LOAD

0 to 50 mV

POWER

SUPPLY

TRANSMITTER

Figure 8: Voltage (0 to 50 mV)

OPERATION

The sensor offset can be changed through the TBU-00 software. The USB cable may 

be connected to the transmitter without causing any measurement errors. See item  5 

Zero Offset on the first page of this manual. 

The user must choose the most suitable sensor and range to the process. The selected 

range must not exceed the maximum range of measurement defined for the sensor 

and should not be smaller than the minimum range for the same sensor. 

Note: 

The transmitter accuracy is based on the maximum range of the sensor used, 

even when a narrower range is programmed. 

Example:

•  The Pt100 sensor in the range 0 to 100°C and accuracy of 0.12%, the maximum 

  error will be 1.02°C  (0.12% of 850 °C )

•  The Pt100 sensor in the range of 500 to 600°C  and accuracy of 0.19%, the maximum 

  error will be 1.61°C  (0.19% of the 850°C )

Note: 

When  the  measurements  are  made  at  the  transmitter,  ensure  the  Pt100 

excitation  current  required  by  the  calibrator  is  compatible  with  the  Pt100  excitation 

current used in the transmitter: 0.8 mA. 

SAFETY INFORMATION

Any control system design should take into account that any part of the system has the 

potential to fail. This product is not a protection or safety device and its alarms are not 

intended to protect against product failures. Independent safety devices should always 

be provided if personnel or property are at risk.

Product  performance  and  specifications  may  be  affected  by  its  environment  and 

installation. It’s the responsibility of the user to assure proper grounding, shielding, 

cable routing, and electrical noise filtering are in accordance with local regulations, 

EMC standards, and good installation practices.

SUPPORT

 

This  product  contains  no  serviceable  parts  inside.  For  troubleshooting,  visit  our 

frequently asked questions at www.dwyer-inst.com or contact our technical support 

team at 1-800-872-9141. 

MAINTENANCE/REPAIR

Upon  final  installation  of  the  Model  TBU,  no  routine  maintenance  is  required.  The  

Model TBU is not field serviceable and is not possible to repair the unit. Field repair 

should not be attempted and may void warranty.

WARRANTY/RETURN

Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact 

customer service to receive a Return Goods Authorization number before shipping the 

product back for repair. Be sure to include a brief description of the problem plus any 

additional application notes.