Settings
46
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
1
The user must manually stop the controller by pressing the off button.
2
The controller must be
o
powered down or
o
a reset initiated by
§
going from the RUN mode to the AUTO or OFF mode, or
§
changing a setting in the menu and exiting the menu system.
4.4.6.1 Fault Monitor Example
In this example, a sensor is monitoring the temperature of an engine block. If the temperature rises above 275°F, a warning
message is displayed. If the temperature rises above 350°F, the engine shuts down and a failure message is displayed.
Relevant Settings
Setting
Value
Signal Source
Same as Engine Temperature
Display
Disable (If enabled, controller will display Engine Temperature twice)
Sensor Type
Same as Engine Temperature
Sensor Table Name
Engine Temp.
Active Range
Running
Mode Select
Fault Monitor
Setpoints -> Low Warning
Disabled
Setpoints -> Low Failure
Disabled
Setpoints -> High Warning
275°F
Setpoints -> High Failure
350°F
The chart above shows the connection between engine temperature and time. At approximately 13 minutes run time, the
temperature rises above the 275°F warning threshold, activating the warning display. The engine will continue to run because it
has not reached the 350°F failure threshold. At 20 minutes run time, the temperatures falls below the warning threshold and the
warning disappears.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...