Dyna-Glo IR12DTL-2 Manual Download Page 9

8

PREPARING FOR INSTALLATION

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with

doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space Length × Width × Height = cu. ft. (volume of space)

  Example: Space size 20 ft. (length) × 16 ft.(width) × 8 ft. (ceiling height) = 2560 cu. ft. (volume 

  of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these 

rooms to the total volume of the space.

2. Divide the space volume by 50 cu. ft. to determine the maximum BTU/hr the space can support.

  _______ (volume of space) ÷ 50 cu. ft.= (Maximum BTU/hr the space can support)

  Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum BTU/hr the space  

  can support)

3. Add the BTU/hr of all fuel burning appliances in the space.

  Vent-free heater _________ BTU/hr

  Gas water heater* ________BTU/hr

  Gas furnace _____________BTU/hr

  Vented gas heater ________BTU/hr Example:

  Gas heater logs __________BTU/hr Gas water heater 30,000 BTU/hr

  Other gas appl ____BTU/hr Vent-free 26,000 BTU/hr

  Total = ____BTU/hr Total = 56,000 BTU/hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the

 outdoors and vents to the outdoors.

4. Compare the maximum BTU/hr the space can support with the actual amount of BTU/hr used.

  _______ BTU/hr (maximum the space can support)

  _______ BTU/hr (actual amount of BTU/hr used).

  Example: 51,200 BTU/hr (maximum the space can support) 56,000 BTU/hr (actual amount of 

  BTU/hr used)

The space in the above example is a confined space because the actual BTU/hr used is more than 

the maximum BTU/hr the space can support.

You must provide additional fresh air. Your options are as follows:

a) Rework worksheet, adding the space of an adjoining room. If the extra space provides an 

  unconfined space, remove door to adjoining room or add ventilation grills between rooms. See  

  “Ventilation Air From Inside Building,” page 9.

b) Vent room directly to the outdoors. See “Ventilation Air From Outdoors”, page 9.

c) Install a lower BTU/hr heater if lower BTU/hr size makes room unconfined. If the actual BTU/hr  

  used is less than the maximum BTU/hr the space can support, the space is an unconfined space. 

  You will need no additional fresh air ventilation.

Summary of Contents for IR12DTL-2

Page 1: ...en connecting this appliance to a specified fuel supply at the time of installation Change of the selector setting to other than the fuel type specified at the time of installation could damage this a...

Page 2: ......

Page 3: ...ropane Ignition Electronic Push Button Manifold Pressure 5 in W C 10 in W C Inlet Gas Pressure Maximum 14 in W C 14 in W C M nimum For purposes of input adjustment 6 in W C 11 in W C Dimensions in H x...

Page 4: ...able vapors and liquids WARNING Do not place clothing or other flammable material on or near the appliance Never place any objects on the heater WARNING Due to high temperatures locate this appliance...

Page 5: ...servicing Only a qualified service person should service and repair heater 9 To prevent performance problems do not use propane LP fuel tank of less than 100 lbs capacity 10 WARNING Do not allow fans...

Page 6: ...DELS The fan kit helps to distribute the warmed air into the space more rapidly NOTE This is an optional accessory and is not required for operation of the heater State of Massachusetts The installati...

Page 7: ...r produces approximately one 1 ounce 30 mL of water for every 1 000 BTUs 3 Kw of gas input per hour An unvented room heater is intended as a supplemental heater rather than a primary heat source In mo...

Page 8: ...unconfined space This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air Adjoining rooms are...

Page 9: ...TU hr Example Gas heater logs __________BTU hr Gas water heater 30 000 BTU hr Other gas appliances ____BTU hr Vent free heater 26 000 BTU hr Total ____BTU hr Total 56 000 BTU hr Do not include direct...

Page 10: ...se items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation fo...

Page 11: ...loor using the support legs Select models WARNING Maintain the minimum clearances shown in See Fig 3 If you can provide greater clearances from floor ceiling and joining wall Fig 3 Mounting clearances...

Page 12: ...etween the locked positions 3 Remove plug from the inlet of the NG regulator 4 If the LP plug was removed previously apply thread sealant to ensure that there are no leaks and install the NG plug into...

Page 13: ...FAN OPTIONAL WARNING Electrical Grounding Instructions This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a prope...

Page 14: ...e table where the heater will be placed for leg installation to prevent scratch ing of the table and or the heater 2 Set back of heater on table with the bottom of heater extending outside the table e...

Page 15: ...pe mounting bracket to wall where heater will be located Make sure mounting bracket is level 2 Mark screw locations on wall See Fig 16 Note Mark only last hole on each end of mounting bracket Insert 2...

Page 16: ...h expansion bracket 6 Insert expansion bracket screws ST4 8 15 16 through wall mounting bracket and into expansion brackets 7 Tighten expansion bracket screws ST4 8 15 16 until mounting bracket is fir...

Page 17: ...ust be a minimum 6 WC for NG 11 WC for LP with a max pressure of 14 WC for NG 14 WC for LP If gas line pressure is higher regulator damage could occur CAUTION Never connect heater directly to an LP su...

Page 18: ...3 5kPa The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psi 3 5 kPa Pres...

Page 19: ...hnician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS MANUAL GAS CONTROL 1 STOP Read the safety informatio...

Page 20: ...seconds after pilot lights Release control knob Note If pilot goes out repeat steps 3 through 7 Wait 1 minute before attempting to light pilot again If after several tries the pilot still goes out tur...

Page 21: ...between HIGH 5 and LOW 1 See Fig 25 MANUAL CONTROL OPERATION Manual valves remain burning in the HIGH setting until manually turned to OFF See Fig 25 Fig 25 Control Knob Position Manual Thermostatic O...

Page 22: ...28 shows a correct burner flame pattern Fig 29 shows an incorrect burner flame pattern with lifting and excessive flame height If burner flame is incorrect turn heater off see To Turn Off Gas to Appli...

Page 23: ...mpressed air no greater than 30 PSI You can use a vacuum cleaner in the blow position If using compressed air in a can please follow the directions on the can If you don t follow directions on the can...

Page 24: ...module or ignition module 7 Bad battery 1 Replace ODS Refer to care and maintenance on page 22 2 Replace ODS Refer to care and maintenance on page 22 3 Replace ignitor cable Refer to care and mainten...

Page 25: ...Delayed ignition of burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner see Care and Mainte nance page 21 or contact customer service Burner...

Page 26: ...r 3 Clean ODS pilot see Care and Maintenance page 22 Gas odor exists even when control knob is in OFF position 1 Gas leak See Warning Statement at top of page 22 2 Control valve is defective 1 Locate...

Page 27: ...E CAUSE PROBLEM QUALIFIED INSTALLING AGENCY Only a qualified agency should perform installation and replacement of gas piping gas utilization equipment or accessories and repair and servicing of equip...

Page 28: ...R30K GHP 03 L 1000 IR30K GHP 03 L 1000 6 Thermostatic Gas Valve SIT 630 1 0630560 0630560 0630560 7 Manual Gas Valve 1 GS7A 12K GS7A 18K GS7A 30K 8 Gas Selector Valve 1 GH01 GH01 GH01 9 Regulator Brac...

Page 29: ...______________________________________ TYPE OF STORE __________________________ CITY STATE WHERE PURCHASED ______________________________________________ PRICE PAID _______________________ Please Take...

Page 30: ...ds SAVE THIS CARD Place Postage Stamp Here GHP Group Inc 8280 Austin Avenue Morton Grove IL 60053 3207 GHP Group Inc 8280 Austin Ave Morton Grove IL 60053 3207 Tel 877 447 4768 www ghpgroupinc com 828...

Reviews: