Voltage Input Calibration procedure
ENT
Input 1V from external.
Under calibration of 1V
ENT
ENT
Input 5V from external.
Under calibration of 5V
End of calibration
After calibration, the “End of
Calibration” message appears
under the end of calibration button.
• Analog input has already been calibrated on the factory setting
• When you interrupt the calibration in the middle, the calibration value will be
lost.
If you interrupt the calibration, start from the beginning again.
• Calibrated analog input is required for AI measurement.
CAUTION
Bulletin F-9-PUX2