background image

KP

1-3. Adjustment method and procedure same as dEAdzone.
4. Push <DOWN> at dEAdZONE mode and KP mode is displayed.
5. Push <ENTER> and *KP message appears on LCD.
6. Adjust KP values with <UP> or <DOWN>. Adjusted value is applied immediately
without additional operation. Users can easily check its adjustment by changing the
current input signal to the positioner. Optimum control value is found by adjusting
values during valve operation.
7. Push <ENTER> to save the value. +KP message appears on LCD.
8. Push <ESC>. 

9. Push <ESC> twice to return to RUN mode. 

PT

1-3. Adjustment method and procedure same as dEAdZONE.
4. Push <DOWN> 7 times at dEAdZONE mode and PT mode is displayed. 
5. Push <ENTER> at PT mode and *PT message appears  on LCD.
6. Adjust PT value with <UP> or <DOWN>. Adjusted value is applied immediately
without additional operation. Users can easily check its adjustment by changing the
current input signal to the positioner. Optimum control value is found by adjusting
the  values  during  valve  operation.  Push  <ENTER>  to  save  the  value  and  +PT
message appears on LCD.

7. Push <ESC>.
8. Push <ESC> twice to return to RUN mode. 

HAND CAL

When  auto  calibration  is  started,  Series  195  and  295  positioners  set  zero  points
and end points based on full stroke. 

Hand Calibration Types

PV_ZERO: Edit mode to change the zero point of valve.
PV_END: Edit mode to change the end point of a valve.
TR_ZERO: Edit mode to change the zero point of transmitter.
TR_END: Edit mode to change the end point of transmitter. 

Adjustment of valve zero point (1 to 5) and end point (6 to 10).

1.  Push  <ENTER>  at  RUN  mode  for  6  seconds  and  the  AUTO  CAL  mode  is
displayed. Push <DOWN> three times, and the HAND CAL mode is displayed. 
2. Push <ENTER> at HAND CAL mode and PV_ZERO mode is started.
3. Push <ENTER> at PV_ZERO mode and *PZ mode is started. At this mode it is
available to change valve zero point, and the valve stem moves automatically to the
current zero point. On LCD, the valve stroke is displayed as 0%. +PZ message that
indicates  edit  mode  of  zero  point  and  inner  value  showing  current  zero  point
position is also displayed. 
4. Adjust valve stem by pushing <UP> or <DOWN>. When valve stem has arrived
at the desirable zero point, save it with <ENTER>. +PZ message appears on LCD. 
5. Push <ESC> to return to PV-ZERO mode. (Push <ESC> twice to return to RUN
mode.)
6.  In  order  to  change  valve  end  point,  push  <DOWN>  at  PV_ZERO  mode  and
PV_END mode begins.
7. Push <ENTER> at PV_END mode and *PE mode is displayed. At this mode it is
available  to  change  valve  end  point,  and  the  valve  stem  moves  automatically  to
current  end  point.  On  LCD,  the  valve  stroke  is  displayed  100%.  *PE  message
indicating edit mode of end point and inner value of end point is also displayed. 
8. Adjust  valve  stem  with  using  <UP>  or  <DOWN>.  When  valve  stem  arrives  at
desirable end point, save it with <ENTER>. +PE message appears on LCD.
9. Push <ESC> to return to PV-END mode. 
10. Push <ESC> twice and RUN mode is displayed. 

Adjustment of zero point (1 to 4) and end point (5 to 9) of transmitter.

If  valve  zero  point  and  end  point  are  changed,  transmitter  is  also  changed
automatically. Usually there is no need for the transmitter zero point and end point
to be adjusted by users, but if transmitter output signal is unstable, transmitter zero
point and end point should be adjusted. The ammeter showing feedback signal is
necessary and the connection should be down as shown.

1. Push <DOWN> at PV-END mode and then TR_ZERO mode is displayed. 
2. Push <ENTER>. *R_ZERO mode is started and at this mode users can adjust
the zero point of the transmitter. Valve stem is moved to zero point automatically. 
3. Push <UP> or <DOWN>. The number on the LCD is changed and the measured
current value is changed accordingly on an ammeter equipped outside. Adjust it to
be 4 mA and push <ENTER> to save it. +R_ZERO message is displayed. 
4. Push <ESC>. TR_ZERO mode is displayed.
5. Push <DOWN> at TR_ZERO mode. Then TR_END mode is displayed. (Push
<ESC> twice to return to RUN mode.)
6. Push <ENTER>. *TR_END mode is started and at this mode users can adjust
the  end  point  of  the  transmitter.  The  valve  stem  is  moved  to  the  end  point
automatically.
7. Adjust measured current value to be 20 mA on ammeter with <UP> or <DOWN>
buttons. Push <ENTER> to save it. +R_END message appears.

8. Push <ESC>. TR-END mode is displayed. 

Feed back signal 

(12 ~ 30V)

4 ~ 20 mA

INPUT

Page 7

<ENTER>

<DOWN>

3 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

<DOWN>

7 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

3 times

COMPLETED

<ENTER>

6 seconds

<DOWN>

3 times

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ENTER>

<ESC>

<ENTER>

<DOWN>

<UP>/<DOWN>

then <ENTER>

COMPLETED

<ESC>

<DOWN>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

<DOWN>

<ENTER>

<UP>/<DOWN>

then <ENTER>

<ESC>

COMPLETED

Summary of Contents for Proximity 195 Series

Page 1: ...in low voltage 8 5 V leaving no limitation in controller Variable orifice is applied in case of a small actuator the hunting is controlled to the optimum condition during operation HART communication...

Page 2: ...bracket meets the above conditions Series 195 can be installed very easily 2 Assemble Series 195 and bracket with bolts Use standard bolts in bolt holes on the backside of the unit 3 After assembling...

Page 3: ...based on 79 20 mm of actuator stem height If the actuator stem height is higher such as 1 18 30 mm or 1 97 use the table below to check hole positions Ex If H is 30 mm A L should be locked in H 30 ho...

Page 4: ...id particles Result of being passed through 5 micron or finer filter 3 Does not contain oil or lubricating oil 4 Comply with ANSI ISA 57 3 1975 R1982 or ISA S7 3 1975 R1981 5 Not used beyond the range...

Page 5: ...ode After connecting the power to the positioner the following is displayed on the LDC in 6 seconds RUN on the bottom line means that the Smart Positioner adjusts valve stroke based on an outside sign...

Page 6: ...in Two lines appear on the LCD The upper line indicates valve stroke by percentage and the lower line indicates absolute value of inner resistance of the positioner MA means that Manual mode is in ope...

Page 7: ...rs on LCD 5 Push ESC to return to PV ZERO mode Push ESC twice to return to RUN mode 6 In order to change valve end point push DOWN at PV_ZERO mode and PV_END mode begins 7 Push ENTER at PV_END mode an...

Page 8: ...this mode users can adjust the first point of characteristic in 16 points The number on the LCD is the valve stroke percentage set to P0 4 Adjust the valve stroke percentage using UP or DOWN 5 Save it...

Page 9: ...solute resistance value Information Checked on VIEW Mode Error Code MT ERR L MT ERR H CHK AIR RNG ERR C D Code Description and Cause Positioner is improperly installed Positioner lever is not parallel...

Page 10: ...nc Printed in U S A 7 14 FR RV 443953 00 Rev 4 Usedtime UserSet ENT Enterbutton ManualMode Auto2 Autocal RUNMode ENT 5sec ESC ESC Auto1 ENT BIAS Auto3 ESC ESC V_O ESC ESC Hartver Character KP Endpoint...

Reviews: