Series 626 & 628 Pressure Transmitters

Specifications - Installation and Operating Instructions

Bulletin E-111

Pressure Ranges

Pressure
Range 

0-15 psia
15-0 psia
0-30 psia
0-50 psia
0-100 psia
0-200 psia
0-300 psia
0-5 psig
0-15 psig
0-30 psig
0-50 psig
0-100 psig
0-150 psig
0-200 psig
0-300 psig
0-500 psig
0-1000 psig
0-1500 psig
0-2000 psig
0-3000 psig
0-5000 psig
0-8000 psig

Over
Pressure

45 psia
45 psia
90 psia
150 psia
300 psia
600 psia
900 psia
50 psig
150 psig
300 psig
300 psig
500 psig
750 psig
1000 psig
1500 psig
2500 psig
5000 psig
5000 psig
5000 psig 
7500 psig
10000 psig
12000 psig

Maximum
Pressure

30 psia
30 psia
60 psia
100 psia
200 psia
400 psia
600 psia
10 psig
30 psig
60 psig
100 psig
200 psig
300 psig
400 psig
600 psig
1000 psig
2000 psig
3000 psig
4000 psig
6000 psig
7500 psig
10000 psig

CAuTION:

Do  not  exceed  specified  supply  voltage  ratings.

Permanent damage not covered by warranty will result. This device
is not designed for 120 or 240 volt AC operation. Use only on 13 to
30 VDC.

The  Series  626  and  628  Pressure  Transmitters 

converts  a  single  positive

pressure into a standard 4-20 mA output signal. The Series 626 and 628 can be
used  to  accurately  measure  compatible  gases  and  liquids;  Series  626  full  scale
accuracy  is  0.25%;  Series  628  full  scale  accuracy  is  1.0%  (see  specifications).
Designed  for  industrial  environments  with  a  NEMA  4X  (IP66)  housing,  this
transmitter resists most effects of shock and vibration. 

SPECIFICATIONS
Service:

Compatible gases and liquids.

Wetted Materials: 

Type 316 SS.

Accuracy: 

626: 0.25% FS, 0.20%

RSS; 628: 1.0% FS, 0.5% RSS; 626
absolute ranges: 0.5% FS, 0.35% RSS.
(Includes linearity, hysteresis, and
repeatability).

Temperature Limit: 

0 to 200°F (-18 to

93°C).

Compensation Temperature Range:

0 to 175° (-18 to 79°C).

Thermal Effect:

626: ±0.02% FS/°F.

628: ±0.04% FS/°F (includes zero and
span).

Pressure Limits: 

See table.

Power Requirements:

10-30 VDC (for

4-20 mA, 0-5, 1-5, 1-6 VDC outpus);
13-30 VDC (for 0-10, 2-10 VDC
outputs); 5 VDC ±0.5 VDC (for 0.5-4.5
VDC ratio-metric output).

Output Signal:

4-20 mA, 0-5 VDC,1-5

VDC, 0-10 VDC, or 0.5-4.5 VDC.

Response Time: 

300 ms.

Loop Resistance: 

0-1000 Ohms max.

R max = 50 (Vps-10) Ohms (4-20 mA
output), 5K Ohms (0-5, 1-5, 1-6, 0-10,
2-10, 0.5-4.5 VDC output).

Current Consumption: 

38 mA

maximum (for 4-20 mA output); 10 mA
maximum (for 0-5, 1-5, 1-6, 0-10, 2-10,
0.5-4.5 VDC output); 140 mA
maxumum (for all 626/628/629-CH with
optional LED).

Electrical Connections: 

Conduit

Housing (-CH): terminal block, 1/2˝
female NPT conduit; General Purpose
Housing (-GH): cable DIN EN 175801-
803-C.

Process Connection:

1/4˝ male or

female NPT and BSPT.

Enclosure Rating:

NEMA 4X (IP66).

Mounting Orientation: 

Mount in any

position.

Weight:

10 oz (283 g).

Agency Approvals:

CE.

INSTALLATION
1.  Location:

Select  a  location  where  the  temperature  of  the  transmitter  will  be

between 0 and 175°F (-18 to 79°C). Distance from the receiver is limited only by
total loop resistance. The tubing or piping supplying pressure to the unit can be
practically any length required but long lengths will increase response time slightly.

2. Position:

The transmitter is not position sensitive. However all standard models

are  originally  calibrated  with  the  unit  in  a  position  with  the  pressure  connection
downward.  Although  they  can  be  used  at  other  angles,  for  best  accuracy  it  is
recommended that units be installed in the position calibrated at the factory.

3. Pressure Connection:

Use a small amount of plumber’s tape or  other suitable

sealants  to  prevent  leaks.  Be  sure  the  pressure  passage  inside  the  port  is  not
blocked.

4. Electrical Connections
Wire Length 

-The maximum length of wire connecting the transmitter and receiver

is a function of wire size and receiver resistance. Wiring should not contribute more
than  10%  of  the  receiver  resistance  to  total  loop  resistance.  For  extremely  long
runs (over 1000 feet), choose receivers with higher resistance to minimize the size
and cost of connecting leads. Where wiring length is under 100 feet, wire as small
as 22 AWG can be used.

-CH Conduit Housing

LIQUID TIGHT FITTING

CORD DIAMETER RANGE

.200 to .350 (5.08 to 8.89)

1-9/32

[32.54]

2-15/16 [74.61]

OPTIONAL 1/4 NPT

FEMALE FITTING

3-1/2 [88.90]

1/4 NPT

MALE FITTING

3/4

[19.05]

1/4 NPT

5-1/2 [139.70]

1-3/32

[27.76]

-GH General Purpose Housing

7/8 [22.23]

HEX

1/4 NPT

2-27/64 [61.52]

3-13/64 [81.36]

055/64 [21.83]

 

   

   

www.

.com

[email protected]

1.800.561.8187