Dwyer Instruments RHP-W series Specifications-Installation And Operating Instructions Download Page 2

1.  Push tab on bottom of cover and lift cover from back plate. (See Figure 1).
2.  Select the mounting location, away from diffusers, lights, or any external 

influences.

3.  Mount transmitter on a vertical surface to a standard electrical box using the two 

#6 M2C type screws provided.

4. Pull wires through sub base hole and make necessary connections.
5.  Reattach cover to base plate.

Wiring

Use maximum 18 AWG wire for wiring to terminals. Refer to figures 2 through 5 for
wiring information.

Current Output Models (RHP-XW1X)

Current output models must be powered with 10-35 VDC supply voltage. Wire the
RH current output as shown in Figure 2. If the unit has a 4-20 mA temperature out-
put, wire the temperature receiver between terminal 3 and the negative terminal of
the power supply. If the unit has a passive temperature sensor, wire to terminals 4
and 5. If the RH output is not required, wire the negative terminal of the power sup-
ply to terminal 1 of the transmitter. If the temperature output is not used, it may be
left disconnected.

Voltage Output Models (RHP-XW2X)

Wire as shown in Figure 3. Voltage outputs may be powered with 15-35 VDC or 15-
29 VAC. Note polarity when using DC power. If the unit has a voltage temperature
output, wire the temperature receiver between terminal 4 and negative terminal of
power supply. If the unit has a passive temperature sensor, wire to terminals 5 and
6. For units with RH and temperature voltage outputs, the RH or Temperature out-
put may be used by itself.

Models with Selectable Current or Voltage Outputs (RHP-XW44)

These models may be wired for current or voltage output. Note that both outputs
must be wired either for current or voltage. It is not possible to wire one output for
current, and the other for voltage. 

Prior to wiring, verify that the Current/Voltage select switch is set to current or volt-
age as desired. Refer to “Setting the Current/Voltage Select Switch”.

Current  Output  Selected:

Wire  as  shown  in  Figure  4.  Current  outputs  must  be

powered with 10-35 VDC. If the RH output is not required, wire the negative termi-
nal of the power supply to terminal 1 of the transmitter. All units come with 4-20 mA
RH  and  Temperature  outputs.  If  the  4-20  mA  temperature  output  is  not  used  it
maybe left disconnected. If the unit has a passive temperature sensor, wire to ter-
minals 7 and 8.

Voltage Output Selected:

Voltage outputs may be powered with 15-35 VDC or 15-

29 VAC. Note polarity when using DC power. Wire the RH voltage output as shown
in  Figure  5.  If  the  unit  has  a  voltage  temperature  output,  wire  the  temperature
receiver between terminal 6 and the negative terminal of the power supply. All units
come with RH and Temperature voltage outputs. If the temperature or RH voltage
output is not used it may be left disconnected. If the unit has a passive temperature
sensor, wire to terminals 7 and 8.

Setting the Current/Voltage Select Switch

Remove  the  cover  of  the  unit  as  shown  in  Figure  1.  The  Current/Voltage  select
switch is located on the back of the circuit board. Set the switch “IOUT” for current,
“VOUT” for voltage.

1   2   3   4   5   6   7   8

1 2 3 4 5 6 7 8

POWER
SUPPLY

POWER
SUPPLY

+     -

+

-

RH RECEIVER

RH RECEIVER

+

+

--

TEMP RECEIVER

TEMP RECEIVER

PASSIVE TEMP.
SENSOR

PASSIVE TEMP.
SENSOR

(IF PRESENT)

(IF PRESENT)

(IF PRESENT)

(IF PRESENT)

+

+

--

4-20MA

4-20MA

4-20MA

4-20MA

BOTTOM TAB

HINGE

TO REMOVE COVER
APPLY PRESSURE TO
BOTTOM TAB WHERE 
INDICATED AND THE 
TWO PARTS 
WILL BECOME 
UNHINGED AT TOP

REVERSE PROCESS 
TO APPLY COVER

MOUNTING
BACK PLATE

SELF-LATCHING
COVER

MOUNTING

SCREWS

Figure 1

 

Figure 2

Figure 3

 

Figure 4

 

Figure 5

Figure 6

www.

.com

[email protected]

1.800.561.8187

Reviews: