female White Neutral Red or Orange for 277V Printed Circuit Board Transformer power Connector male Battery Connector Front cover assembly Frame Black for 120V White Neutral Red or Orange for 277V Screw 8 32 0 875 Transformer power Connector male Back plate 120VAC 0V NEUTRAL 277VAC GROUND GREEN Green Ground wire Page 2 of 4 PCBA BAT Transformer Power Connector Transformer LED Front Cover LED Modul...

Page 3: ...k for 120V White Neutral Red or Orange for 277V Screw 8 32 0 875 Heater power connector male Transformer power Connector male Back plate JUMPER Heater power connector female Printed Circuit Board Note 1 2pcs short circuit connector in the accessory bag 2 For 120Vac input connection short circuit connector insert in female connector marked JUMPER in slots 1 and 2 3 For 277Vac input connection short...

Page 4: ...lf testing and a 90 minute discharge once every 365 days after AC power has been supplied for a minimum of 24 hrs SERVICE INDICATION MANUAL TESTING WARNING The unit also provides for manual testing by pushing the test button in a specific pattern n o i t a c i d n I D E L n o i t c a e R n o i t c A Push test button Once within 2 seconds 30 second test FLASHING Green Push test button Twice within ...