background image

DynaQuip Controls • 10 Harris Industrial Park • St. Clair, MO 63077
Tel. 800-545-3636 • Fax. 636-629-5528  • www.watercop.com

8

WARNING! 

Before opening case, unplug power cord. When case is open, it is possible to  

contact electrified components. Always unplug the power cord before opening the unit. 
Wear eye protection for plumbing and electrical work. 

Notice:

 WaterCop

®

 should be installed downstream of existing shut-off valves and pressure reducers.  

Install 18” downstream from existing indoor water meters to allow for future meter maintenance. 

Manually Test the Valve

To test your WaterCop

®

 CLASSIC System, gently pull the safety plugs out from each end of the valve . Check the position of 

the valve by looking in either threaded end .
In the open position, you will be able to see through the valve; in the closed position only the shiny surface of the ball 

will be visible . Place the base of the housing on a sturdy surface, as close as feasibly possible to the location where it 

will be permanently installed . Plug the WaterCop

®

 power cord into a nearby 120 VAC outlet . The valve position indicator 

lights should now correspond to the actual position you noticed: Green = Open, Red = Closed . Grasp both sides of the 

housing (not the valve) with the valve pointing away from you for safety . Being very careful not to have your fingers 

or other objects near the valve openings, press the colored circle just below the unlit indicator light . You will hear the 

motor change the valve position . Again, look into the threaded end of the valve to verify that the valve has changed 

position . 

If it appears that the valve has not turned from one position to the other, DO NOT try to reposition the valve 

yourself by inserting any tool or fingers into the valve. 

Operate the valve several more times from open to close, 

checking each time for proper positioning . If you are experiencing trouble getting the valve to open and shut, call the 

800 number listed below .

Manually Test the Flood Sensors

Flood and Temperature sensors require power to operate . Use either fresh “AA” alkaline batteries (not included) and/or a 

WaterCop

®

 AC Adaptor (sold separately) to power . If both are used, batteries will provide back-up power in the event AC 

power is lost . Rechargeable batteries are not recommended . To install batteries, remove the battery cover located on the 

back of the sensor and install batteries in accordance with the (+ and -) placement guide . Reinstall the back plate . 
Follow suggestions found in the section titled “Placement of Flood Sensors” for recommendations where sensors should 

be placed . Locate a wall near the area you choose to monitor .
Avoid high traffic areas where cord or sensor could be stepped on or kicked . Mount transmitter at a convenient location on 

the wall, two to three feet above the floor . This will help avoid damage to the sensor and provide a strong signal . Use hook 

and loop fastener included with the unit .
1 .   Following all safety precautions, make sure that the WaterCop

®

 is plugged in and the valve is in the OPEN position . 

Leave the WaterCop

®

 near your main water line, on a sturdy surface . It is important that anyone who will be near the 

valve is aware of the safety precautions, and does not insert any object into the valve, or handle the valve during  

the test .

2 .   At one of the locations you have chosen to monitor, drop the sensor probe (not the mounted transmitter) into a cup of 

water . Hold until you hear the sensor transmit a signal to the WaterCop

®

 (about 5 seconds) . The signal will be a series of 

short beeps followed by a long tone . This test simulates a leak, and lets you check for interference between the sensor 

and the WaterCop

®

 .

3 .   Take the sensor out of the water and carefully dry off the sensor and prongs . It should stop beeping .
4 .   Go back to your WaterCop

®

 and verify that the valve has closed (the red indicator light will be lit) .

5 .   Keeping all objects away from the valve, reset the WaterCop

®

 by pushing the green circle below the OPEN text .

6 .   Repeat steps 2 through 5 until you have tested each sensor directly in the locations you wish to monitor .

STOP

Summary of Contents for WaterCop classic

Page 1: ...1 DynaQuip Controls 10 Harris Industrial Park St Clair MO 63077 Tel 800 545 3636 Fax 636 629 5528 www watercop com CLASSIC Owner s Manual Installation Guide...

Page 2: ...llation Prodedure 9 Review Location and Type of Main Supply Line 9 Additional Part Requirements 10 Compression Fittings 10 Solder Fittings 11 Electrical Connection 11 Warnings and Precautions 11 Chang...

Page 3: ...m TRANSMIT RECEIVE Range Enhancing Repeater DynaQuip Controls Inc St Clair MO www watercop com Water Sensor Transmitter DynaQuip Controls Inc St Clair MO www watercop com LISTED 57HM Range Enhancing R...

Page 4: ...es The WaterCop valve should be installed in the main water line just downstream from the main shut off valve in your home The front control panel of the WaterCop should be easily visible in order to...

Page 5: ...ets may disturb it The sensor probe should be placed FLAT on the floor so water can be detected as soon as it begins to accumulate The sensor probe may be secured to the floor with adhesive dots suppl...

Page 6: ...interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful int...

Page 7: ...of the valve when testing WARNING The WaterCop case is NOT EXPLOSION PROOF The shut off valve must NOT be installed where it could ignite flammable vapors or explosive mixtures WARNING To reduce risk...

Page 8: ...below Manually Test the Flood Sensors Flood and Temperature sensors require power to operate Use either fresh AA alkaline batteries not included and or a WaterCop AC Adaptor sold separately to power I...

Page 9: ...ire are clear of doors drawers sharp edges or other hazards that may cause damage Unplug the WaterCop after the testing is complete The WaterCop can now be installed Prior to installation read all war...

Page 10: ...choice of fittings and methods of installation Compression Fittings Theunitcanbeinstalledwithcompressionfittingsusingcommonhouseholdtoolsandbasicmechanicalability Youwillneed a 2 fittings male pipe th...

Page 11: ...c items we recommend plugging the WaterCop Actuator into a surge protector Warnings and Precautions WARNING The motorized drive unit case is not capable of supporting any loads Do not attempt to use t...

Page 12: ...ts 5 6 and 7 are used to control the valve position from a remote location The most common is your home security system control panel This is done by wiring these contacts to a control switch on the p...

Reviews: