background image

INSTALLATION:

1. Remove the front cover. When required, remove battery to access J-box mounting holes.

2. Mount the equipment securely in place on the wall. Two additional ‘Key Hole’ mounting holes are located at the 
top of the unit housing in addition to the ‘J-Box’ mounting holes. These ‘2’ additional mounting slot holes must be 
used when the unit is mounted to the wall. Additional chain support may be required by local codes.

3. Extend 24hr AC supply of rated voltage to the equipment, which is furnished with a dual voltage (120/277V) field 
selectable input. Connect unit to utility power using an approved connector. For 120V supply connect the line wire 
to the Black lead and for 277V supply connect the line wire to the Orange lead. Connect neutral wire to the White 
lead. The Ground wire (green lead) needs to be connected in accordance with the local codes. DO NOT energize 
the circuit at this time.

CAUTION: insulate the unused Black or Orange wire. Failure to do so may cause an unsafe condition.

4. Install and connect the battery. Refer to the Illustration. Connect the Red (+) lead from the PC board assembly to 
the positive (+) terminal on the battery and the Black(-) lead from the PC board assembly to the negative (-) battery 
terminal.

CAUTION: Observe polarity. Failure to connect the battery properly will result in equipment failure and an unsafe 
condition. NOTE: The Emergency lights will NOT come ON at this time.

5. Energize the unit with AC supply. The charge indicator will illuminate.

6. Replace the unit cover.

7. Adjust and focus the lighting heads as required.

OPERATION:

1. To test the equipment, depress the TEST switch and the emergency lights will illuminate.

2. Once you release the TEST switch the emergency lights will turn OFF.

3. The automatic charger will return into action, charging the battery and trying to maintain it in a fully charged state. 
NOTE: Allow the battery to charge for a minimum of 24 hrs after installation or after a power failure before conduct-
ing a 90-minute test (see TESTING section). CAUTION: This equipment is furnished with a sophisticated solid 
state transfer switch which will automatically disconnect the emergency lights from the battery if the battery has 
been discharged to the end of its useful output.

PAGE 2

SAVE THESE INSTRUCTIONS