Dyness battery and Growatt off grid inverter Setup 

 

Check List: 

 
Dyness B4850 * 4   
Power cable*1 pair 
Parallel cable*3 pairs 
Communication cable Bat-Inv*1 
Communication cable Bat-Bat*3 
Growatt SPF 5000TL HVM-ES 

 

Before start,

 

make sure battery and inverter size match.

 

Follow Dyness user manual to check details, it is recommended to 
use battery in 1: 2 configuration. 
In our case now, 5kW inverter connects to 9.6kWh battery. 

 

 
Step 1 : Cable connect in inverter 

Keep both inverter and battery completely off. 
Connect power cable and comm cable to inverter first. 
Note: Comm cable has label on, make sure the inverter side goes 
to battery side, inverter side to the inverter BMS side ,battery side 
left for later on in battery connection. 

 

 

Summary of Contents for DYN-B4850

Page 1: ...tch Follow Dyness user manual to check details it is recommended to use battery in 1 2 configuration In our case now 5kW inverter connects to 9 6kWh battery Step 1 Cable connect in inverter Keep both inverter and battery completely off Connect power cable and comm cable to inverter first Note Comm cable has label on make sure the inverter side goes to battery side inverter side to the inverter BMS...

Page 2: ...er cable parallel cable communication cable Bat Inv and comm cable Bat Bat as above 1 Comm cable from the host CAN IN port to the inverter CAN port 2 Comm cable from the host CAN OUT to slave1 CAN IN slave1 CAN OUT to slave2 CAN IN 3 Power cable should be connected diagonally one is connected at the top socket and another one is at the bottom ...

Page 3: ...er or Fuse between inverter and battery to protect both products Step 5 Switch on all the B4850 power switch then press the host SW button about 3S to wake up it all the slaves will be woken up automatically Step 6 Turn on the DC breaker Step 7 Power on the inverter ...

Page 4: ...inverter are connected Now inverter is started it should show the battery voltage battery and inverter are connected Step 11 Inverter setup Long press ENTER to set make sure 05 are properly set as below 05 LI type Lithium ...

Page 5: ...go Step 13 Shut Down 1 Remove all the load 2 Disconnect PV Grid 3 Turn off DC breaker between the battery and inverter 4 Turn off the inverter power switch shut down the inverter 5 Long press SW button to power off the battery then switch off all the batteries Power switch ...

Reviews: