White Paper: How to Connect HS35iQ Encoder Fault Output to a PLC 

P a g e

 | 

 

 

 

 

DYNAPAR   |   

Phone: 1.800.873.8731   |   Website

www.dynapar.com 

   

 

 

Rev 1-9-2023-1

 

 
Software Setup 

 
The routine written to read the fault output and turn on the LED is shown in Figure 2. 
 

 

Figure 2. PLC software routine 

 
An Examinine Off was used as the fault output is high during non-fault conditions and transitions to low when a 
fault occurs.  The routine simply reads the status of the fault output on 

DC IN 0

 and will energize 

DC OUT 08 

connected to the LED if a low condition is read. 
 

 
Testing 

 
After everything was connected properly, the program was downlaoded to the PLC and it was set to run mode.  
To test proper functionality a cable fault was triggered by detaching the load resistor from one of the encoder 
outputs (A/B/Z).  The cable fault LED on the encoder transitions to 

RED

 

at the same time the LED connected to 

the PLC turns on (Figure 3).  After the fault is corrected the cable fault LED on the encoder turns 

GREEN

 

and 

the LED on the PLC turns off (Figure 4). 
 

 

Figure 3. PLC indicating active fault output 

Summary of Contents for HS35iQ

Page 1: ...ee an example of how to connect the fault output of the HS35iQ encoder to a PLC with example connection diagrams and necessary accessories How to Connect HS35iQ Encoder Fault Output to a PLC White Paper ...

Page 2: ...e Setup The following components were used to test this example HS35iQPROGR81721R2 encoder with 2 2k load resistors L27ERM QBFC1B PLC 24V DC Power supply LED with current limiting resistor The supply terminals for the PLC and the encoder were both connected to the same 24V DC power supply The 24V power supply was also connected to the V and COM0 connections on the DC OUT port included with the PLC...

Page 3: ...White Paper How to Connect HS35iQ Encoder Fault Output to a PLC P a g e 3 DYNAPAR Phone 1 800 873 8731 Website www dynapar com Rev 1 9 2023 1 Figure 1 Wiring diagram for example ...

Page 4: ...atus of the fault output on DC IN 0 and will energize DC OUT 08 connected to the LED if a low condition is read Testing After everything was connected properly the program was downlaoded to the PLC and it was set to run mode To test proper functionality a cable fault was triggered by detaching the load resistor from one of the encoder outputs A B Z The cable fault LED on the encoder transitions to...

Page 5: ...kit encoders to large mill duty tachometers Dynapar has a strong market presence in a wide range of industries including steel paper elevator oil and gas aerospace defense medical material handling and industrial servo manufacturing Dynapar offers a broad array of encoders and resolvers through our well established Dynapar Hengstler NorthStar and Harowe brands Dynapar supports global customers wit...

Reviews: