3  Getting Started 

3.1  Connecting TRT3x to a Test Object 

Before TRT3x has been connected to a test object (e.g. power transformer), the following steps have to be 

verified: 

•  The test object is disconnected from its circuit in accordance with the national safety regulations and 

is properly grounded to the protective earth. 

•  The transformer is completely de-energized. 
•  TRT3x  itself  should  be  properly  grounded.  To  do  this,  the  grounding  screw  on  the  top  of  TRT3x 

should be connected to PE using the provided grounding cable.

 

 

Note: 

Always  connect  measuring  cables  to  TRT3x  first  and  then  to  the  test  object  terminals. 
Additionally,  measuring  cables  can  be  connected  to  the  test  object  terminals  first,  but 
only if the test object terminals are grounded. 

 

When  disconnecting,  always  disconnect  cables  from  the  test  object  terminals  first  and 
then from  TRT3x. Additionally,  measuring  cables can be disconnected from  TRT3x first, 
but only if the test object terminals are grounded.

 

 

The grounding wire PE should be disconnected last. 

 

Not following these instructions may cause life-threatening situations. 

 

Cable test leads are terminated with the specially adjusted clips. The colors and markings of the test cables 

are shown in the Table 1. 

 

Table 1

Test lead colors and markings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If  the  primary  neutral  connection  does  not  exist,  the  1N  (H0;  N)  lead  should  be  left  isolated  from  the 

transformer (i.e. the test object) and from the other connection leads. It must be placed in such a way that it 

is completely isolated from other connections or earth. No personnel should be in a position to touch it!  

 

To maximize the accuracy and measurement repeatability, make sure all clamps have a good connection to 

the test object and avoid any crossing between the measuring cables. 

 

If the three-phase transformer has a tertiary winding,  it should be tested the same  way as  the secondary. 

The transformer is energized using  the high voltage windings. Test  leads 2U, 2V, 2W and 2N (X1, X2, X3 

and X0; a, b, c and n)

 

are in this case connected to the tertiary winding of the transformer. 

 

IEC Test 

Lead 

Marking 

ANSI 

Test Lead 

Marking 

Australian 

Test Lead 

Marking 

Transformer 

Terminal 

Voltage 

Test Lead 

Color IEC 

Australian 

Test Lead 

Colors 

Malaysian 

Test Lead 

Colors 

1N 

H0 

Neutral 

Blue 

Black 

Black 

1U 

H1 

High 

Red 

Red 

Red 

1V 

H2 

High 

Black 

White 

Yellow 

1W 

H3 

High 

Yellow 

Blue 

Blue 

2N 

X0 

Neutral 

Blue 

Black 

Black 

2U 

X1 

Low 

Red 

Red 

Red 

2V 

X2 

Low 

Black 

White 

Yellow 

2W 

X3 

Low 

Yellow 

Blue 

Blue 

Summary of Contents for TRT3 Series

Page 1: ...TRT3x THREE PHASE TRANSFORMER TURNS RATIO TEST INSTRUMENT Manual ...

Page 2: ... Message Malfunction 13 4 4 Error Message Error printer 13 4 5 Error Message Check paper 14 4 6 Error Message USB flash drive 14 4 7 Error Message Connect both neutral cables 14 4 8 Error Message Emergency Stop 14 4 9 Error Message Connections 15 5 Troubleshooting Guide 16 6 Customer Service 17 7 Packing the Instrument for Shipment 17 8 Technical Data 18 8 1 Mains Power Supply 18 8 2 Output data 1...

Page 3: ... in the Manual WARNING Warning indicates that potential hazard may occur CAUTION Caution indicates that potential damage may occur to the instrument or to the test object connected to the instrument Terms on the Device The following warning terms used in this document may appear on the device WARNING indicates that potential hazard may occur CAUTION indicates that potential damage may occur to the...

Page 4: ...ing connections particularly if a fault is suspected Before putting TRT3x into operation check the test set for any visible damage Do not operate TRT3x under wet or moist conditions condensation Do not operate TRT3x if explosive gas or vapors are present Only external devices that meet the requirements for SELV equipment according to EN 60950 or IEC 60950 should be connected to TRT3x through the s...

Page 5: ...be used for measurements in Measurement Category I CAT I for voltages up to 250V The device is also designed to withstand occasional transient overvoltage up to 1000Vpk WARNING AVERTISSEMENT This equipment is classified as measurement category I and must not be used within measurement category II III and IV Cet équipement est classée dans la I catégorie de mesure et ne doit pas être utilisé pendan...

Page 6: ...apply either three single phase test voltages in turns or a true three phase test voltage to the transformer primary windings Three induced voltages at the transformer s secondary side are measured Please note any use of TRT3x other than the ones described in this Manual are considered improper and will void the device warranty ...

Page 7: ...on TRT3x is separated from the mains power supply 2 Protective Earth Connector For protection against parasitic currents or voltages always connect TRT3x protective earth connector to the protective ground PE Use only the original cable For safety reasons always establish this connection before establishing any other connection and remove this connection as the very last step 3 Operator Control Di...

Page 8: ... be started Red LED Lights continuously in case of an operational error Lights continuously when a test is started and a test voltage is applied 4 H and X Terminals H cable terminal The terminal for connecting the H test cable X cable terminal The terminal for connecting the X test cable 5 Emergency Stop Turns off output voltage in case of an emergency 6 Interface and Flash Drive Connectors Interf...

Page 9: ... terminated with the specially adjusted clips The colors and markings of the test cables are shown in the Table 1 Table 1 Test lead colors and markings If the primary neutral connection does not exist the 1N H0 N lead should be left isolated from the transformer i e the test object and from the other connection leads It must be placed in such a way that it is completely isolated from other connect...

Page 10: ... hidden hidden Only true three phase test True 3 phase test using 3 phase voltage AUTO hidden hidden Autotransformer menu See the Table 4 Press ENTER to choose one of the available options in the configuration menu 1 If the vector group is selected TRT3x will perform both the true three phase test by applying true three phase test voltage and the phase by phase test by applying single phase test v...

Page 11: ...ratio deviation calculation is enabled the following menu is displayed to enter the name plate voltages and the tap changer positions If the name plate voltages are not entered TRT3x will perform the test and display the results but it will not calculate or display the turns ratio deviation After the name plate voltages and tap changer position s are entered press ENTER to confirm a selection The ...

Page 12: ...sition of the transformer Test Record can contain the results of all tap changer positions or the complete results obtained from one transformer Note Manual selection of record reading will delete results from the existing memory locations Once these parameters are defined pressing ENTER changes the status to the READY state If one of the values has to be changed press STOP to return to the previo...

Page 13: ... no connections errors found there may be a short circuit within the transformer itself 4 2 Error Message Turns ratio too low This message is displayed if the turns ratio of the transformer under the test is lower than 0 8 In this case the user should check whether H and X cables are misplaced reversed 4 3 Error Message Malfunction In the case of an internal error TRT3x will display the massage Ma...

Page 14: ...7 Error Message Connect both neutral cables If one of the neutral cables is not connected to the autotransformer during the AVGD test this message will be displayed User needs to connect both neutral cables to avoid this message 4 8 Error Message Emergency Stop This message is displayed when the Emergency stop button on the front panel of the device is pressed Release the Emergency stop button by ...

Page 15: ...ge Connections The Connections is displayed if the H or X cables are not connected properly to TRT3x There are also green LED lights next the connectors that lights up to indicate these connectors are connected properly Figure 4 9 Error message Connections ...

Page 16: ...rform the test three four times using each test voltage Save all results 2 Connect the shorted primary and secondary cables clamps of TRT3x instrument to the primary side of the transformer as shown in the figure below Perform the test three four times using each test voltage Save all results 3 Take the secondary cables clamps of TRT3x instrument from the primary side of the transformer and connec...

Page 17: ... busy telephone lines do not delay the response 7 Packing the Instrument for Shipment Prior to sending the instrument to DV Power for servicing please contact the DV Power Customer Service at Local support Sweden 46 8 731 78 24 International support 46 70 0925 000 E mail support dv power com for the return instructions Note DV Power is not responsible for any damage during shipping Please carefull...

Page 18: ... resolution 5 digits Typical turns ratio accuracy 0 8 999 0 05 1000 3999 0 05 4000 15000 0 1 80 or 100 V AC 0 8 999 0 05 1000 3999 0 1 4000 15000 0 2 40 V AC 0 8 999 0 05 1000 3999 0 1 4000 15000 0 2 8 or 10 V AC 0 8 999 0 05 1000 1999 0 1 1 V AC Guaranteed turns ratio accuracy 0 8 999 0 125 1000 3999 0 125 4000 15000 0 25 80 or 100 V AC 0 8 999 0 125 1000 3999 0 25 4000 15000 0 5 40 V AC 0 8 999 ...

Page 19: ...Maximum relative humidity 95 non condensing 8 5 Dimensions and Weight Dimensions W x H x D 480 x 197 x 395 mm 18 9 x 7 75 x 15 55 in Weight 8 kg 17 5 lbs 8 6 Applicable Standards Installation overvoltage category II Pollution degree 2 Safety LVD 2006 95 EC CE Conform Standard EN 61010 1 2001 EMC Directive 2004 108 EC CE Conform Standard EN 61326 1 2006 ...

Page 20: ...le 3 m 3 connection with TTA clamps HC 03 03MCWC X winding test cable 3 m 3 connection with TTA clamps XC 03 03FCWC H winding test cable 10 m 3 connection with TTA clamps HC 10 03MCWC X winding test cable 10 m 3 connection with TTA clamps XC 10 03FCWC H winding test lead 3 m 1 connection with TTA clamps HC 03 01MCWC X winding test lead 3 m 1 connection with TTA clamps XC 03 01FCWC H winding test l...

Page 21: ...urate and up to date as possible IBEKO Power AB assumes no responsibility for errors or omissions or for damages resulting from the use of the information contained herein IBEKO Power AB cannot take over liability resulting in any way from the use of this document or parts thereof The product information pictures drawings and all technical data contained within this manual are not contractually bi...

Reviews: