Dwyer Instruments LOVE CONTROLS DIVISION Iso Verter II 4380 Installation Instructions Manual Download Page 2

Iso Verter

®

II 

Model 4380

Installation Instructions

Bulletin 949-0513

Getting Started

Mount the socket and wire per instructions on below (Figure 2).

Refer to the exploded diagram in Figure 1. Carefully remove the
four screws from the bottom of the plug end. Slide the cover off.

Program for desired input following instructions on page 2.

Program for desired output following instructions on page 3.

Refer to the exploded diagram in Figure 1. Carefully replace the
cover and re-install the four screws to secure the cover to the base.
Screws should be tightened to a snug fit (6 in-lb torque max.).

Calibrate the unit using the procedure on page 4.

WARNING: 

Do not attempt to operate or calibrate this

device  with  the  cover  removed.  Potentially  lethal
voltage is present on some of the internal components.
Make  sure  that  the  cover  is  firmly  in  place  before
plugging into the socket.

Wiring

Wire the mounting socket as shown in the drawing shown in Figure
2.

For DIRECT ACTING inputs wire the positive lead to terminal five
and the negative lead to terminal six (as shown).

For  REVERSE ACTING  inputs  wire  the  positive  input  lead  to
terminal six and the negative lead to terminal five.

              LOVE CONTROLS DIVISION              

Phone: 219/879-8000

              DWYER INSTRUMENTS, INC.                       

www.love-controls.com

                    P.O. BOX 373 • MICHIGAN CITY,                              

Fax: 219/872-9057

                    INDIANA 46360, U.S.A.                                             

e-mail: [email protected]

Figure 1:

Remove cover to access

program switches

Figure 2:

Wiring socket

Summary of Contents for LOVE CONTROLS DIVISION Iso Verter II 4380

Page 1: ...CURE ASSET SOLUTIONS SERVICE CENTER REPAIRS Experienced engineers and technicians on staff at our full service in house repair center WE BUY USED E Sell your exce We also offer www artisan REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR Visit us on the information o specifications Contact us 888 88 SOURCE sales artisantg...

Page 2: ... using the procedure on page 4 WARNING Do not attempt to operate or calibrate this device with the cover removed Potentially lethal voltage is present on some of the internal components Make sure that the cover is firmly in place before plugging into the socket Wiring Wire the mounting socket as shown in the drawing shown in Figure 2 For DIRECT ACTING inputs wire the positive lead to terminal five...

Page 3: ...ON and turn switch five OFF 5 For ZERO SUPPRESSION eg 4 to 20 mA turn switch four OFF and turn switch five ON 6 For DIRECT ACTING INPUT turn switch six OFF 7 For REVERSE ACTING INPUT turn switch six ON and reverse input wiring RANGE SELECT SWITCH BANK Turn ON the switch for the scale desired All other switches should be OFF If BI POLAR INPUT is selected the scale will be MINUS SELECTION to PLUS SE...

Page 4: ... mA turn switch six OFF and turn switch seven ON If BIPOLAR or REVERSE ACTION is selected do not use the ZERO SUPPRESSION switch Use the ZERO adjustment to suppress the output 7 Switch eight is always OFF It is not connected to any circuitry If switch eight is turned ON there is no effect on the operation of the device RANGE SELECT SWITCH BANK Turn ON the switch for the scale desired All other swi...

Page 5: ... low end output 4mA for example 3 Apply the appropriate input for the high end of the scale 4 Adjust the SPAN screw for the desired high end output 20mA for example 5 Repeat as necessary Note Instrument is factory calibrated for 4 to 20 mA Uni Polar Direct Acting Input and 4 to 20 mA Uni Polar Output Any change from this default condition may require field re calibration to ensure accuracy of zero...

Page 6: ...CURE ASSET SOLUTIONS SERVICE CENTER REPAIRS Experienced engineers and technicians on staff at our full service in house repair center WE BUY USED E Sell your exce We also offer www artisan REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR Visit us on the information o specifications Contact us 888 88 SOURCE sales artisantg...

Reviews: