Holding Registers

Device Name:

 A string, up to 40 characters long, that will be displayed on the LCD (if 

present). When reading or writing, all 20 registers must be requested. Strings less than 

40 characters shall be 0 padded.

Velocity Unit:

 Selects the unit of velocity for the value in the velocity register. See 

Table 1.

Flow Unit: 

Selects the unit of flow for the value in the Flow register. See Table 2.

Volume Unit: 

Selects the unit of volume for the value in the Total Flow register. See 

Table 3.

Reset Total Flow: 

When a value of 1 is written to this register, the value in the Total 

Flow register is reset to 0. Writing a value of 0 has no effect. This register will always 

return a 0 when read.

Reset Device: 

When a value of 1 is written to this register, the device will perform a 

warm reset after 5 seconds. Writing a value of 0 has no effect. This register will always 

return 0 when read.

* Default unit

Multi-Address Support

Multi-Address support allows a register to be read or written to using different byte 

orientations specified by the address range.  For example, input register 0003 can 

also be read at 2003, 4003 and 6003 with different byte orientations as listed in Table 

7.  Registers that do not have multi-address support are only available in Big-Endian 

byte orientation (Modbus

®

 standard).

Register

Description

Data Type

Range

0001 – 0020

0021

0022

0023

0024

0025

Device Name

Velocity Unit

Flow Unit

Volume Unit

Reset Total Flow

Reset Device

String

Unsigned 16bit integer

Unsigned 16bit integer

Unsigned 16bit integer

Unsigned 16bit integer

Unsigned 16bit integer

0 – 7

0 – 15

0 – 3

0 or 1

0 or 1

Float/32bit Values

16Bit Values

Register 1

Register 2

Register 3

Byte Order

Address Range MSB

LSB

MSB

LSB

Big-Endian

Byte Swap

Word Swap

Little-Endian

1-2000

2001-4000

4001-6000

6001-8000

A

B

C

D

B

A

D

C

C

D

A

B

D

C

B

A

A

B

A

B

B

A

B

A

TABLE 1: VELOCITY UNIT VALUES

Value Unit

*0

1

2

3

4

5

6

7

Feet-per-second (ft/s)

Feet-per-minute (ft/min)

Feet-per-hour (ft/hr)

Feet-per-day (ft/day)

Meters-per-second (m/s)

Meters-per-minute (m/min)

Meters-per-hour (m/hr)

Meters-per-day (m/day)

TABLE 2: FLOW UNIT VALUES

Value Unit

*0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Cubic-feet-per-second (ft

3

/s)

Cubic-feet-per-minute (ft

3

/min)

Cubic-feet-per-hour (ft

3

/hr)

Cubic-feet-per-day (ft

3

/day)

Gallons-per-second (gal/s)

Gallons-per-minute (gal/min)

Gallons-per-hour (gal/hr)

Gallons-per-day (gal/day)

Liters-per-second (L/s)

Liters-per-minute (L/min)

Liters-per-hour (L/hr)

Liters-per-day (L/day)

Cubic-meters-per-second (m

3

/s)

Cubic-meters-per-minute (m

3

/min)

Cubic-meters-per-minute (m

3

/min)

Cubic-meters-per-day (m3/day)

TABLE 3: VOLUME UNIT VALUES

Value Unit

0

*1

2

3

Cubic-feet (ft

3

)

Gallons (gal)

Liters (L)

Cubic-meters (m3)

Summary of Contents for IEF Series

Page 1: ...U that enables or disables a network termination resistor as defined below When the network jumper is placed in the ON position there is a 120 ohm termination resistor in place When the network jumper is placed in the OFF position there is no termination resistor in place Default OFF NETWORK TERMINATION JUMPER DWYER INSTRUMENTS INC P O BOX 373 MICHIGAN CITY INDIANA 46360 U S A Phone 219 879 8000 F...

Page 2: ...nding Database Revision Property List Serial Number 607xxx Series IEF 607xxx DEVICE 8 Operational 0 Dwyer Instruments Inc 607 IEF HN 10 COM x x x x x 1 14 See BACnet Services below See Table Above See Table Above 480 NO_SEGMENTATION 3 6000 3 127 1 Empty 1 xxxxxxxx BACnetObjectIdentifier CharacterString 40 BACnetObjectType BACnetDeviceStatus CharacterString Unsigned CharacterString CharacterString ...

Page 3: ...etPropertyIdentifier Read Read Read Read Read Read Read Read Write Read Write Read Write Read Property Default Value Property Data Type Access Object Identifier Object Name ObjectType Present Value Status Flags Event State Reliability Out Of Service Units COV Increment Property List AV2 Total Flow ANALOG_INPUT 0 Current reading 0 NORMAL 0 NO_FAULT_DETECTED 0 FALSE 0 Cubic feet 79 1 0 BACnetObjectI...

Page 4: ...ate Reliability Out Of Service Property List BV1 Reverse Flow BINARY_VALUE 5 Inactive 0 0 NORMAL 0 NO_FAULT_DETECTED 0 FALSE 0 BACnetObjectIdentifier CharacterString BACnetObjectType BACnetBinaryPV BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetARRAY N of BACnetPropertyIdentifier Read Read Read Read Read Read Read Read Write Read Property Default Value Property Data Type Access...

Page 5: ... If the string is shorter than the allotted size the remaining bytes will be zero padded Property Default Value Property Data Type Access Object Identifier Object Name ObjectType Present Value Status Flags Event State Reliability Out Of Service Property List BSV1 Status Flags BITSTRING_VALUE 39 FFFFFFFF FFFF 0 NORMAL 0 NO_FAULT_DETECTED 0 FALSE 0 BACnetObjectIdentifier CharacterString BACnetObject...

Page 6: ...e only available in Big Endian byte orientation Modbus standard Register Description Data Type Range 0001 0020 0021 0022 0023 0024 0025 Device Name Velocity Unit Flow Unit Volume Unit Reset Total Flow Reset Device String Unsigned 16bit integer Unsigned 16bit integer Unsigned 16bit integer Unsigned 16bit integer Unsigned 16bit integer 0 7 0 15 0 3 0 or 1 0 or 1 Float 32bit Values 16Bit Values Regis...

Page 7: ..._______________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________...

Page 8: ...___ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________...

Reviews: