![Dwyer Instruments DHII Digihelic II Series Specifications-Installation And Operating Instructions Download Page 3](http://html.mh-extra.com/html/dwyer-instruments/dhii-digihelic-ii-series/dhii-digihelic-ii-series_specifications-installation-and-operating-instructions_2544552003.webp)
2
SPECIFICATIONS
Service:
Air and non-combustible, compatible gases.
Wetted Materials:
Consult factory.
Housing Material:
Aluminum, glass.
Accuracy:
±0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up).
Stability:
< ±1% per year.
Pressure Limits:
Ranges ≤ 2.5 in. w.c. = 2 psi
5˝: 5 psi; 10˝: 5 psi; 25˝: 5 psi; 50˝: 5 psi; 100˝: 9 psi.
Temperature Limits:
32 to 140°F (0 to 60°C).
Compensated Temperature Limits:
32 to 140°F (0 to 60°C).
Thermal Effects:
0.020%/°F (0.036/°C) from 77°F (25°C).
Power Requirements:
High Voltage Power = 100 to 240 VAC, 50 to 400 Hz or 132 to 240 VDC;
Low Voltage Power = 24 VDC ±20%.
Power Consumption:
Low Voltage Power = 24 VDC - 130 mA max.
High Voltage Power = 100 to 240 VAC, 132 to 240 VDC - 7VA max.
Output Signal:
4-20 mA DC into 900 ohms max.
Zero & Span Adjustments:
Accessible via menus.
Response Time:
250 ms (dampening set to 1).
Display:
4 digit backlit LCD 0.6˝ height. LED indicators for set point and alarm status.
Electrical Connections:
Euro type removeable terminal blocks with watertight conduit fittings for
1/2˝ watertight conduit.
Process Connections:
1/8 female NPT.
Enclosure Rating:
Designed to meet NEMA 4 (IP66).
Mounting Orientation:
Mount unit in vertical plane.
Size:
4.73˝ x 4.73˝ x 3.43˝ (120 mm x 120 mm x 87.1 mm).
Weight:
2 lb 10 oz (1.19 kg).
Serial Communications:
Modbus
®
RTU, RS485, 9600 Baud.
Agency Approvals:
UL & CE.
SWITCH SPECIFICATIONS
Switch Type:
2 SPDT relays.
Electrical Rating:
8 Amps at 240 VAC resistive.
Set Point Adjustment:
Adjustable via keypad on face.
Modbus
®
is a registered trademark of Schnieder Automation.
www.
.com
1.800.561.8187