Dynalite DBC410 Installation Manual Download Page 7

DBC410 Installation Manual Rev K.docx

   7

 

AUX Input 

- This is a dry contact interface that is active low.  The dry contact is connected between the AUX 

and GND terminals on the DyNet connector strip.  The function of the AUX input is programmable.  Ensure 
that the cable length between the dry contact and terminal strip is no longer than 2 metres.

 

 

Service LED

 - The Service LED has 3 signalling modes, which are useful for troubleshooting:

 

Blinking slowly (1Hz) = Normal Operation 
Blinking fast (4Hz) = Network Activity Detected 

On = Fault 
 

Service Switch

 - The Service Switch has three functions: 

1 push = Transmit Network ID 
3 pushes = All Channels 100% 
Push & hold for 4 sec = Reboot 

 

Top Set

 - This adjusts the maximum output that all other control sources can select, ie: if the Top Set is fully 

clockwise,  100%  selected  by  a  control  source  will  give  100%  output.    If  it  is  fully  anti-clockwise,  100% 

selected by a control source  will give 50% output. This control is useful for extending lamp life and can be 
operated  without  any  form  of  network  control,  effectively  turning  the  device  into  a  stand-alone  power 
conditioner and lamp protector. 

 

Accessory Module Socket

 - Accepts plug in modules for optional features such as DMX512 ports and Time 

clocks. Consult your distributor for details on the available accessory modules. 

 

 

Summary of Contents for DBC410

Page 1: ...er Installation Manual contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Supplied by ...

Page 2: ...eck Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specifi...

Page 3: ...pply Connections Knock Out For Low Voltage Cable Entry Glands for Load Cables 225mm 320mm DyNet Network Connections Control CPU Relays Mounting Point Network Socket Service Switch EARTH LINK Depth 75mm Transformer SHEILD GND D D 12V AUX 0V CH 1 CH 2 CH 3 CH 4 N1 N2 N3 N4 LINE 4 LINE 3 LINE 2 LINE 1 For spare parts please call your nearest Dynalite Customer Service Centre and specify DBC410 ...

Page 4: ...kets are designed to accommodate 4 fixing screws up to 8mm diameter The DBC410 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control...

Page 5: ...rol Cables Load control cables can be terminated on the 2 x 4 way terminal strips located directly above the Load terminals The left terminal block is the output for 0 to 10V or DSI if selected by software setup Note that most types of 1 10V HF Fluorescent Ballast control wiring is polarity conscious The terminal of the ballast connects to the left terminal block and the terminal connects to the r...

Page 6: ... pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended ...

Page 7: ...ervice Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This adjusts the maximum output that all other control sources can select ie if the Top Set is fully clockwise 100 selected by a control source will give 100 output If it is fully anti clockwise 100 selected by a control source will give 50 output This control is useful for ext...

Page 8: ...ol cable from DBC410 to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings specification Supply 230V 14 50 60Hz Single Phase at 40A Outputs 4 x switched outputs at 10A 4 x signal control outputs selectable to 1 10VDC and DSI Optional Maintained Output 1 x Maintained NC output for testing battery packs in fixtures ...

Reviews: