Add oil

The generator requires engine oil to operate properly. The generator, when new from the package, 
contains no oil in the crankcase

*

. You must add the proper amount of oil before operating the 

generator for the first time. This amount is equal to the oil capacity of the engine crankcase:

WARNING:

 

Do not apply engine oils with additives or 2-stroke gasoline engine oils.

 They don’t 

have enough lubrication and may shorten the engine’s service life.

a. 

Make sure the generator is on a level surface.

b. 

Unscrew the oil filler/dipstick cap from the engine.

c. 

Using a funnel, add the appropriate amount of oil  

 

into the crankcase. You will know the crankcase is  

 

full when the oil level has reached the lower lip of  

 

the opening you have just poured the oil into.

d. 

Replace the oil filler cap.

Step 4 - Adding Oil

Engine oil recommended: SAE 10W-30.

 Viscosity varies with 

regions and temperatures. Choose your oil viscosity using the 

chart to the left.

* A small amount of oil from factory testing may be present on 

arrival.

WARNING

: DO NOT overfill the crankcase. This 

may damage the motor and shorten the overall 

life of your generator.

Model Number

XP13000X

Engine Oil Capacity

40.58 fl. oz. (1.2L)

Summary of Contents for XP13000X

Page 1: ...stomer Care Team Toll Free 8 5 pm PST Mon Fri 844 DUROMAX This manual provides information regarding the operation and maintenance of these products We have made every effort to ensure the accuracy of the information in this manual We reserve the right to change this product at any time without prior notice ...

Page 2: ......

Page 3: ...asoline 30 Starting the Generator Using Recoil Start 32 Starting the Generator 3 Generator Components 16 Package Contents 18 Packing Braces 19 Wheel Kit Installation 20 Connect the Battery 22 Adding Oil 23 Adding Gasoline 24 Grounding the Generator 25 High Altitude Operation 25 Generator Setup 4 AC Usage 36 Connecting a Load to the Generator 38 Using the Digital Multimeter 40 Using the Generator 2...

Page 4: ...48 Spark Plug Maintenance 50 Emptying the Gas Tank 52 Cleaning the Fuel Filter Cup 54 Storage and Transportation 55 Specifications 56 66 Basic Troubleshooting 58 Changing Inspecting the Carbon Brushes 59 Changing Inspecting the AVR 61 Wiring Diagram 64 Maintenance and Care Warranty Troubleshooting 9 70 Contact Information ...

Page 5: ......

Page 6: ...aily lives Inevitability when disaster strikes and we are left without power for a prolonged period of time our way of life is put at risk This is by far the most critical time for reliable portable power DUROMAX FOR WORK On the job site portable power allows you the ability to get work done in remote locations when traditional power sources are usually unavailable Equipment like table saws sander...

Page 7: ... we are committed to Powering Everyone Anywhere STOP Please do not return to the store DuroMax representatives are ready to help you with any questions concerns or issues about your new product We can guide you through assembly start up and how to operate your new generator We want you to be able to put your new generator to use right away CALL US BEFORE YOU CONSIDER RETURNING THE PRODUCT 1 844 DU...

Page 8: ...st can exceed 150 F 65 C Do not touch hot surfaces Pay attention to warning labels on the generator denoting hot parts of the machine Allow generator to cool several minutes after use before touching engine or areas which heat during use The safety alert symbol is used with one of the safety words DANGER CAUTION or WARNING to alert you of hazards Please pay attention to these hazard notices both i...

Page 9: ...off position and disconnect the spark plug WARNING This generator produces a powerful voltage which can result in electrocution ALWAYS ground the generator before using it see the Grounding the Generator portion of the PREPARlNG THE GENERATOR FOR USE The generator should only be plugged into electrical devices either directly or with an extension cord NEVER connect to a building electrical system ...

Page 10: ...bove safety notices please familiarize yourself with the safety and hazard markings on the generator GENERAL SAFETY PROCEDURES DANGER DO NOT OVERFILL THE GAS TANK OVERFILLING CAN RESULT IN A FIRE EXPLOSION OR DEATH 1 5 10 ...

Page 11: ...DON T TOUCH CAUTION HIGH TEMPERATURE DANGER HOT EXHAUST KEEP SAFE DISTANCE DON T TOUCH BURN RISK CARBON MONOXIDE SAFE DISTANCE GENERAL SAFETY PROCEDURES 11 ...

Page 12: ...detector for your home the CO Alert tests the air for to keep you safe and healthy CO Detected If dangerous carbon monoxide levels are detected Generators are convenient but they can also be dangerous All fuel burning appliances and equipment release a poisonous gas called carbon monoxide Carbon monoxide also known as CO can be dangerous for humans and pets even in small amounts because it blocks ...

Page 13: ...utely mandatory to keep your family safe from carbon monoxide But there s even more you can do By educating yourself about all carbon monoxide risks you ll be better prepared to protect your family from this colorless odorless threat Visit takeyourgeneratoroutside com for more information ...

Page 14: ...________ Serial Number _____________________________________________ A purchase receipt may be necessary for warranty parts or service in the future If you have a paper receipt staple it here for easy reference If you purchased the unit online save the email receipt where you can access it and record your details here for convenience in the future Purchase Date ____________________________________...

Page 15: ...GENERATOR SETUP Proper setup of your generator will get you going as soon as possible while making sure you and your equipment are safe and cared for 15 ...

Page 16: ...tal 8 3 gallon gasoline fuel tank 5 Power Panel Contains the start switch plugs meters and circuit breakers 6 Handles Longest handles of any DuroMax model allow easy movement across any surface 7 Battery 12V DC battery that powers the electric start system 8 Oil Fill and Dipstick Use to add or check the oil 9 Engine Switch 3 Position switch to Start Run or turn Off the generator 10 Charging Light ...

Page 17: ...lays voltage hertz and time running 16 CO Alert Shuts down the engine in the event of CO buildup 17 120 240V 4 Prong Receptacle Use to connect electrical devices that run 120 or 240 volt 60Hz single phase AC current NEMA 14 50 18 120 240V 4 Prong Twist Lock Use to connect electrical devices that run 120 or 240 volt 60Hz single phase AC current NEMA L14 30 19 120v 3 Prong GFCI Receptacle Use to con...

Page 18: ...rew Driver Oil Funnel w hose Spanner Spark Plug Wrench Plug Ends Phillips and slot blade screwdriver used for generator maintenance Used to add oil to the generator without messy spills Assorted wrenches used in generator maintenance and assembly 10mm 12mm 13mm 15mm and 17mm 19mm Used in spark plug maintenance inspection and installation Plug heads for the receptacles found on the generator are in...

Page 19: ...EVER Attempt this if you have put fuel or oil in the generator 1 Step 1 Remove Shipping Braces Remove braces The shipping braces prevent engine movement during shipment Flip the generator over and remove the brightly colored braces between the motor and the frame and the wood brace under the generator 2 19 Note Shipping braces can be thrown away They will not be needed again ...

Page 20: ...lation Optional Install wheels a Place the wheels onto the axles 4 Install wheel axles a Place the smallest washer onto the wheel axle bolts b Insert wheel axle bolts through the frame and secure with the provided nut and wrenches 2 Install inside wheel washers a Place one of the large washers onto the axles 3 20 ...

Page 21: ...e brackets on the frame using the provided bolts and nuts Do not overtighten the handles it will prevent free movement 7 Install cotter pins a Place the cotter pin through the hole at the end of the axle and bend it out to secure the wheel 6 Flip Over a Flip the assembled generator over onto its wheels and support brackets 8 ...

Page 22: ...ove and behind the battery One side is connected to ground and the other end needs to be connected to the battery b Route the free end to the negative battery terminal 2 Connect the negative cable a Push the black rubber boot up the wire to expose the connector b Securely connect the free end of the battery cable to the negative battery terminal using the screw and nut from the battery with the sc...

Page 23: ...service life a Make sure the generator is on a level surface b Unscrew the oil filler dipstick cap from the engine c Using a funnel add the appropriate amount of oil into the crankcase You will know the crankcase is full when the oil level has reached the lower lip of the opening you have just poured the oil into d Replace the oil filler cap Step 4 Adding Oil Engine oil recommended SAE 10W 30 Visc...

Page 24: ...ns smoothly use only FRESH UNLEADED GAS WITH AN OCTANE RATING OF 87 OR HIGHER Never use an oil gasoline mixture Never use old gas Avoid getting dirt or water in the fuel tank Gas can age in the tank and make it hard to start up the generator in the future Never store generator for extended periods of time with fuel in the tank DANGER DO NOT OVERFILL THE GAS TANK OVERFILLING CAN RESULT IN A FIRE EX...

Page 25: ...at differs from that at which this engine was certified for extended periods of time may increase emissions High altitude performance can be improved by specific modifications to the carburetor If you always operate your generator at altitudes above 3 000 feet 900 meters have a dealer perform this carburetor modification This engine when operated at high altitude with the carburetor modifications ...

Page 26: ...26 ...

Page 27: ...e are still steps you should take to prepare it for operation each time you use it IMPORTANT At this point you should be familiar with the procedures described in the first portion of this section entitled GENERATOR SETUP If you have not yet read this section go back and read it now ...

Page 28: ...e oil filler dipstick cap c With a dry cloth wipe the oil off of the stick on the inside of the cap d Insert the dipstick as if you were replacing the cap and then remove it again There should now be oil on the stick If there is no oil on the stick or oil only at the very end of the stick you should add oil until the engine crankcase is filled see Adding Oil portion of the Maintenance section e Be...

Page 29: ...he Gas Level Optional DANGER DO NOT OVERFILL THE GAS TANK OVERFILLING CAN RESULT IN A FIRE EXPLOSION OR DEATH 1 5 WARNING Gasoline and gasoline fumes are highly flammable Do not fill the tank near an open flame Always allow the engine to cool for several minutes before refueling DO NOT overfill the fuel tank Fuel expands when shaken or heated ALWAYS leave 11 2 space or more at the top of the tank ...

Page 30: ... main power panel Turn the switch ON to allow power to the push button start 3 Turn idle control OFF The idle control is located on the top center of the main power panel Turn the switch OFF to prevent the unit from trying to idle down before the engine is warmed up 2 Starting the Generator Using Gasoline Start the Generator The push button start is located on the left side of the main power panel...

Page 31: ... The breaker is located on the right side of the front power panel Flip the breaker up to allow the power to flow to the receptacles Connect your devices to the receptacles on the front panel Start with the largest loads first 7 ...

Page 32: ... switch is located on the top center of the main power panel Turn the switch ON to allow power to the push button start The choke lever is located above the air filter to the left of the recoil start Slide the lever to the right to cut the air supply and allow more gas into the engine to start 3 Turn idle control OFF 4 The idle control is located on the top center of the main power panel Turn the ...

Page 33: ...choke left to the OPEN position as the engine warms up 6 Turn breaker ON Connect The breaker is located on the right side of the front power panel Flip the breaker up to allow the power to flow to the receptacles Connect your devices to the receptacles on the front panel Start with the largest loads first 7 CAUTION Release the recoil handle only after the cord has retracted Releasing the recoil ha...

Page 34: ...34 ...

Page 35: ... still steps you should take to prepare it for operation each time you use it IMPORTANT At this point you should be familiar with the procedures described in the first portion of this section entitled GENERATOR SETUP If you have not yet read this section go back and read it now 35 ...

Page 36: ... each electrical device add these numbers to find the total rated wattage you wish to draw from the generator If this number exceeds the rated wattage of the generator DO NOT connect all these devices Select a combination of electrical devices which has a total rated wattage lower than or equal to the rated wattage of the generator 36 You may connect electrical devices running on AC current accord...

Page 37: ...ectric drill 600 900 Television 500 0 Deep freezer 500 800 Garage door opener 480 600 Stereo 400 0 Box fan 300 600 Clock radio 300 0 Security system 180 0 DVD player 100 0 Common light bulb 75 0 CAUTION The generator can only run at its surge wattage capacity for a very short time Connect only electrical devices requiring a rated running wattage equal to or less than the rated wattage of the gener...

Page 38: ...s can ONLY be connected to the 240V receptacle Plug in devices Turn breaker on Turn on connected devices Plug in devices to the appropriate receptacle When using the generator balance the load as closely as possible Placing more load on one side of the circuit will reduce the breaker trip period Flip the circuit breaker up to the ON position to allow power to the receptacles Start or turn on appli...

Page 39: ...ble below for recommended cords based on the power requirement of the electrical device DEVICE REQUIREMENTS WIRE GAUGE BY LENGTH ft AMPS WATTS 120 240V 10 25 50 100 150 5 600 1200 18 16 14 12 10 10 1200 2400 16 14 12 12 10 15 1800 3600 14 14 12 12 10 20 2400 4800 12 12 12 10 10 25 3000 6000 12 10 10 10 8 30 3600 7200 10 10 10 8 NR 40 4800 9600 8 8 6 6 NR 50 6000 12000 6 6 6 NR NR NR NOT RECOMMENDE...

Page 40: ...oduced by the generator in volts Frequency The frequency currently produced by the generator in Hz Hours Run The number of hours the engine has currently been running When the generator is started the display will read the current voltage Press the MODE button to cycle through the multimeter functions ...

Page 41: ...41 Hours Total The number of hours the generator has been run in total 4 ...

Page 42: ...42 ...

Page 43: ...r maintenance and storage are essential to ensure trouble free use of your generator when you need it By following the maintenance and care requirements you can keep your generator running smoothly and efficiently for years to come ...

Page 44: ...LACE SPARK ARRESTOR CLEAN IDLE SPEED CHECK ADJUST VALVE CLEARANCE CHECK ADJUST COMBUSTION CHAMBER CLEAN 500 HOURS FUEL TANK FILTER CLEAN FUEL TUBE CHECK EVERY 24 MO REPLACE IF NECESSARY TO BE PERFORMED AT MONTHS INDICATED OR HOUR INTERVAL WHICHEVER COMES FIRST 44 WARNING Improper maintenance or failure to correct a problem before operation can cause a malfunction in which you can be seriously inju...

Page 45: ...MAINTENANCE LOG Date Generator Hours Maintenance Performed 45 ...

Page 46: ...a Make sure the generator is on a level surface b Unscrew the oil filler dipstick cap c With a dry cloth wipe the oil off of the stick on the inside of the cap d Insert the dipstick as if you were replacing the cap and then remove it again There should now be oil on the stick If there is no oil on the stick or oil only at the very end of the stick you should add oil until the engine crankcase is f...

Page 47: ... contaminated with water or dirt Using a 12mm hex wrench unscrew the oil drain plug which is located on the crankcase underneath the oil filler dipstick cap Allow all the oil to drain from the generator Drain oil Drain oil into an approved oil disposal container Contact your local auto parts store for information on oil disposal Replace drain plug Replace the oil drain plug and tighten with a 12mm...

Page 48: ...e may cause less air to enter the engine or dirty air to enter the engine causing overheating and engine wear MAINTENANCE AND CARE CONTINUED Cleaning the Air Filter Remove the filter cover screw Remove filter cover Clean out filter casing Remove the filter cover screw Remove the filter cover and the sponge like element from the casing Wipe the dirt from inside the empty air cleaner casing ...

Page 49: ...sing Attach the cover Washcleanerelement Wash the sponge like elements in household dish detergent and warm water Drycleanerelement Pat on a dry cloth and allow the elements to dry completely Addengineoiltoelements Soak the dry elements in a small amount of engine oil Wring out any excess oil ...

Page 50: ...er maintenance may cause reduced fuel economy misfires trouble starting or damage to the spark plug threads Spark Plug Maintenance Remove spark plug cap Removesparkplug Inspectsparkplug Pull on the spark plug cap to remove it Unscrew the spark plug from the generator using the spark plug wrench included with this product Visually inspect the spark plug MAINTENANCE AND CARE CONTINUED ...

Page 51: ...d discard and replace it with a new spark plug We recommend using an F7RTC spark plug such as NGK BP6ES Install spark plug Replace spark plug cap Screw the spark plug back into its place on the generator using the spark plug wrench Replace the spark plug cap ...

Page 52: ...e fuel filter cup of any fuel 1 2 3 CAUTION Do not store fuel from one season to another Gasoline sold at the pump today contains additives such as ethanol that even when stored properly may damage the fuel system components If you have been using gasoline in your generator before storing your generator for extended periods of time you should drain your generator fuel tank of gasoline MAINTENANCE ...

Page 53: ...lve to the ON position Drain all the gas from the generator 4 Shut fuel valve off Replace fuel filter cup Store emptied gas Turn the fuel valve to the OFF position Reinstall the fuel filter cup Store the emptied gasoline in a suitable place and add fuel stabilizer to keep fuel fresh and usable 5 6 7 53 ...

Page 54: ...ve to the OFF position 1 Cleaning the Fuel Filter Cup Remove fuel filter cup Clean filter cup Replace fuel filter cup Unscrew the fuel filter cup from the fuel valve using a wrench Clean the cup of all sediment using a rag or brush Reinstall the fuel filter cup 2 3 4 54 ...

Page 55: ...to run 3 5 minutes 3 Turn off the fuel valve 4 Allow the unit to stall out 5 Turn off the engine switch 6 Add fuel stabilizer to the gas remaining in the tank 7 Store If you do not plan to start the unit for longer than 30 days 1 Turn off the main breaker 2 Allow the unit to run 3 5 minutes 3 Turn off the fuel valve 4 Allow the unit to stall out 5 Turn off the engine switch 6 Drain the fuel tank S...

Page 56: ...edFrequency 60 Hz AC Phase Single Dimensions LENGTH 28in WIDTH 22in HEIGHT 23in Engine Type 4 Stroke OHV Forced Air Ignition System Non Contact Transistor Displacement 500cc Starting Type Electric Recoil Fuel Tank Capacity 8 3 US Gal 31L Oil Capacity 40 58 fl oz 1 2L Run Time 50 Gasoline 8 hr Noise Level 74db 56 ...

Page 57: ...TROUBLESHOOTING This section of the manual is to help you troubleshoot problems with your generator 57 ...

Page 58: ...vel Move the generator to a level surface Oil is low Add change the oil Engine runs but there is no electrical output The circuit breaker is OFF Turn ON circuit breaker Wiring connection is bad Replace extension cord s Device connected to generator is malfunctioning Disconnect malfunctioning device The generator runs but does not support all electrical devices connected Generator is overloaded Dis...

Page 59: ...or The carbon brushes are wearable parts and should be inspected every 250 running hours Remove generator cover Remove bolt from brush Disconnect AVR wires Remove the 2 bolts of the generator cover Pull off the cover Remove the bolt holding the carbon brush Remove the two wires from the AVR on the carbon brush 1 2 3 59 ...

Page 60: ...h Install new carbon brush with bolt 4 Connect AVR wires Insert and connect the 2 wires from the AVR be sure to connect and correctly 5 6 Replace generator cover Replace the back cover of the generator and secure it with the 2 bolts TROUBLESHOOTING CONTINUED 60 ...

Page 61: ...he generator If the generator is overheated or overloaded the AVR may be damaged and require replacement Remove generator cover Remove AVR bolts Disconnect AVR wire clip Remove the 2 bolts of the generator cover Pull off the cover Remove the 2 bolts holding the AVR Disconnect the wire clip 1 2 3 61 ...

Page 62: ... Remove the 2 wires from the AVR on the carbon brush 4 Install new AVR Install the new AVR with the 2 bolts 5 6 Reconnect wires to brush Insert and connect the 2 wires from the AVR Make sure to connect and correctly Changing Inspecting the AVR Continued TROUBLESHOOTING CONTINUED 62 ...

Page 63: ...Replace generator cover Replace the back cover of the generator and secure it with the 2 bolts 8 63 ...

Page 64: ...WIRING DIAGRAM 64 ...

Page 65: ...65 ...

Page 66: ...RESSED OR IMPLIED U S FEDERAL AND CALIFORNIA EMISSIONS CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The U S Environmental Protection Agency EPA California Air Resources Board and DuroMax Power Equipment are pleased to explain the emissions control system s warranty on your 2021 2022 small off road engine In California new small off road engines must be designed built and equippe...

Page 67: ...warranty repairs shall be completed in a reasonable amount of time not to exceed 30 days If you have any questions regarding your warranty coverage contact us at 844 387 6629 or email support duromaxpower com DEFECTS WARRANTY REQUIREMENTS The warranty period begins on the date the engine or equipment is delivered to an ultimate purchaser and extends for a period of Two Years GENERAL EMISSIONS WARR...

Page 68: ...cturer distribution centers that are franchised to service the subject engines 6 The owner must not be charged for diagnostic labor that leads to the determination that a warranted part is in fact defective provided that such diagnostic work is performed at a warranty station 7 The manufacturer is liable for damages to other engine components proximately caused by a failure under warranty of any w...

Page 69: ...ols 7 Traps filters precipitators and any other device used to capture particulate emissions 8 Electronic controls 9 Vacuum temperature and time sensitive valves and switches 10 Hoses belts connectors and assemblies Evaporative Emission Warranty Part List 1 Fuel Tank 2 Fuel Cap 3 Fuel Line for liquid fuel and fuel vapors 4 Fuel Line Fittings 5 Clamps 6 Pressure Relief Valves 7 Control Valves 8 Con...

Page 70: ...ors are your lifeline in the event of an emergency Should you have any problems please contact our customer service department DUROMAX POWER EQUIPMENT 5800 Ontario Mills Parkway Ontario CA 91764 Customer Service 844 DUROMAX Customer Service Hours 8 5 pm PST Website www duromaxpower com Email customerservice duromaxpower com ...

Page 71: ......

Page 72: ...5800 Ontario Mills Parkway Ontario CA 91764 United States 844 DUROMAX REV XP13000X 07302021 ...

Reviews: