DyTerra NH3 Assembly Manual Download Page 18

QUICK SET-UP GUIDE 

Note: A tutorial also available on DyTerra’s YouTube Channel

When the console is powered up for the first time it will flash CAL and US VOLUME PER ACRE. This means the console 
must be programmed before operation.
1.  To begin programming, 

ENTER

 to accept US VOLUME.

2.  Display will now flash SP1-WHEEL DRIVE 
  a)  Press the 

CE button

, display will now show SP2-RADAR SPEED SENSOR. 

ENTER 

to accept SP2.

3.  Display will now flash C-CD-STANDARD VALVE 
  a) If you have a 2 valve system (Tagged #2123 on the valve) then 

ENTER

 to accept standard valve 

  b) If you have a single FAST VALVE (Tagged #743 on the valve) then press 

CE button

 until you come to C-FC-FAST    

    CLOSE VALVE and 

ENTER

 to accept.

4.  Display will now flash CAL SELF TEST 0.0. Leave this as-is for now.  

 NOTE:

 FOR THE FOLLOWING CALIBRATION SETTINGS YOU WILL NEED TO 

DEPRESS THE KEY

 IN WHICH YOU WANT TO  

  ENTER DATA, FOLLOWED BY 

ENTER

, FOLLOWED BY THE 

NUMBER YOU WISH TO ENTER

, FINALLY FOLLOWED BY 

ENTER

  

  AGAIN TO SAVE.
5.  Next press 

BOOM 1 CAL

 button and then 

ENTER

 and then enter the width of your applicator in INCHES (i.e.: 720” for   

 60ft.). 

ENTER

 to save.

6.  Boom 2 and 3 width should both be zero, if they are not, then enter 0 for both.
7. Press 

SPEED CAL

 button then 

ENTER

, then enter a speed calibration number, then 

ENTER

.   

 

NOTE:

 For Raven Phoenix 10 GPS Sensor, use Cal #785 and for Raven Radar Gun use #586. 

  a) If your Raven console speed does not match up with your actual tractor speed or you are using a third party speed  
    sensor, you can just increase or decrease the Cal number until they match.
8. Press 

METER CAL

 button then 

ENTER

, then enter the calibration number from the flow meter, then 

ENTER

  a) The Meter Cal number is on a grey tag located on the flow meter under the Raven cooler. It will have a number  
    (i.e.: 169/lbsN) on it. This is the number you use. NOTE: DO NOT USE LIQUID OR LITRES number. 
  b) This is also the number you can change if you find you are over applying or under applying.  To do this, take your  
    desired application rate divided by the rate you applied and multiply by the flow meter number  
    (i.e.: 100lbs / 90lbs x169 = 187 as new number).
9. Press 

VALVE CAL

 button then 

ENTER

 and enter your calibration number then 

ENTER

.   

  a) Your Valve Cal number is on the valve motor. For a standard two-valve system the number is 2123 and for a single  
    fast valve setup it’s 743. 
10. Press 

RATE 1 CAL 

button then 

ENTER

, then enter desired lbs. of N to be applied (should be a rate you typically apply at,  

  i.e. 100 lbs.) then 

ENTER

.

11. Press 

RATE 2 CAL

 button then 

ENTER

 then enter Rate 2 desired lbs. of N to be applied then 

ENTER

. This provides the  

  ability to switch to a higher or lower application rate on the fly. 

IMPORTANT NOTE:

 You must enter a number in RATE 2  

  to complete calibration process.

16

RAVEN 440 CONSOLE

Summary of Contents for NH3

Page 1: ...NH3 KIT ASSEMBLY GUIDE MIINST NH3 KIT GUIDE...

Page 2: ...r item in the table of contents and disregard any items that do not apply to the kit you have purchased If you need assistance or have any questions that are not answered in this guide please give us...

Page 3: ...D SECTION CONTROL 9 JOHN BLUE MANIFOLD NO SECTION CONTROL 10 JOHN BLUE MANIFOLD SECTION CONTROL 11 JOHN BLUE SPLITTER 12 CHECK VALVE SECTION CONTROL ONLY 13 HIGH FLOW BREAKAWAY KIT 14 HOSE LENGTHS 15...

Page 4: ...sembled they can be attached to your applicator Mount the pressure gauges so you can see them from the tractor cab if possible When running lines keep in mind how many folds your applicator has and wh...

Page 5: ...unevenly to each manifold which will result in streaking Connect each manifold outlet to a shank or boot STEP 5 BREAKAWAY KIT Install the breakaway bracket at the back of your cultivator according to...

Page 6: ...VES AND FLOWMETER Part Part Number A Continental Superflow Cooler CTA SF 3000GT B Raven Fast Valve 1 RV1 063 0173 878 C Raven Flowmeter RV1 063 0173 867 D 1 Strainer MIPAGET24 100 E 1 Ball Valve BVSS2...

Page 7: ...CONTINENTAL COOLER BREAKDOWN 5 O Ring included in CTA SF RK A SF 2 A SF 1 Base Barb 7550 4 O Ring included in CTA SF RK Bleeder Valve A 411 2 Bolt 09 375 125 4 Screw A 400 250 Hose Barb A 1132...

Page 8: ...EN Flowmeter Sensor RV1 063 0171 669 D Gruvlock Coupling RV1 333 0006 032 E 0 400 PSI Liquid Gauge PGA4004L F RAVEN Control Valve RV1 117 0171 706 G RAVEN On Off Valve RV1 117 0171 705 H Strainer Kit...

Page 9: ...CONTINENTAL B 9500 METER SETUP 7 A CTB 9500 B B MICMS24...

Page 10: ...Gauge Product In King Nipple MVD Manifold Product Out Stand 4 HELPFUL POINTERS Use thread tape and thread sealant when installing the king nipple MVD MANIFOLD NO SECTION CONTROL 8...

Page 11: ...quicker on off response time for each section If you mount the on off valves at the splitter it will take longer for product in the lines to get to the ground when turning that section on and will all...

Page 12: ...In Tee 6 Nipple Stand Product Out King Nipple 10 HELPFUL POINTERS Use thread tape and thread sealant when installing connecting plumbing Use thread sealant when installing plumbing and hosebarbs JOHN...

Page 13: ...response time for each section If you mount the on off valves at the splitter it will take longer for product in the lines to get to the ground when turning that section on and will allow more produc...

Page 14: ...lon tape and pipe sealant to assemble plumbing 1 Plug 6 Nipple 1 Tee Splitter 6 Nipple Product In Splitter Splitter stand Product Out to Manifolds Product Out to Manifolds Product In 12 Q Do hoses fro...

Page 15: ...lve which regulates what rate you are applying NH3 at The second valve is an on off valve that allows you to quickly stop or start applying NH3 The advantage of having two valves is that when you turn...

Page 16: ...cket Part STFM150K Repair Kit 1 Part STFM150 0022 Plunger Kit 1 STFM150 0023 1 CONTINENTAL WITH BRACKET Part CTB SWV 125 D Repair Kit Part CTA SWV125150 RK o rings Rebuild CTA SWV125150 RBK 1 CONTINEN...

Page 17: ...NIFOLD SETUP 4 MANIFOLD AND UP SETUP FOR MAXIMUM ACCURACY KEEP ALL HOSES BETWEEN SPLITTER MANIFOLDS EQUAL LENGTH NOTE Hoses from the manifolds to the ground should also be the same length 15 HOSE LENG...

Page 18: ...or Raven Phoenix 10 GPS Sensor use Cal 785 and for Raven Radar Gun use 586 a If your Raven console speed does not match up with your actual tractor speed or you are using a third party speed sensor yo...

Page 19: ...will also wipe out all the calibration settings you just entered This is done by turning the power switch OFF then depress and hold the CE button while turning the power switch back ON Program all set...

Page 20: ...low meter may have burnt out Flow meter replacement parts are on page 10 of the DyTerra Catalogue 1 Check the control valve cabling for wear or breaks 2 Check and clean cable connections 3 Check the v...

Page 21: ...UME should increase by increments of 1 or more counts 5 If TOTAL VOLUME does not increase remove the section of cable and repeat test at the connector next closest to the console Replace defective cab...

Page 22: ...ou have a faulty cable or connection Check or replace implement harness 7 If there is voltage remove the flow sensor and check to see that the paddle wheel inside the flow meter is spinning freely If...

Page 23: ...DICKEY john Actuator Part Number DJ467095060 required when upgrading to a CTA BVT valve Flow Sensor Module Part Number DJ457901570AS1 Part Number DJ457904000 DICKEY JOHN COMMON REPLACEMENT 21...

Page 24: ...A RV1 063 0172 982 RV1 117 0171 686 RV1 117 0159 410 1 VALVES 1 CONTROL VALVE N A RV1 063 0173 206 N A RV1 117 0171 355 1 ON OFF VALVE N A RV1 063 0173 207 N A RV1 117 0171 355 1 FAST VALVE N A RV1 06...

Reviews: