Dwyer Instruments A-435-A Installation And Operating Instructions Manual Download Page 2

Mode Selection / Digital Dampening Menu

From the home display, pressing the span and zero button simultaneously for 3 

seconds will access the Menu Security Level. If the level is set to 0 or 1, pressing and 

holding the span button for 3 seconds a second time will access the Mode Selection 

Menu. The display will default to Pressure when first powered up.  Pressing the zero 

button will cycle to Velocity and Flow. 

Once the desired Mode is displayed, pressing and holding the span button for three 

seconds will save the selected mode and display the digital dampening or averaging 

parameter. This parameter stabilizes the output and the display by averaging the 

readings. There are 2.5 readings taken each second and the user can select the 

number of seconds that they would like to average up to 240 seconds. The display and 

the output will continue to update at a rate of 2.5 updates per second, but the moving 

average is used for these updates.

PRESSURE MODE

Maximum Output Adjustment

If the Pressure Mode was selected, pressing and holding the span after adjusting the 

digital dampening will enter the Pressure Mode. In this menu, the maximum output 

pressure (

POH

) can be adjusted to any pressure between the lowest dip switch range 

to the highest dip switch range. If the dip switch settings are preferred over manually 

setting the range, the 

POH

 parameter can be set to off.

VELOCITY MODE

K-Factor Adjustment

If the Velocity Mode was selected, pressing and holding the span after adjusting the 

digital dampening will enter the Velocity Mode and the transmitter will display the 

engineering unit that has been selected by the dip switch. Pressing and holding the 

span button for three seconds will enter the K – Factor adjustment. The K – Factor 

can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing 

the span button to select the digit and pressing the zero button to increment the value 

of the digit. Pressing and holding the span button for three seconds will enter the 

Maximum Output Adjustment parameter.

Maximum Output Adjustment

The maximum output can be equivalent to a velocity or a pressure. After adjusting 

the K-Factor, the display will indicate if the adjustment is set for pressure or velocity.  

Pressing the zero button will toggle between the selections. Pressing and holding 

the span button for three seconds will enter the maximum output adjustment. The 

maximum output can be adjusted by pressing the span button to select the digit and 

pressing the zero button to increment the value of the digit. Pressing and holding the 

span button for three seconds will save this value and go to the Security Update Menu.

FLOW MODE

K-Factor Adjustment

If the Flow Mode was selected, pressing and holding the span after adjusting the digital 

dampening will enter the Flow Mode and the transmitter will display the engineering 

unit that has been selected by the dip switch. Pressing and holding the span button for 

three seconds will enter the K – Factor adjustment. The K – Factor can be adjusted 

between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button 

to select the digit and pressing the zero button to increment the value of the digit. 

Pressing and holding the span button for three seconds will enter the Area Adjustment 

parameter.

Area Adjustment

For Flow applications, the area is multiplied by the velocity to determine the volumetric 

air flow. The area will be listed in either feet or meters depending on the dip switch 

settings. The units will be indicated on the display at the time of adjustment.The area 

can be adjusted by pressing the span button to select the digit and pressing the zero 

button to increment the value of the digit. Pressing and holding the span button for 

three seconds will enter the Maximum Output Adjustment parameter.

Maximum Output Adjustment

The maximum output can be equivalent to a flow or a pressure. After adjusting the 

Area parameter, the display will indicate if the adjustment is set for pressure or flow.  

Pressing the zero button will toggle between the selections. Pressing and holding 

the span button for three seconds will enter the maximum output adjustment. The 

maximum output can be adjusted by pressing the span button to select the digit and 

pressing the zero button to increment the value of the digit. Pressing and holding the 

span button for three seconds will save this value and go to the Security Update Menu.

Security Update / Save Changes Menu

The Security Update Menu allows the security level to be set either higher or lower 

than the current security level setting. This security level will be displayed the next 

time the Menus are accessed from the home screen. Pressing the zero button cycles 

through the security levels. Pressing and holding the span button for three seconds 

accepts the new security level and gives the option to save all the menu changes. 

Pressing the zero button will toggle between yes and no. Yes will save the changes 

made to all menu items and no will discard all the changes made to all menu items. If 

the display is set to yes, pressing and holding the span will save the menu items and 

return the display to the Home Position.

FACTORY DEFAULT PROCEDURE

In order to reset all of the menu settings back to their factory programmed values, 

press and hold both the span and zero buttons simultaneously for 10 seconds until 

FACt

 is displayed on the LCD. Upon releasing the buttons, the unit will be factory 

defaulted. Since resetting the transmitter will wipe out all changes, it is necessary to 

zero (and possibly span) the transmitter before taking measurements.

MAINTENANCE/REPAIR

Upon final installation of the A-435-A, no routine maintenance is required. The A-435-A 

is not field serviceable and it is not possible to repair the unit. Field repair should not 

be attempted and may void warranty.

WARRANTY/RETURN

Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact 

customer service to receive a Return Goods Authorization number before shipping the 

product back for repair. Be sure to include a brief description of the problem plus any 

additional application notes.

APPENDIX I

Air Velocity / Air Flow Calculations

Velocity is calculated using the below equation:

   Velocity(fpm) = K-Factor x 4004.4 x √(Diff. Press. (in of w.c.)

Velocity in m/s is then calculated from the equation:

   Velocity(m/s) = Velocity(fpm) x 0.00508

Flow is calculated using the below equation:

  Flow(cfm) = Area(Ft

2

) x K-Factor x 4004.4 x √(Diff. Press. (in of w.c.)

  Flow (m

3

/h) = Flow (cfm) x 1.6992

APPENDIX II

Maximum Flow

Range 

in w.c.

Max Displayed Flow Max (K Factor x Area)

CFM

M

3

/H

CFM Mode M

3

/H Mode

0.5

5

28

5885000

5885000

5885000

9999000

9999000

9999000

2037.2

644.2

272.2

154.5

59.9

25.3

All manuals and user guides at all-guides.com

Summary of Contents for A-435-A

Page 1: ...ting This may be due to a sensor failure or incorrect pressure being applied Err1 The sensor is damaged rErr Negative display value too low to display PROGRAMMING MENUS Home Menu During normal operation the display will be in the Home Menu and will display the current measured pressure and the engineering units Menu Access Security While in the Home Menu press and hold the Zero and Span buttons si...

Page 2: ...parameter Area Adjustment For Flow applications the area is multiplied by the velocity to determine the volumetric air flow The area will be listed in either feet or meters depending on the dip switch settings The units will be indicated on the display at the time of adjustment The area can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the va...

Page 3: ...SELECTIONS SELECTIONS OR OR INCREMENTS INCREMENTS DIGITS DIGITS DISPLAY DISPLAY IS IS NOT NOT NECESSARY NECESSARY SEQUENCE SEQUENCE TO TO NEXT NEXT DIGIT DIGIT ACTIVE ACTIVE DIGIT DIGIT WILL WILL BLINK BLINK W W C C C C in in in in HOME HOME POSITION POSITION FACTORY FACTORY SETTINGS SETTINGS RESTORED RESTORED THEN THEN RETURNS RETURNS TO TO HOME HOME POSITION POSITION HOLD HOLD 7 7 SECONDS SECOND...

Page 4: ...AGING MENU MENU VELOCITY VELOCITY MODE MODE MENU MENU ADJUST ADJUST VELOCITY VELOCITY OUTPUT OUTPUT HIGH HIGH UPON UPON RELEASE RELEASE UPON UPON RELEASE RELEASE UPON UPON RELEASE RELEASE ZERO ZERO ZERO ZERO ZERO ZERO ZERO ZERO SPAN SPAN SPAN SPAN INCREMENT INCREMENT DIGIT DIGIT INCREMENT INCREMENT DIGIT DIGIT SELECT SELECT DIGIT DIGIT SELECT SELECT DIGIT DIGIT TO TO UPDATE UPDATE SECURITY SECURIT...

Page 5: ...IGIT INCREMENT INCREMENT DIGIT DIGIT SELECT SELECT DIGIT DIGIT SELECT SELECT DIGIT DIGIT TO TO UPDATE UPDATE SECURITY SECURITY AND AND SAVE SAVE MENU MENU o o K ADJUST ADJUST DISPLAY DISPLAY K K FACTOR FACTOR SELECT SELECT MAXIMUM MAXIMUM OUTPUT OUTPUT SET SET BY BY PRESSURE PRESSURE OR OR FLOW FLOW FPM FPM OR M S M S BASED BASED ON ON DIP DIP SWITCH SWITCH SETTING SETTING TO TO PoH PoH PRESSURE P...

Page 6: ...___________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ______...

Reviews: