Dwyer Instruments AVUL Series Installation And Operating Instructions Manual Download Page 6

Modbus

®

 Communication Protocol DIP Switch Settings

Use the middle DIP Switch SW2 to configure the Modbus

®

 Communication Protocol 

address of the device. The LCD will show the address when the transmitter is powered 

on. Valid addresses range from 1 to 247. By default, the device is shipped with the 

address 127 (as shown in Figure 10). A valid and unused address should be set before 

connecting to an existing network. However, the address can be changed while the 

device is operational. If the address is changed, the device will stop responding to the 

currently configured address immediately. The device waits 15 seconds after the last 

switch change before applying the new address. The device will not function properly 

if an invalid address is set. The red LED will periodically blink once indicating an invalid 

address. The LCD will display 

A Err 

when the transmitter is powered on if the address 

is invalid. See Appendix V for setting the Modbus

®

 Communication Protocol address 

of the device. Use the right DIP Switch SW3 to configure other hardware and software 

options.

Figure 7: Common power supply

Figure 8: Local power supply

SW3

SW2

KEY:

128 - MSB

64

32

16

8

4

2

1 - LSB

SW1

ZERO

SPAN

SW2 SW3

TERMINATING

RESISTOR

BIAS

RESISTOR

AUTO SERIAL

CONFIGURATION

Figure 9

Switch

On

Off

1-2 – Display Units Selection

3-4 – Reserved

5 - Intelligent Serial 

Configuration

6 – D1[+] Network resistor

7 – D0[-] Network resistor

8 – Terminating resistor

Enabled

511Ω Pull-up to 5 V

511Ω Pull-down to GND

120Ω between D0[-] and 

D1[+]

Disabled

Pull-up not connected

Pull-down not 

connected

Open

Table 5: DIP switch SW3 functions

APPENDIX IV: Programming Via Modbus

®

 Communication Protocol

Intelligent Serial Configuration

Intelligent  serial  configuration  enables  the  device  to  determine  the  baud  rate,  data 

size, party, stop bits and even the Modbus

®

 Communication Protocol mode directly 

from the serial traffic. This allows the Series AVUL to be quickly and easily deployed 

after a valid Modbus

®

 Communication Protocol address is chosen. 

To activate intelligent serial configuration, set a valid Modbus

®

 Communication Protocol 

address using the left DIP switch SW2, connect the serial bus and power wires, and 

then apply power. The device will power up and begin examining the serial bus for 

communication.  The  Red  LED  will  repeatedly  flash  twice,  indicating  that  intelligent 

serial configuration is in progress. 

If  the  device  is  setup  offline  or  away  from  the  main  network,  it  is  necessary  to 

generate  Modbus

®

  Communication  Protocol  traffic  in  order  to  configure  the  serial 

communication.  Attempting  to  read  input  registers  is  a  good  method  to  generate 

Modbus

®

  Communication  Protocol  traffic.  Note  that  while  serial  configuration  is  in 

progress, the device may not respond to requests. The device may require multiple 

read requests to complete the serial configuration process. 

The intelligent serial configuration process will complete once a message addressed 

to  the  device  is  received  and  processed  successfully.  The  serial  configuration 

parameters are then saved to non-volatile storage and loaded by default each time the 

device starts. If the serial configuration of the bus changes, a power cycle of the device 

is required to restart the Intelligent Serial Configuration process.

The String data type is read as a stream of ASCII characters, with the first character 

sent in the MSB of the first register, and the second character sent in the LSB of the 

first register and so on. If the string is shorter than the allotted size, the remaining bytes 

will be zero padded.

1 - The serial configuration, no parity with one stop bit is not officially supported by the 

Modbus

®

 Communication Protocol standard. However, if this configuration is desired, 

set switch 5 on DIP switch SW3 to off. The device will configure itself in Modbus

®

 RTU 

Communication Protocol mode with a data size of 8, no parity, and 1 stop bit. The baud 

rate will still be determined automatically.

Modbus

®

 Mode Supported Baud Rates Data Size Parity Stop Bits

RTU

9600

19200

38400

57600

76800

115200

8

Even

Odd

None

1

1

None 2

ASCII

7

Even

Odd

1

None 2

Table 6: Supported Modbus

®

 communication protocol configurations

Function Name

Function Code

Read Coils

Read Holding Registers

Read Input Registers

Write Single Coil

Write Single Register

Write Multiple Registers

01

03

04

05

06

16

Table 7: Supported Modbus

®

communication protocol functions

Register Description Data Type Value

Range

Multi-

Address 

Supported

0001 – 

0002

0003 – 

0004

Register

Velocity 

Flow Area 

(ft

2

)

Velocity 

Flow Area 

(m

2

)

Description

Float

Float

Data Type

0.01…999.99

0.00093…92.9

Value

0.01…999.99

0.00093…92.9

Range

Yes

Yes

Multi-

Address 

Supported

Table 8: Holding registers

D1[+]

D0[-]

COM

D1[+]

D0[-]

COM

POWER

SUPPLY

+ -

PWR GND IOUT VOUT D1[+] D0[-] COM

PWR GND IOUT VOUT

TO NEXT

DEVICE

D1[+]

D0[-]

PWR

COM

D1[+]

D0[-]

PWR

COM

TO PREVIOUS

DEVICE

D1[+] D0[-] COM

Summary of Contents for AVUL Series

Page 1: ...10 VDC Response Time 90 10 s typical Zero and Span Adjustments Digital push buttons Output Load Resistance Current output 0 to 1100 max Voltage output Minimum load resistance 1 k Current Consumption 6...

Page 2: ...current loop load resistance RMAX is defined by the following the equation RMAX where VPS is the power supply voltage For a 24 VDC nominal power supply this evaluates to RMAX 1100 ohms Shielded two w...

Page 3: ...ws the values The units will be displayed on the optional LCD display if connected The default operating mode is velocity but changes can be made such as flow mode via the menu system while an optiona...

Page 4: ...d to reduce vibration or disturbances of the user related to the button presses The security level that is set in the Programming Menu section of the manual will determine which calibrations if any ma...

Page 5: ...ms and no will discard all the changes made to all menu items If the display is set to yes pressing and holding the span will save the menu items and return the display to the home position FACTORY DE...

Page 6: ...cating that intelligent serial configuration is in progress If the device is setup offline or away from the main network it is necessary to generate Modbus Communication Protocol traffic in order to c...

Page 7: ...byte orientations as listed in Table 10 Registers that do not have multi address support are only available in Big Endian byte orientation Modbus Communication Protocol standard APPENDIX V Setting Mod...

Page 8: ...SPAN ZERO SEQUENCE TO NEXT DIGIT ACTIVE DIGIT WILL BLINK SPAN BLINKING DIGIT ZERO SPAN HOME POSITION SECURITY LEVEL SELECTION WHILE BUTTONS ARE PRESSED WHEN BUTTONS ARE RELEASED DISPLAYS CURRENT SECU...

Page 9: ...RELEASE SPAN UPON RELEASE SPAN SPAN UPON RELEASE SPAN TO UPDATE SECURITY AND SAVE MENU INCREMENT DIGIT SELECT DIGIT ZERO SPAN INCREMENT DIGIT SELECT DIGIT ZERO SPAN FPM OR M S BASED ON DIP SWITCH SET...

Page 10: ...TO UPDATE SECURITY AND SAVE MENU INCREMENT DIGIT SELECT DIGIT ZERO SPAN INCREMENT DIGIT SELECT DIGIT ZERO SPAN FPM OR M S BASED ON DIP SWITCH SETTING ADJUST FLOW OUTPUT HIGH INCREMENT DIGIT SELECT DI...

Page 11: ...Security Menu FROM UPDATE SECURITY AND SAVE MENU UPDATE SECURITY LEVEL ZERO ZERO ZERO SPAN SPAN SPAN SPAN ZERO SAVE CHANGES SPAN UPON RELEASE ZERO ZERO SPAN SPAN HOME POSITION...

Page 12: ..._____________________________________________________________________________________________________________ __________________________________________________________________________________________...

Reviews: