background image

11

INM7700-6   

Jan 2010

7.2

Power supply check

Check that the power supply to an individual barrier circuit (or to an
MTL7798 power feed module or an MTL7799 dummy barrier
sourcing the power bus ) is functional and that the voltage across the
supply with respect to earth is correct. For example, in Figure 20 the
presence of 24V on terminal 1 and 12V on terminal 2 when the
switch in the hazardous area is closed confirms the serviceability of
almost the complete circuit.

7.3

Barrier resistance test

To test the resistance of a barrier on site, refer to figure 20 and carry
out the following procedure:

a) Unplug hazardous-area cables from terminals 3 and 4.

b) Unplug safe-area cables from terminals 1 and 2.

WARNING: Take care when handling safe-area cables;
the relay contacts in figure 20 for example could be
carrying mains voltage.

c) Measure the end-to-end resistance of the barrier by connecting a

digital multimeter (set to a suitable 

Ω

range) between terminals

1 and 3. The reading should typically be slightly less (eg 1–3%
lower) than the maximum end-to-end resistance listed in tables 4
to 10 for the appropriate barrier type or approximately 10–20%
higher than the figure specified in the safety description.

d) Check the functioning of the diode-return channel (,

7787P+, only) by selecting the diode test function on the
multimeter and connecting it between terminals 4 (+ve) and 2
(–ve). This measures the forward voltage drop of the Schottky
diodes in the chain: the reading should be less than 0.9V.
Repeat the test with the connections reversed (ie, terminals 4
(–ve) and 2 (+ve) for an expected reading of 

for the reverse

voltage drop.

e) Tests c) and d) confirm the continuity of both barrier channels. If

either channel is open-circuit it is most likely that the fuse has
blown. The safe-area circuit should be investigated in an attempt
to discover the cause of the fault. 

Note:

if the barrier is removed, make sure the safe-area and

hazardous-area cables disconnected during operations 

a)

and 

b)

are connected to an earth-rail, a dummy barrier or insulated
completely.

c) If it is not possible to disconnect wiring to the barrier for steps a)

and b), carry out the tests given in table 4.

8

EQUIPMENT AND BARRIER TESTS

8.1

Thermocouple and RTD tests

8.1.1

Thermocouple circuit testing

Thermocouple test and calibration equipment is rarely certified
intrinsically safe and therefore requires special authorisation before it
can be used for testing or calibrating thermocouple circuits in
hazardous areas. To overcome this problem, the thermocouple
circuits can be protected by using an MTL7760ac barrier as shown
in figure 21. This permits the thermocouple output to be measured
without needing special authorisation to use uncertified thermocouple
test equipment.

As it is seldom possible to measure accurately the temperatures of
thermocouples located in hazardous areas, a safe way of adjusting
calibration tables to compensate for plant temperatures is needed.
This can be done by disconnecting the compensating cables from the
thermocouple, shorting them together, and measuring the temperature
of the shorting point.

8.1.2

Resistance temperature detector (RTD) circuit

testing

Resistance temperature detector (RTD) circuits can be tested by
disconnecting the measuring leads from the RTD head in the
hazardous area and connecting them to a resistance box. Sometimes
it is more convenient to connect the resistance box in the safe area,
for instance at point ‘xx’ in figure 22. For the latter method, however,
the RTD must be shorted out or an allowance made for its
temperature. The effect of a negative temperature change can be
simulated by connecting the resistance box into the measurement lead
at point ‘yy’. The advantage of connecting the resistance box at the
RTD head is that any leakage can also be determined by connecting
the resistance box at point ‘yy’.

8.2

Barrier tests

8.2.1

General

MTL7700 Series barriers do not need to be subjected to routine
testing if they are in normal use. Generally, the inspection tests
described in section 6 are more than adequate. However, if the
performance of barriers is in any way suspect, then carry out the
detailed tests described in this section. Barriers which pass these tests
satisfactorily are highly unlikely to represent an unacceptable level of
risk or cause a circuit malfunction.

There are two types of test (as shown by tables 4 to 10); a simple test
using a digital multimeter to test barriers on site and a more
comprehensive bench test using a constant current source to establish
the breakdown characteristics.

Although certification requirements concentrate on pulse-current tests,
in many ways the leakage current tests described in this section are
a more satisfactory method of testing suspect diodes. If a complete
functional check of a barrier is needed, then the multimeter and
constant current tests described in sections 8.2.2 and 8.2.3 should be
made although, for most purposes, the multimeter tests should suffice.

1

2

3
4

370

Ω

+24Vdc

12V

0V

400

Ω

12V

relay

Plant earth via DIN-rail

30mA

Figure 20

:  Switch-status transfer circuit using an MTL7787 barrier

1

2

3
4

1

2

3
4

Compensating cables

Safe-area

equipment

Calibration

equipment

MTL7760ac

Figure 21

:  Calibrating a thermocouple barrier circuit

Summary of Contents for MTL7700 Series

Page 1: ...Instruction Manual INM7700 MTL7700 Series Shunt diode safety barriers ...

Page 2: ...ii INM7700 6 Jan 2010 ...

Page 3: ...ons 7 5 3 Connections to plant earth 7 5 4 Connections to dummy barriers 9 6 MAINTENANCE 9 6 1 General 9 6 2 Routine inspection 9 7 FAULT FINDING 10 7 1 Introduction 10 7 2 Power supply check 11 7 3 Barrier resistance test 11 8 EQUIPMENT AND BARRIER TESTS 11 8 1 Thermocouple and RTD tests 11 8 2 Barrier tests 11 8 3 Tests for Active Barriers 12 8 4 Test tables for passive barriers 14 APPENDIX A TY...

Page 4: ...INM7700 6 Jan 2010 iv ...

Page 5: ...ith the product these publications are available either from the company website www mtl inst com or on request from your local MTL office 2 DESCRIPTION 2 1 Introduction MTL7700 Series fourth generation intrinsically safe shunt diode safety barriers are innovative successors to the MTL700 Series MTL7700 Series barriers are 1 2 or 3 channel devices that use intrinsically safe explosion protection t...

Page 6: ...for mounting over a column of barriers for marking barrier locations Supplied with labels in 1m lengths for cutting to size TGL7700 Spare labels for use with TAG57 tagging strips 0 5m strips supplied in sets of 10 IMB57 Tagging strip supports Two needed for each tagging strip It can also be used as centre support by breaking off the top end tab Power accessories figure 3 BPL7700 Power link for fee...

Page 7: ...ing accessories As a guide on a given length of DIN rail allow space length for a Barrier packing pitch 12 6mm b ETL7000 earth terminals 10mm each minimum of two c IMB57 tagging strip support 16 0mm minimum of if specified two d ISP7000 insulating spacer 14 7mm minimum of if specified two e ERB57S or O earth rail 8 mm minimum of two mounting bracket if specified See Note in section 4 3 2 Make sure...

Page 8: ...f applicable and complies with the recommendations contained in the relevant sections of IEC 60079 14 for the gas group temperature classification and area classification required 2 4 1 6 2 Make sure the barriers are of the correct type and polarity as specified in the safety documentation 3 4 1 Make sure all barriers are mounted the right way round and are properly attached so that the essential ...

Page 9: ...inals are recommended one at either end of a column of barriers to provide redundancy and to simplify earth testing procedures WARNING Apart from rare occasions when the mounting surface carries the IS earth the ONLY method of providing the IS earth connection from any one column of MTL7700 Series barriers is from ETL7000 earth terminals Never make the plant IS earth connection to the earth screen...

Page 10: ...blies IMB57 The tagging strip assembly figure 12 identifies the location of individual barriers ensuring that they are replaced correctly after removal for maintenance or testing Once installed the tagging strip pivots upwards to provide access to and allow removal of individual barriers Each assembly uses two tagging strip supports IMB57 a tagging strip TAG57 and tag labels TGL7700 The assembly i...

Page 11: ...A for specific connections for individual barriers and applications 5 2 3 Bussed Power applications and connections When a number of barriers use a common power supply the optional power link BPL7700 can be used Typical applications include hazardous area switches solenoids and 4 20mA transmitters and the barriers it can be used with are the MTL7706 MTL7707 MTL7787 MTL7787P and MTL774x See figure ...

Page 12: ... see section 4 3 4 an earth conductor normally copper wire with a cross sectional area of at least 4mm2 12AWG must be connected between ETM7 earth terminals located at each end of the rail and the spare terminals on the ETL7000 terminals at each end of the column of barriers See figure 17 5 3 4 Hazardous area equipment isolation Hazardous area equipment and interconnections should be isolated from...

Page 13: ...ly to the neutral star point This reduces interference problems but is not essential for safety reasons f In general the use of barriers in all measurement leads reduces the possibility of earth circulating currents causing measurement problems g Resistance from the neutral star point to terrestrial earth via the buried earth mat or rods is determined by other regulations and is not modified or de...

Page 14: ...e and their operation is easy to check However when fault finding is necessary it must only be undertaken after checking with plant personnel responsible for safety that it is safe to proceed The fault finding procedures described in this section call for the use of a digital multimeter this being the most common type used However other types can be used provided their characteristics when measuri...

Page 15: ...mocouple circuits can be protected by using an MTL7760ac barrier as shown in figure 21 This permits the thermocouple output to be measured without needing special authorisation to use uncertified thermocouple test equipment As it is seldom possible to measure accurately the temperatures of thermocouples located in hazardous areas a safe way of adjusting calibration tables to compensate for plant t...

Page 16: ...ers 8 3 1 Tests for the MTL7706 Comprehensive testing requires specialised equipment beyond the scope of on site tests However an effective test which will confirm that the unit is operating correctly is shown in figure 24 Ammeter 1 measures the transmitter simulator current of between 4 and 20mA flowing from terminal 4 and the safe area load current flowing to terminal 4 simultaneously Since thes...

Page 17: ...th an ohmeter check the status of the output contacts according to Table 3 3 4 1 2 MTL7742 5 6 7 8 Bussed Power 24V Vs Vs 2KΩ Figure 27 Test circuit for MTL7742 3 4 1 2 MTL7745 5 6 620W 10kW 24V Bussed Power Line Fault Output Vs Vs Figure 30 Test circuit for MTL7745 Table 3 Test conditions for MTL7745 3 4 1 2 MTL7743 5 6 7 8 Bussed Power 24V Vs Vs Channel 1 Channel 2 Channel 1 Channel 2 Figure 28 ...

Page 18: ...ode and 0 3V for each Schottky diode the expected reading across the diode chain can be determined BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Test Test Voltage Voltage No Ω Ω ve ve 10μ μA 20mA V Ω Ω mA Min Max Min Max Min Max 7758 7 5 10 750 14 17 Vfz x 1 6 6 9 6 6 7 7758 7 5 10 750 14 17 Vfz x 1 6 6 9 6 6 7...

Page 19: ...157 84 92 9 6 10 9 10 4 11 2 Table 7 Dual channel ac barriers BARRIER DATA MULTIMETER TESTS CONSTANT CURRENT TESTS MTL Safety End to end Diode Diode Terminal Terminal model Description Resistance Test Test Voltage Voltage No Ω Ω ve ve 10μ μA 20mA V Ω Ω mA Min Max Min Max Min Max 7760ac 10 50 200 62 75 6 9 5 6 9 9 8 7765ac 15 100 150 112 124 12 14 1 12 7 14 4 7778ac 28 600 47 614 651 24 0 24 4 25 4...

Page 20: ...Min Max Min Max 7787 28 300 93 311 333 Vfz x 2 26 6 27 4 26 7 27 6 7787 ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7787P 28 237 119 241 253 Vfz x 3 26 4 27 4 26 5 27 6 7787P ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 7789 38 300 93 614 651 Vfz x 2 26 6 27 4 26 7 27 6 7789 ch2 28 0 9V 26 Vfz x 2 26 6 27 4 26 7 27 6 Table 10 Diode return barriers Note Vfz is the voltage dropped by a forward biased z...

Page 21: ...c Receiver 7 5 3 4 1 2 MTL7755ac Receiver Figure A6 Low level analogue inputs RTD s Figure A2 2 wire transmitters with 250Ω conditioning Hazardous Area Safe Area 3 4 1 2 MTL7760ac MTL7765ac MTL7778ac Recorder Controller Data logger Computer Compensating cable Figure A3 Thermocouple mV input Hazardous Area Safe Area 3 4 1 2 MTL7743 MTL7744 7 8 5 6 Logic signal Logic signal Power Figure A7 2 channel...

Page 22: ... bridges Hazardous Area Safe Area 3 4 1 2 MTL7745 5 6 620Ω 10kΩ 22 9 30V LFD COM CH 1 Power Bus Figure A10 Single channel switch proximity input with Line Fault Detect Hazardous Area Safe Area 3 4 1 2 MTL7789 7 8 5 6 Power 26V Power 26V Power Bus Figure A11 Low power digital outputs Hazardous Area Safe Area 3 4 1 2 MTL7741 5 6 7 8 NO COM Power Bus 22 9V 30V NC Figure A12 Single channel switch prox...

Page 23: ......

Page 24: ...anallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail sales mtlindia com MTL Italia srl Via Cantù 11 I 20092 Cinisello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it MTL Instruments KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel 81 0 3 6430 3128 Fax 81 0 3 6430 3129 E mail sales mtlkk co jp MTL Instruments...

Reviews: