Dwyer Instruments Series CDTV Specifications-Installation And Operating Instructions Download Page 3

Menu Descriptions

ROC    

Define which output relay will be configured.

 

      CO

2

 default

      VOC

      Max CO

2

 / VOC

RON

 

   Relay set point

      Sets the CO

2

 or VOC concentration which the optional relay is energized.

 

      Low limit:   

0 PPM

      Factory setting:  

1000 PPM

      High limit:    

2000 PPM (CO

2

 or VOC), 5000 PPM (only CO

2

)

ROF

       Relay off set point

      Sets the CO

2

 or VOC concentration which the optional relay is de-energized. 

            Setting value lower than RON provides direct action for detecting  

 

      high concentrations of CO

2

. Setting value higher than RON provides indirect 

            action for detecting low concentrations of CO

2

 or on the LCD display will be 

            lit to indicate when the relay is energized.

      Low limit:   

0 PPM

      Factory setting: 

950 PPM

      High limit:   

2000 PPM (CO

2

 or VOC), 5000 PPM (only CO

2

)

DSP

       Display configuration

            Determines the LCD display configuration during normal operation. The 

      LCD display can indicate the CO

2

 concentration or VOC concentration.

      C 

  

 

CO

2

 concentration only

      V 

  

 

VOC only

UNI

    Units selection

            Temperature and barometric pressure values can be displayed in US 

            engineering units or SI engineering units. The factory default is to display 

      US engineering units.

COL

    CO

2

 low output range

      Sets the CO

2

 concentration for the lowest output (0 V, 1 V, 2 V, 0 mA, 2 mA, 

      4 mA).

      Low limit:   

0 PPM

      Factory setting: 

0 PPM

      High limit:   

2000 PPM (CO

2

 or VOC), 5000 PPM (only CO

2

)

COH

 

   CO

2

 high output range

      Sets the CO

2

 concentration for the highest output (10 mA or 5 V, 20 mA or 

            10 V). When COH is set above COL, the transmitter is direct acting and the 

            output will increase with an increase in CO

2

 level. When COH is below 

            COL, the transmitter is reverse acting and the output will increase with a 

      decrease in CO

2

 level.

      Low limit:   

0 PPM

      Factory setting: 

2000 PPM (CO

2

 or VOC), 5000 PPM (only CO

2

)

      High limit:   

2000 PPM (CO

2

 or VOC), 5000 PPM (only CO

2

)

VOL

       VOC low output range 

                Sets the VOC for the lowest output (0 V, 1 V, 2 V, 0 mA, 2 mA, 4 mA). To 

            configure output for 450 PPM equal 0V, set VOL to 450 PPM. Even if power 

            is lost the VOL setpoint will remain in memory.

                Low limit:   

0 PPM

      Factory setting: 

0 PPM

                High limit:   

2000 PPM CO2 equivalent 

VOH

       VOC high output range

            Sets the VOC level for the highest output (10 mA or 5 V, 20 mA or 10 V). 

            When VOH is set above VOL, the transmitter is direct acting and the output 

            will increase with an increase in VOC level. When VOH is below VOL, the  

            transmitter is reverse acting and the output will increase with a decrease in 

      VOC level.

      Low limit:   

450 PPM

      Factory setting: 

2000 PPM CO

2

 equivalent

      High limit:   

2000 PPM CO

2

 equivalent

BAR

    Barometric pressure

            Sets the typical barometric pressure for the location where the transmitter 

            is mounted. The factory setting is for standard pressure at sea level. 

            Adjusting the barometric pressure gives a more accurate measurement, 

            especially at higher elevations. Refer to the elevation charts in Figure 9 for 

            typical barometric pressures at a given elevation.

             Low limit:   

20.0 in Hg / 600 hPa

            Factory setting: 

29.9 in Hg / 1013 hPa

            High limit:   

32.0 in Hg / 1100 hPa

CAL

    Calibration

            Calibrates in carbon dioxide sensor to a known gas valve. Read calibration  

            instructions before using this feature. Hold for 5 seconds.

EDITING MENU PARAMETERS

Before any adjustment can be made to the transmitter, the Menu Lockout Dip Switch 

must be set to the ˝On˝ position (See Figure 3) 

 

 

 

ACCESSING MENU PAPRAMETERS

Step 1:  

To enter the menu structure, press Up button and Down button

 

simultaneously for 5 seconds (display will show RON parameter).

Step 2:  

Press Up button or Down button to cycle between menu items.

Step 3:  

Press Enter to edit the value for the displayed menu item (SET will    

 

appear on display).

Step 4:  

Press Up button or Down button to adjust the value of the menu  

item.

Step 5:  

Press Enter button to save the changes (SET will disappear).

Step 6:  

Repeat Steps 2 through 5 for each of the parameters.

Step 7:  

To exit the menu at any time, press and hold Up button and Down    

 

button simultaneously for 5 seconds or wait 10 seconds without  

 

 

pushing any buttons.

Figure 5: Side View of Wall Transmitter

Enter

Up

Remote Display Port

Down