OPERATION
Selecting Engineering Units
Four sets of jumper pins are located in the back of the meter,
between the meter and the adder board. Move the jumper to fit
over the appropriate pins which correspond to the desired
engineering units. See Figure 1.
Selecting Decimal Point Position
Four decimal point positions are available on the digital panel
meter. Move the jumper to correspond to the desired decimal
point location. See Figure 2.
Setting J1, J2, J3 (See Figure 3 & 4):
If:
The minimum display is
≤
0 or
Minimum display is > 0 and the (maximum display/minimum
display) > 5;
The J1, J2 & J3 should be all set to the top jumper (see Figure 3).
If:
The minimum display is > 0 and the (maximum display/minimum
display)
<
5;
The J1, J2 & J3 should be all set to the bottom jumper (see Figure
4).
FIGURE 2
FIGURE 4
A
B
J3 J2 J1
FIGURE 3
MAINTENANCE
Upon final installation of the Series DPMW LCD Digital Process
Meters, no routine maintenance is required. A periodic check of
the system calibration is recommended. The Series DPMW is not
field serviceable and should be returned if repair is needed (field
repair should not be attempted and may void warranty). Be sure to
include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return
good authorization number before shipping.