13
RMO500 Getting Started
6.7 Duty Cycles
During tests, RMO500 generates a high DC current that heats up the test set. To
prevent RMO500 from overheating, certain duty cycles apply depending on the
used test current.
S i n g l e T e s t
Test current
(A)
Cooling time between
first 4 tests (sec)
Cooling time after
4 tests (sec)
10
20
50
100
200
0 0
300 5 20
400 10 40
500 30 90
C o n t i n u o u s T e s t
Test current
(A)
Maximal test
duration
time (sec)
Cooling time
between tests (sec)
10
20
50
100
300 0
200 150 150
300 60 300
A built-in control prevents these cooling times from being skipped. If you try to
start a test within the cooling period, the display shows "Wait" and a timer counting
down. After the cooling period has elapsed, start the test using the set test
parameters by pressing the
Ω
button.Cooling of RMO500 is supported by a built-in
fan that is automatically activated every time a test is started from the
Test
menu. It
continues running 5 minutes after the test is finished.
Table 6-11:
Cooling time
between
single
tests
Table 6-12:
Cooling time
between
continuous
tests