Dwyer Instruments TBU-00 Specifications-Installation And Operating Instructions Download Page 1

Model TBU-00 Temperature Transmitter

Specifications - Installation and Operating Instructions

Bulletin T-TBU-00

The 

Model TBU-00 Temperature Transmitter

 is a high precision temperature 

transmitter designed to easily mount in most temperature sensor instrument 

enclosures. The universal input reduces inventory while the micro-USB port facilitates 

easy  configuration,  and  calibration  in  the  lab  or  in  the  field.  The  versatile  TBU 

model allows for selection and configuration of input type, measurement range, and 

calibration. The output can be set as either direct 4 to 20 mA, or reverse 20 to 4 mA, 

through easy to use configuration software.

Configuration

During  the setup, the transmitter is powered by the USB, and  does  not require  an 

external  power  supply.  See  Figure  1.  The  transmitter  setup  can  also  be  made  by 

connecting it to the loop using the loop power supply. There is no electrical insulation 

between  the  transmitter  and  the  communication  port  (interface),  therefore  do  not 

configure the transmitter when it is connected to the process. 

FACTORY SETTING AND CONFIGURATION

When  the  transmitter  is  used  with  the  factory  setting,  no  further  action  is  required 

and the transmitter is ready to be installed. Changes to the configuration are possible 

through the TBU software, provided free of charge on the Dwyer website. The factory 

setting for the TBU is for a Pt100 3-wire sensor with a range of 0 to 100°C with 0°C 

zero correction and an output of 4 to 20 mA.

After these connections, the user must run the TBU software. See Figure 2 for software 

screen.

The fields in the software screen pictured in Figure 2 mean:

1. 

General Information:

 This field shows information that identifies the transmitter. 

    This information could be sent to Dwyer Instruments when additional technical 

    assistance is requested. 

2. 

Sensor:

 Select the type of sensor to be used.

3. 

Measuring Range: 

Sets the measurement range of the transmitter.

  

Lower Range Limit:

 Equivalent temperature for a current of 4 mA.

  

Upper Range Limit:

 Equivalent temperature for a current of 20 mA.

  

Sensor Range:

 The values chosen cannot exceed the range of the sensor.

  

Minimum Range:

 Do not set a lower band (span) than the minimum range indicated.

4. 

Sensor Failure:

 Establishes the output behavior when the transmitter indicates a  

  failure.

  

Minimum: 

Output current goes to < 3.6 mA (down-scale), typically used for 

  refrigeration.

  

Maximum:

 Output current goes to > 22.0 mA (up-scale), typically used for heating.

5. 

Zero Offset: 

Offset allowing for small deviations presented in the transmitter output.

6. 

Send Configuration:

 Once set, the setup will be uploaded to the transmitter.

7. 

Read Configuration: 

Reads the current setup in the connected transmitter. 

SPECIFICATIONS

Input:

 Thermocouples J, K, R, S, T, N, E, and B; 2, 3, or 4 wire Pt100 RTD, 2 or 3 

wire Pt1000 RTD, 2 wire NTC thermistor, or 0 to 50 mV voltage.

Output:

 Linearized 4 to 20 mA, 2 wire or 20 to 4 mA loop powered.

Transmitter Type:

 2, 3, or 4 wire.

Temperature Limits:

 -40°F to 185°F (-40 to 85°C).

Power Requirements:

 10 to 35 VDC.

Accuracy:

 See chart below.

Temperature Drift:

 < ±0.16% / 25°C.

Response Time:

 1.6 s, typical.

Weight:

 1.4 oz (40 g).

Agency Approvals:

 CE.

1-23/32 [43.5]

13/16 [20.5]

Figure 1: USB cable connections

Figure 2: Software screenshot

TRANSMITTER

USB CABLE

PLUG A

TO PC USB PORT

MICRO B

POWERED 

CURRENTS 

LOOP

ACCURACY CHART

Input Type

Max. Temperature 

Range

Min. Temperature

Range

Accuracy (Typical)

Voltage

Thermocouple J

Thermocouple K

Thermocouple R/S

Thermocouple T

Thermocouple N

Thermocouple E

Thermocouple B

Pt100/Pt1000 RTDs

NTC Thermistor

0 to 50 mV

-148 to 1400°F 

(-100 to 760°C)

-238 to 2498°F 

(-150 to 1370°C)

-58 to 3200°F 

(-50 to 1760°C)

-256 to 752°F 

(-160 to 400°C)

-454 to 2372°F 

(-270 to 1300°C)

-130 to 1328°F 

(-90 to 720°C)

932 to 3308°F 

(500 to 1820°C)

-328 to 1202°F 

(-200 to 650°C)

-22 to 248°F 

(-30 to 120°C)

5 mV

212°F (100°C)

212°F (100°C)

752°F (400°C)

212°F (100°C)

212°F (100°C)

212°F (100°C)

752°F (400°C)

104°F (40°C)

104°F (40°C)

±0.1% FS

±0.1% FS

±0.1% FS

±0.1% FS

±0.1% FS

±0.1% FS

±0.1% FS

±0.1% FS

±0.13% FS

±0.3°C

The USB communication port (micro-USB) of the TBU-00 is not 

electrically insulated from the transmitters input. Connection while 

equipment is powered may result in equipment damage.

CAUTION

®