3.2.6 Connecting inverter
Caution:
A external DC Breaker that operates both positive and negative conductors
simultaneously between the BDU and inverter on the power cable is recommended.
After waking up the BDU and ensure that the BDU is pre-charged, you can turn on it.
Danger:
Please confirm that the battery system is in the off state before connecting. It may cause
electric shock to personnel and damage to the inverter if connect the battery directly
without power off.
Connect the positive and negative connectors with the positive and negative power lines
together. Both ends must have connectors, and the connector on the inverter side is
provided by the inverter. If that 2m power cable is not long enough, please find another
power cable of the same specification, the length cannot be longer than 3m.
●
Connect External Power Cable to the inverter;
●
Connect the INVERTER-CAN communication cable to the inverter RJ45 CAN port.
Connect to inverter DC- terminal
Connect to inverter DC+ terminal
Connect to inverter RJ45 CAN communication port