Dwyer Instruments DM-2000 Series Installation And Operating Instructions Download Page 2

©Copyright 2017 Dwyer Instruments, Inc.

Printed in U.S.A. 3/17

FR# 443402-00 Rev. 4

ELECTRICAL CONNECTIONS

CAUTION: Do not exceed specified supply voltage ratings.  Permanent damage not 

covered by warranty will result.  This unit is not designed for 120 or 240 volts AC line 

operation.

Electrical connections are made to the terminal block located in back of the transmitter. 

Terminals are and - (see Fig. B below).

Wire Length

The maximum length of wire connecting transmitter and receiver is a function of wire 

size  and  receiver  resistance.  Wiring  should  not  contribute  more  than  10%  of  the 

receiver resistance to total loop resistance. For extremely long runs (over 1000 feet), 

choose receivers with higher resistance to minimize size and cost of connecting leads. 

Where wiring length is under 100 feet, hook-up wire as small as 22 AWG can be used.

2-Wire Operation

An external power supply delivering 10-35 VDC with minimum current capability of 

40 mA DC (per transmitter) must be used to power the control loop. See Fig. C for 

connection of the power supply, transmitter and receiver. The range of appropriate 

receiver load resistance (RL) for the DC power supply voltage available is expressed 

by  the  formula  and  graph  in  Fig.  D.  Shielded  two  wire  cable  is  recommended  for 

control loop wiring. If grounding is required, use the negative side of the control loop 

after the receiver.

USER CALIBRATION

The transmitter may be user calibrated with two buttons on the front. The standard 

models have buttons labeled “ZERO” and “SPAN”. LCD models have buttons labeled 

“ZERO”  and  “UNITS”.  The  “UNITS”  button  on  the  LCD  models  has  2  functions.  If 

pushed for less than 2 seconds and released the pressure units that are displayed on 

the LCD will change when the button is released. If pushed and held for 4 - 5 seconds 

the “UNITS” button serves the same function as the “SPAN” button on the standard 

models.

To calibrate the transmitter you will need three pieces of equipment. You will need 

a calibrated pressure source capable of generating a stable pressure value for 

the maximum range of the unit under test, an instrument capable of validating the 

calibration pressure, and an ampmeter, capable of measuring mA, to measure the 

current output from the unit under test. The transmitter is calibrated using the following 

procedure.

Preparation

  –  Connect  the  ampmeter  and  power  supply,  being  careful  to  observe 

polarities. The transmitter must be calibrated in a vertical position.

Performing ZERO Calibration, SPAN Calibration or Restore Factory 

Calibration Coefficients:

  1.  Press both the ZERO and UNITS/SPAN buttons simultaneously for 6 or more 

      seconds. Release both buttons. The units indicator on the LCD should blink on 

      and off. This indicates the gage is ready for calibration or restoration of 

      coefficients. The units indicator blinks for approximately 10 minutes, then stops 

      blinking.

  2.  a) ZERO calibrate the gage by applying no pressure to the gage and 

      then pressing the ZERO button for 3 seconds.

      b) SPAN calibrate the gage by applying full-scale pressure to the gage and 

      then pressing the UNITS/SPAN button for 3 seconds.

      c.) Restore the gage’s factory calibration coefficient by pressing both the ZERO 

      and UNITS/SPAN buttons simultaneously for 3 seconds.

MAINTENANCE

Upon  final  installation  of  the  Series  DM2000  Differential  Pressure  Transmitter  and 

the companion receiver no routine maintenance is required. The Series DM2000 

Transmitter  is  not  field  serviceable  and  should  be  returned,  freight  prepaid,  to  the 

factory if repair is required. Please enclose a description of the problems encountered 

plus any available application information.

Figure

 B

Figure

 C

Figure D

2-Wire Connections

Power Supply Voltage – VDC (2-wire)

1500

1400

1300

1200

1100

1000

900

800

700

600

500

400

300

200

100

50

To

tal Receiver Resistance ()

Maximum Value (1250 )

R   Max. =

0           5       10    13   15        20         25         30        35         40  

L

Vps–10.0

20mA DC

Operating

Region

RECEIVER

SERIES 

DM-2000

PRESSURE 

TRANSMITTER

1
2

POWER

SUPPLY

10-35 VDC

mA

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219/879-8000
Fax: 219/872-9057

dwyer-inst.com
e-mail: [email protected]

Reviews: